SEMI E54.8-0305 © SEMI 1999, 2005 11 Table 9 Controller Object Attribute Identifiers SEMI CDM Attribute ID PROFIBUS Index Attribute Detail/ A lternative Access Method CA16 80 Setpoint CA17 81 Process Variable CA18 82 Con…

SEMI E54.8-0305 © SEMI 1999, 2005 10
Table 6 Active Element Object Attribute Identifiers
SEMI CDM
Attribute ID
PROFIBUS
Index
Attribute Detail/
A
lternative
Access Method
nA1 65 Name
nA2 66 Status
nA3 67 Alarm Enable
nA4 68 Warning Enable
7.5.5 Sensor Attributes
7.5.5.1 The attributes of Sensors are mapped to Process data objects of PROFIBUS. These attributes are contained
in any Sensor-AI, Sensor-EI and Sensor-BI Object.
7.5.5.2 The Slot number used is the instance number in the device. The index is the numeric value of the Sensor
Attribute identifier with an offset of 64 (see Table 7).
Table 7 Sensor Object Attribute Identifiers
SEMI CDM
Attribute ID
PROFIBUS
Index
Attribute Detail/Alternative
Access Method
nA16 80 Value Can be mapped as Input
Data Object
nA17 81 Report Inhibit
Time
nA18 82 Enable Report
Rate
nA19 83 Report Rate
7.5.6 Actuator Attributes
7.5.6.1 The attributes of Actuators are mapped to Process data objects of PROFIBUS. These attributes are
contained in any Actuator-AO, Actuator-EO and Actuator-BO Object.
7.5.6.2 The Slot number used is the instance number in the device. The index is the numeric value of the Actuator
Attribute identifier with an offset of 64 (see Table 8).
Table 8 Actuator Object Attribute Identifiers
SEMI CDM
Attribute ID
PROFIBUS
Index
Attribute Detail/Alternative Access
Method
nA16 80 Setting Can be mapped as Output
Data Object
nA17 81 Safe State
nA18 82 Watch Rate
nA19 83 Watch Dog The value of this variable
reflects the WD_Factor
parameter of PROFIBUS
7.5.7 Controller Attributes
7.5.7.1 The attributes of Controllers are mapped to Process data objects of PROFIBUS.
7.5.7.2 The Slot number used is the instance number in the device. The index is the numeric value of the Controller
Attribute identifier with an offset of 64 (see Table 9).

SEMI E54.8-0305 © SEMI 1999, 2005 11
Table 9 Controller Object Attribute Identifiers
SEMI CDM
Attribute ID
PROFIBUS
Index
Attribute Detail/
A
lternative
Access Method
CA16 80 Setpoint
CA17 81 Process Variable
CA18 82 Control Variable
CA19 83 Data Type
CA20 84 Data Unit
CA21 85 Alarm Settle Time
CA22 86 Alarm Error Band
CA24 88 Warning Settle Time
CA25 89 Warning Error Band
7.5.8 Sensor Analog Input Attributes
7.5.8.1 The attributes of Sensor Analog Inputs are mapped to Process data objects of PROFIBUS.
7.5.8.2 The Slot number used is the instance number in the device. The index is the numeric value of the Sensor
Analog Input Attribute identifier with an offset of 64 (see Table 10).
Table 10 Sensor Analog Input Object Attribute Identifiers
SEMI CDM
Attribute ID
PROFIBUS
Index
Attribute Detail/Alternative
Access Method
SaiA64 128 Offset
SaiA65 129 Gain
SaiA66 130 Data Type
SaiA67 131 Data Units
SaiA68 132 Safe State
SaiA69 133 Enable Report Delta
SaiA70 134 Report Delta
SaiA71 135 Enable Report ROC
SaiA72 136 Report ROC
SaiA73 137 Alarm Trip Point High
SaiA74 138 Alarm Trip Point Low
SaiA75 139 Alarm Hysteresis
SaiA76 140 Warning Trip Point High
SaiA77 141 Warning Trip Point Low
SaiA78 142 Warning Hysteresis
7.5.9 Sensor Binary Input Attributes
7.5.9.1 The attributes of Sensor Binary Inputs are mapped to Process data objects of PROFIBUS.
7.5.9.2 The Slot number used is the instance number in the device. The index is the numeric value of the Sensor
Binary Input Attribute identifier with an offset of 64 (see Table 11).

SEMI E54.8-0305 © SEMI 1999, 2005 12
Table 11 Sensor Binary Input Object Attribute Identifiers
SEMI CDM
Attribute ID
PROFIBUS
Index
Attribute Detail/Alternative
Access Method
SbiA64 128 Debounce Control
SbiA65 129 Alarm State
SbiA66 130 Warning State
7.5.10 Sensor Enumerated Input Attributes
7.5.10.1 The attributes of Sensor Enumerated Inputs are mapped to Process data objects of PROFIBUS.
7.5.10.2 The Slot number used is the instance number in the device. The index is the numeric value of the Sensor
Enumerated Input Attribute identifier with an offset of 64 (see Table 12).
Table 12 Sensor Enumerated Input Object Attribute Identifiers
SEMI CDM
Attribute ID
PROFIBUS
Index
Attribute Detail/Alternative
Access Method
SeiA64 128 Debounce Control
SeiA65 129 Alarm State
SeiA66 130 Warning State
7.5.11 Actuator Analog Output Attributes
7.5.11.1 The attributes of Actuator Analog Outputs are mapped to Process data objects of PROFIBUS.
7.5.11.2 The Slot number used is the instance number in the device. The index is the numeric value of the Actuator
Analog Output Attribute identifier with an offset of 64 (see Table 13).
Table 13 Actuator Analog Output Object Attribute Identifiers
SEMI CDM
Attribute ID
PROFIBUS
Index
Attribute Detail/
A
lternative
Access Method
AaoA64 128 Offset
AaoA65 129 Gain
AaoA66 130 Data Type
AaoA67 131 Data Units
7.5.12 Sensor Binary Input Threshold Attributes
7.5.12.1 The attributes of Sensor Binary Input Thresholds are mapped to Process data objects of PROFIBUS.
7.5.12.2 The Slot number used is the instance number in the device. The index is the numeric value of the Sensor
Binary Input Threshold Attribute identifier with an offset of 80 (see Table 14). The different mapping has to be
done because there is an Overlap to the Sensor Binary Input Attributes enumeration part.
Table 14 Sensor Binary Input Threshold Object Attribute Identifiers
SEMI CDM
Attribute ID
PROFIBUS
Index
Attribute Detail/Alternative
Access Method
SbithA64 144 Reading Valid
SbithA65 145 State
SbithA66 146 Status