Technical_reference - 第103页
Technical Service Manual 103 Revision Dat e: August 2004 mounting pin. Plug the control cable of the new actuator to the contr ol box. Tur n power on to the oven so the actuator c an be operated. Perfor m the ac tuator s…

Technical Service Manual 102 Revision Date: August 2004
REPLACING THE ACTUATOR ASSEMBLY WITH THE BONNET IN THE CLOSED POSITION:
Remove the bonnet bridge sheet metal piece on the end of the oven where the actuator will be changed.
The body of the actuator is accessed through the equipment cabinets on each end of the oven.
Carefully raise the actuator and position it in its frame location. Use the mounting pin to lock the piston in place in the
bracket. As you are pushing the mounting pin into place, install the locking shaft collars on each side of the piston.
Replace the two safety clips on the mounting pin. Let the actuator hang from the mounting pin.
Carefully position the actuator so that the holes for the actuator pivot pin are aligned with the holes in the side of the
actuator sheet metal. Insert the actuator pivot pin. As you are pushing the mounting pin into place, install the locking
shaft collars on each side of the piston. Replace the two safety clips on the mounting pin. Let the actuator hang from the

Technical Service Manual 103 Revision Date: August 2004
mounting pin.
Plug the control cable of the new actuator to the control box. Turn power on to the oven so the actuator can be operated.
Perform the actuator set-up and synchronization at this time.
The installation procedure is the reverse of the removal procedure.
SET-UP AND SYNCHRONIZATION OF THE LINAK ACTUATORS:
The actuators are installed and synchronized on the oven when it is built.
Caution Notes:
The following process is used for two or three actuators on the same oven, and is required only after replacement of an
actuator or control box, or if an actuator is out of adjustment.
1. Do not turn the spindle while the actuator is plugged into the actuator control box. This will send
erroneous pulses to the control box causing misalignment and possible damage to the system. For initial factory
set-up or field replacement, the spindle may be turned no more than three revolutions to align the clevis pin hole
to the bracket. This must only be done when the actuator is unplugged from the control box.
2. Do not unplug the actuator from the control box during operation or in an attempt to adjust or synchronize the
actuators. This will cause misalignment resulting in possible damage to the system.
3. Raising or lowering one side of the heat zone more than the prescribed distance may cause structural damage to
the system.

Technical Service Manual 104 Revision Date: August 2004
TWO ACTUATOR SYSTEM
The following initialization procedure applies to a two actuator system and requires two people to complete it:
1. With the bonnet in the down position and the actuators properly connected mechanically and electrically, raise the
heat zone no more than 1".
2. Disconnect the power to the control box by shutting off the circuit breaker (F52) for at least 5 seconds.
3. On the operator control panel, turn the Hood selector switch to the DOWN position and hold while reconnecting
the main power to the actuator control box. Listen for a buzzing sound coming from the control box. At this point
the hood selector switch will activate the LEFT actuator and lower the heat zone on that side.
4. Keep the hood selector switch engaged making sure the left actuator pulls the main heat zone down tightly
against the lower channel, then release the hood selector switch.
5. Disconnect the power to the control box again by shutting off circuit breaker (F52) for at least 5 seconds
6. On the operator control panel, and turn the hood selector switch to the UP position and hold while reconnecting
the main power to the actuator control box. Listen for a buzzing sound coming from the control box. At this point,
the hood selector switch has been used to activate the RIGHT actuator causing it to raise the heat zone on that
side. Once you notice the right side rising slightly, immediately turn the selector switch to the DOWN position and
lower the heat zone completely. Caution: Moving the heat zone any more than the prescribed distance may
cause structural damage to the system.
7. Keep the hood selector switch engaged making sure the right actuator pulls the main heat zone down tight
against the lower channel, and then release the hood selector switch.
8. Disconnect the power to the actuator control box again by shutting off circuit breaker (F52) for at least 5 seconds.
The initialization process is now complete.