semi合集-English.pdf - 第6786页

SEMI S2-0703a E © SEMI 1991, 2004 15 NOTE 41: With the exception of implementation of ground fault protection, shunt trip units that r e quire power to trip (actuate) are not recomm ended to be used in a safety control c…

100%1 / 7923
SEMI S2-0703a
E
© SEMI 1991, 2004 14
12.3 The emergency off button should be red and
mushroom shaped. A yellow background for the EMO
should be provided.
NOTE 37: Non-lockable self-latching (i.e., twist- or pull-to-
release) EMO buttons may be required by regulations.
12.4 All emergency off buttons should be clearly
labeled as “EMO,” “Emergency Off,” or the equivalent
and should be clearly legible from the viewing location.
The label may appear on the button or on the yellow
background.
12.5 Emergency off buttons should be readily
accessible from operating and regularly scheduled
maintenance locations and appropriately sized to enable
activation by the heel of the palm.
12.5.1 Emergency off buttons should be located or
guarded to minimize accidental activation.
12.5.2 No operation or regularly scheduled
maintenance location should require more than 3 m (10
feet) travel to an EMO button.
12.5.3 The person actuating or inspecting the EMO
button should not be exposed to serious risks of tripping
or falling or of coming in contact with energized
electrical parts, moving machinery, surfaces or objects
operating at high temperatures, or other hazardous
equipment.
12.6 See Section 13.5 for additional EMO guidelines
when EMOs are used with UPSs.
13 Electrical Design
13.1 This section covers electrical and electronic
equipment that use hazardous voltages.
13.2 Types of Electrical Work — The following are the
four types of electrical work defined by this guideline:
Type 1 — Equipment is fully deenergized.
Type 2 — Equipment is energized. Energized circuits
are covered or insulated.
NOTE 38: Type 2 work includes tasks where the energized
circuits are or can be measured by placing probes through
suitable openings in the covers or insulators.
Type 3 — Equipment is energized. Energized circuits
are exposed and inadvertent contact with uninsulated
energized parts is possible. Potential exposures are no
greater than 30 volts rms, 42.4 volts peak, 60 volts dc or
240 volt-amps in dry locations.
Type 4 — Equipment is energized. Energized circuits
are exposed and inadvertent contact with uninsulated
energized parts is possible. Potential exposures are
greater than 30 volts rms, 42.4 volts peak, 60 volts dc,
or 240 volt-amps in dry locations. Potential exposures
to radio-frequency currents, whether induced or via
contact, exceed the limits in Table A5-1 of Appendix 5.
13.3 Energized Electrical Work — The supplier should
design the equipment to minimize the need to calibrate,
modify, repair, test, adjust, or maintain equipment
while it is energized, and to minimize work that must
be performed on components near exposed energized
circuits. The supplier should move as many tasks as
practical from category Type 4 to Types 1, 2, or 3.
Routine Type 4 tasks, excluding troubleshooting,
should have specific written instructions in the
maintenance manuals. General safety procedures (e.g.,
wearing appropriate Personal Protective Equipment and
establishing barriers) for troubleshooting, including
Type 4 work, should be provided.
13.4 Electrical Design — Equipment should conform
to the appropriate international, regional, national or
industry product safety requirements.
13.4.1 Nonconductive or grounded conductive physical
barriers should be provided:
Where it is necessary to reach over, under, or
around, or in close proximity to hazards.
Where dropped objects could cause shorts or
arcing.
Where failure of liquid fittings from any part of the
equipment would result in the introduction of
liquid into electrical parts.
Over the line side of the main disconnect.
Where maintenance or service tasks on equipment
in dry locations are likely to allow inadvertent
contact with uninsulated energized parts containing
either: potentials greater than 30 volts rms, 42.4
volts peak, or 60 volts dc; or power greater than
240 volt-amps.
NOTE 39: A dry location can be considered to be one that is
not normally subject to dampness or wetness.
NOTE 40: Removable nonconductive and noncombustible
covers are preferred.
13.4.2 Where test probe openings are provided in
barriers, the barriers should be located, and the probe
openings should be sized, to prevent inadvertent contact
with adjacent energized parts, including the energized
parts of the test probes.
13.4.3 Where failure of components and assemblies
could result in a risk of electric shock, fire, or personal
injury, those components and assemblies should be
certified by an accredited testing laboratory and used in
accordance with the manufacturer’s specifications, or
otherwise evaluated to the applicable standard(s).
SEMI S2-0703a
E
© SEMI 1991, 2004 15
NOTE 41: With the exception of implementation of ground
fault protection, shunt trip units that require power to trip
(actuate) are not recommended to be used in a safety control
circuit, because they are not fail-safe.
13.4.4 Electrical wiring for power circuits, control
circuits, grounding (earthing) and grounded (neutral)
conductors should be color coded according to
appropriate standard(s) per Section 13.4, or labeled for
easy identification at both ends of the wire. Where color
is used for identification, it is acceptable to wrap
conductor ends with appropriate colored tape or
sleeving; the tape or sleeving should be reliably secured
to the conductor.
EXCEPTION 1: Internal wiring on individual
components, e.g., motors, transformers, meters,
solenoid valves, power supplies.
EXCEPTION 2: Flexible cords.
EXCEPTION 3: Nonhazardous voltage multi-conductor
cables (e.g., ribbon cables).
EXCEPTION 4: When proper color is not available for
conductors designed for special application (e.g., high-
temperature conductors used for furnaces and ovens).
13.4.5 Grounding (earthing) conductors and connectors
should be sized to be compatible in current rating with
their associated ungrounded conductors according to
appropriate standard(s) per Section 13.4.
13.4.6 Electrical enclosures should be suitable for the
environment in which they are intended to be used.
13.4.7 Enclosure openings should safeguard against
personnel access to uninsulated energized parts. (Refer
to Appendix 1 for examples of openings for protection
against access from operators.)
13.4.8 Top covers of electrical enclosures should be
designed and constructed to prevent objects from
falling into the enclosures. (Refer to Appendix 1 for
examples of acceptable top enclosure openings.)
13.4.9 The current interrupting capacity (also known as
amperes interrupting capacity, or AIC) of the
equipment main disconnect should be identified in the
facility installation and maintenance manuals.
13.4.10 The equipment should be provided with main
overcurrent protection devices and main disconnect
devices rated for at least 10,000 rms symmetrical
amperes interrupting capacity (AIC).
NOTE 42: Some facilities may require higher AIC ratings
due to electrical distribution system design.
EXCEPTION: Cord- and plug-connected single phase
equipment, rated no greater than 240 volts line-to-
line/150 volts line-to-ground and no greater than 2.4
kVA, may have overcurrent protection devices with
interrupting capacity of at least 5,000 rms symmetrical
amperes interrupting capacity (AIC).
13.4.11 Equipment should be designed to receive
incoming electrical power from the facility to a single
feed location that terminates at the main disconnect
specified in Section 13.4.9. This disconnect, when
opened, should remove all incoming electrical power in
the equipment from the load side of the disconnect. The
disconnect should also have the energy isolation
(“lockout”) capabilities specified in Section 17.
EXCEPTION 1: Equipment with more than one feed
should be provided with provisions for energy isolation
(lockout) for each feed and be marked with the
following text or the equivalent at each disconnect:
“WARNING: Risk of Electric Shock or Burn.
Disconnect all [number of feed locations] sources of
supply prior to servicing.” It is preferred that all of the
disconnects for the equipment be grouped in one
location.
EXCEPTION 2: Multiple units mounted separately
with no shared hazards and without interconnecting
circuits with hazardous voltages, energy levels or other
potentially hazardous conditions may have:
separate sources of power and separate supply
circuit disconnect means, if they are clearly
identified; or
separate EMO circuits, if they are clearly
identified.
13.4.12 A permanent nameplate listing the
manufacturer’s name, machine serial number, supply
voltage, phase, frequency and full-load current should
be attached to the equipment where plainly visible after
installation. Where more than one incoming supply
circuit is to be provided, the nameplate should state the
above information for each circuit.
NOTE 43: Additional nameplate information may be
required depending on the location of use.
13.5 Uninterruptable Power Supplies (UPSs) — This
section applies to UPSs with outputs greater than: 30
volts rms, 42.4 volts peak; 60 volts dc; or 240 volt-
amps.
13.5.1 Whenever a UPS is provided with the
equipment, its location and wiring should be clearly
described within the installation and maintenance
manual.
13.5.2 Power from the UPS should be interrupted when
any of the following events occur:
the emergency off actuator (button) is pushed; or
the main equipment disconnect is opened; or
SEMI S2-0703a
E
© SEMI 1991, 2004 16
the main circuit breaker is opened.
EXCEPTION: Upon EMO activation, the UPS may
supply power to the EMO circuit, safety related
devices, and data/alarm logging computer systems as
described in the exception clauses of Section 12.2.
13.5.3 The UPS may be physically located within the
footprint of the equipment provided that the UPS is
within its own enclosure and is clearly identified.
13.5.4 The UPS should be certified by an accredited
testing laboratory and be suitable for its intended
environment (e.g., damp location, exposure to
corrosives).
13.5.5 The UPS wiring should be identified as “UPS
Supply Output” or equivalent at each termination point
where the UPS wiring can be disconnected.
13.6 Electrical Safety Tests
13.6.1 Equipment connected to the facility branch
circuit with a cord and plug should not exhibit surface
leakage current greater than 3.5 milliampere (mA) as
determined by testing completed in accordance with
“Leakage Current Test for Plug-and-Cord Equipment”
in SEMI S9.
EXCEPTION: Equipment with leakage current
exceeding 3.5 mA is acceptable if documentation is
provided to substantiate that the equipment is fully
compliant with an applicable product safety standard
that explicitly permits a higher leakage current.
13.6.2 Equipment grounding circuits should have a
measured resistance of one-tenth (0.1) ohm or less as
determined by testing in accordance with SEMI S9.
13.7 Equipment in which flammable liquids or gases
are used should be assessed to determine if additional
precautions (e.g., purging) in the electrical design are
necessary.
NOTE 44: NFPA 497 and EN 1127-1 provide methods for
making this assessment.
14 Fire Protection
14.1 Overview — This section applies to fire hazards
that are internal to the equipment.
14.1.1 This section provides minimum safety
considerations for fire protection designs and controls
on the equipment.
14.1.2 This section also provides minimum
considerations for fire detection and suppression
systems when provided with the equipment.
NOTE 45: Detailed guidance on fire risk assessment and
mitigation for semiconductor manufacturing equipment is
provided in SEMI S14.
14.2 Risk Assessment
14.2.1 A documented risk assessment should be
performed or accepted by a party qualified to determine
and evaluate fire hazards and the potential need for
controls. The risk assessment should consider normal
operations and reasonably foreseeable single-point
failures within the equipment. It should not consider
exposure to fire or external ignition sources not within
the specified use environment.
NOTE 46: This risk assessment can be combined with the
overall hazard analysis performed for this guideline, provided
the risk assessor has the required professional expertise to
perform risk assessments for fire hazards. SEMI S7 describes
qualifications for such an assessor.
14.2.2 If an accurate risk assessment depends on the
user’s adherence to specified procedures or conditions
of use, the supplier should describe such procedures or
conditions and state their importance.
14.2.3 SEMI S14 should be used to assess and report
risks to property and the environment.
14.3 Reporting
14.3.1 A summary report should be provided to the
user. The summary should include the following
characterizations, per SEMI S10, for each residual fire
hazard identified:
the assigned Severity;
the assigned Likelihood; and
the resulting Risk Category.
14.3.2 Optional fire risk reduction features should be
described in the pre-purchase information provided to
the user.
14.3.3 The scope and effectiveness of the means of fire
risk reduction should also be identified and reported,
including the expected risk reduction (as described in
Section 14.3.1).
14.3.4 If, due to fire hazards within the equipment,
thermal or non-thermal (e.g., smoke) damage is
possible outside of the equipment, then this possibility
should be reported to the user. This report should
include a qualitative description of the foreseen
scenario.
14.4 Fire Risk Reduction
14.4.1 Materials of Construction — Equipment should
be constructed of noncombustible materials wherever
reasonable. If process chemicals do not permit the use
of noncombustible construction, then the equipment
should be constructed of materials, suitable for the uses
and compatible with the process chemicals used, that
contribute least to the fire risk.