Safety Precautions Safe-30 AKOE-ID [Door Check] Switches When the door is opened with the [OPERA TION/SET UP] switch set to the "OPERA TION" side, the switch is activated and an error condition is indicated. Wh…

100%1 / 211
Safe-29
AKOE-ID
Safety Precautions
Switch Name Symbol Countermeasures
[EMERGENCY STOP] Switch
(Front)
[EMERGENCY STOP] Switch
(Rear)
S10
S1
1
Pressing one of the [EMERGENCY STOP]
switches cuts power to the following modules.
All power sources for loads are shut off.
The power supply to the mechanisms of all
motor shafts and 24-voltage loads in the
solenoid system (SOL and SV) is shut off.
Note:
The control power supply for the
control boards, switches, and lamps
is excluded.
0704-002
Safety Precautions
Safe-30
AKOE-ID
[Door Check] Switches
When the door is opened with the [OPERATION/SET UP] switch set to the
"OPERATION" side, the switch is activated and an error condition is indicated.
When the switch is set to the "SET UP" side, this switch is not activated.
S12
S13
S12
S14
S13
Top View
Front View Rear View
Switch Name Symbol Countermeasures
[Door Check] Switch S12
S13
S14
When the door is opened, the following measures
are taken.
All power sources for loads are shut off.
The power supply to the mechanisms of all
motor shafts and 24-voltage loads in the solenoid
system (SOL
and SV) is shut off.
Note:
The control power supply for the control
boards, switches, and lamps is excluded.
0704-002
Safe-31
AKOE-ID
Safety Precautions
6. Precautionary Items for Correct Operations
Requirements for Installation
Be sure to fulfill the following requirements for safety purposes.
Overvoltage Category : Category
I
II
Pollution Degree : 3
Overvoltage Categories refer to the level of Impulse W
ithstand Voltage protection
provided at the specified Pollution Degree.
Category III: Primary circuits of a device to which power is directly
supplied from the power distribution panel, and circuits from
the distribution panel to outlets.
Note
The term was changed from "Installation Category" to "Overvoltage
Category".
"Pollution Degree" is a degree of pollution severity.
Pollution Degree 3: Conductive pollution or dry nonconductive pollution
that becomes conductive due to condensation occurs.
T
o be found in industrial environment or construction
sites (harsh environments).
0609-002