semi合集-English.pdf - 第6788页
SEMI S2-0703a E © SEMI 1991, 2004 17 NOTE 47: Some regional codes (e.g ., Uniform Fire Code) may require construction with noncombustible m aterials. 14.4.1.1 The flowcha rt in Appen dix 6 may be used for the selection o…

SEMI S2-0703a
E
© SEMI 1991, 2004 16
the main circuit breaker is opened.
EXCEPTION: Upon EMO activation, the UPS may
supply power to the EMO circuit, safety related
devices, and data/alarm logging computer systems as
described in the exception clauses of Section 12.2.
13.5.3 The UPS may be physically located within the
footprint of the equipment provided that the UPS is
within its own enclosure and is clearly identified.
13.5.4 The UPS should be certified by an accredited
testing laboratory and be suitable for its intended
environment (e.g., damp location, exposure to
corrosives).
13.5.5 The UPS wiring should be identified as “UPS
Supply Output” or equivalent at each termination point
where the UPS wiring can be disconnected.
13.6 Electrical Safety Tests
13.6.1 Equipment connected to the facility branch
circuit with a cord and plug should not exhibit surface
leakage current greater than 3.5 milliampere (mA) as
determined by testing completed in accordance with
“Leakage Current Test for Plug-and-Cord Equipment”
in SEMI S9.
EXCEPTION: Equipment with leakage current
exceeding 3.5 mA is acceptable if documentation is
provided to substantiate that the equipment is fully
compliant with an applicable product safety standard
that explicitly permits a higher leakage current.
13.6.2 Equipment grounding circuits should have a
measured resistance of one-tenth (0.1) ohm or less as
determined by testing in accordance with SEMI S9.
13.7 Equipment in which flammable liquids or gases
are used should be assessed to determine if additional
precautions (e.g., purging) in the electrical design are
necessary.
NOTE 44: NFPA 497 and EN 1127-1 provide methods for
making this assessment.
14 Fire Protection
14.1 Overview — This section applies to fire hazards
that are internal to the equipment.
14.1.1 This section provides minimum safety
considerations for fire protection designs and controls
on the equipment.
14.1.2 This section also provides minimum
considerations for fire detection and suppression
systems when provided with the equipment.
NOTE 45: Detailed guidance on fire risk assessment and
mitigation for semiconductor manufacturing equipment is
provided in SEMI S14.
14.2 Risk Assessment
14.2.1 A documented risk assessment should be
performed or accepted by a party qualified to determine
and evaluate fire hazards and the potential need for
controls. The risk assessment should consider normal
operations and reasonably foreseeable single-point
failures within the equipment. It should not consider
exposure to fire or external ignition sources not within
the specified use environment.
NOTE 46: This risk assessment can be combined with the
overall hazard analysis performed for this guideline, provided
the risk assessor has the required professional expertise to
perform risk assessments for fire hazards. SEMI S7 describes
qualifications for such an assessor.
14.2.2 If an accurate risk assessment depends on the
user’s adherence to specified procedures or conditions
of use, the supplier should describe such procedures or
conditions and state their importance.
14.2.3 SEMI S14 should be used to assess and report
risks to property and the environment.
14.3 Reporting
14.3.1 A summary report should be provided to the
user. The summary should include the following
characterizations, per SEMI S10, for each residual fire
hazard identified:
the assigned Severity;
the assigned Likelihood; and
the resulting Risk Category.
14.3.2 Optional fire risk reduction features should be
described in the pre-purchase information provided to
the user.
14.3.3 The scope and effectiveness of the means of fire
risk reduction should also be identified and reported,
including the expected risk reduction (as described in
Section 14.3.1).
14.3.4 If, due to fire hazards within the equipment,
thermal or non-thermal (e.g., smoke) damage is
possible outside of the equipment, then this possibility
should be reported to the user. This report should
include a qualitative description of the foreseen
scenario.
14.4 Fire Risk Reduction
14.4.1 Materials of Construction — Equipment should
be constructed of noncombustible materials wherever
reasonable. If process chemicals do not permit the use
of noncombustible construction, then the equipment
should be constructed of materials, suitable for the uses
and compatible with the process chemicals used, that
contribute least to the fire risk.

SEMI S2-0703a
E
© SEMI 1991, 2004 17
NOTE 47: Some regional codes (e.g., Uniform Fire Code)
may require construction with noncombustible materials.
14.4.1.1 The flowchart in Appendix 6 may be used for
the selection of materials of construction for equipment.
14.4.1.2 Any portion of equipment that falls within the
scope of SEMI F14 (Guide for the Design of Gas
Source Equipment Enclosures) should be designed in
accordance with that guide.
14.4.2 Elimination of Process Chemical Hazards —
The option of substituting non-flammable process
chemicals for flammable process chemicals should be
considered.
14.4.3 Engineering Controls
14.4.3.1 Fire risks resulting from process chemicals
may be reduced using engineering controls (e.g.,
preventing improper chemical mixing, preventing
temperatures from reaching the flash point).
14.4.3.2 Fire risks resulting from materials of
construction may be reduced using engineering controls
(e.g., non-combustible barriers that separate
combustible materials of construction from ignition
sources, installing a fire suppression system that
extinguishes ignited materials).
14.4.3.3 Equipment power and chemical sources that
present unacceptable fire risks should be interlocked
with the fire detection and suppression systems to
prevent start-up of the equipment or delivery of
chemicals when the fire detection or suppression is
inactive.
NOTE 48: Some jurisdictions require interlocking.
NOTE 49: Refer to Section 6.5 for criteria for acceptability.
14.4.3.4 Shutdown or failure of a fire detection or
suppression system need not interrupt the processing of
product within the equipment by immediately shutting
down the equipment, but should prevent additional
processing until the fire detection or suppression is
restored. Software or hardware may be used for this
function.
14.4.3.5 Controlling smoke by exhausting it (using the
supplier-specified equipment exhaust) from the
cleanroom may be used to reduce fire risks from the
generation of products of combustion. When used, this
reduction method should be combined with detection or
suppression when flames can be propagated.
NOTE 50: Controlling smoke may be sufficient when smoke
is the only consequence (e.g., smoldering components that
generate smoke).
NOTE 51: For controlling smoke to be effective, the smoke
must be removed not only from the equipment, but also from
the cleanroom. This is typically accomplished by using ducted
exhaust.
NOTE 52: The use of exhaust to remove smoke may be
subject to regulations, such as building and fire codes.
NOTE 53: The use of exhaust to remove smoke may create
hazards within the exhaust system. Therefore, a description of
the expected discharge (i.e., anticipated air flow rate,
temperature, and rate of smoke generation) into the exhaust
system may be important information for installation of
equipment.
14.4.4 Fire Detection — The following criteria apply
to any fire detection system determined to be
appropriate for fire protection by the fire risk
assessment:
NOTE 54: Heat detectors, smoke sensing devices, and other
devices used solely for monitoring equipment status may not
need to meet these requirements. Some local jurisdictions,
however, may require that all smoke detectors be connected to
building systems and be compliant with all applicable fire
alarm codes.
14.4.4.1 The fire detection system, which includes
detectors, alarms and their associated controls, should
be certified by an accredited testing laboratory and
suitable for the application and for the environment in
which it is to be used.
NOTE 55: Such certifications typically require that the
components of fire detection systems are readily identifiable
and distinguishable from other components in the equipment.
14.4.4.2 The fire detection, alarm and control system
should be installed in accordance with the requirements
of the certification in Section 14.4.4.1, and in
accordance with requirements of the appropriate
international or national codes or standards (e.g., NFPA
72).
14.4.4.3 The fire detection system should be capable of
interfacing with the facility’s alarm system. It may be
preferable for the equipment supplier to specify the
location and performance of detectors, but not provide
them, so that the user may better integrate the detection
in the equipment with that in the facility. This
alternative should be negotiated explicitly with the user.
14.4.4.4 The fire detection system should activate
alarms audibly and visually at the equipment.
14.4.4.5 Manual activation capability for the fire
detection system should be considered, for the purpose
of providing notification to a constantly attended
location.
14.4.4.6 Activation of trouble or supervisory
conditions should result in all of the following:
notification of the operator;

SEMI S2-0703a
E
© SEMI 1991, 2004 18
allowing the completion of processing of substrates
in the equipment;
prevention of processing of additional substrates
until the trouble or supervisory condition is
cleared; and
providing, through an external interface, a signal to
the facility monitoring system or a constantly
attended location.
NOTE 56: Some local jurisdictions require that such alarms
signal the building/facility fire alarm systems.
14.4.4.7 The fire detection system should be capable of
operating at all times, including when the equipment is
inoperable (e.g., equipment controller problems) or in
maintenance modes (e.g., some or all of the
equipment’s hazardous energies are isolated (“locked
out”). For the purpose of this section, “inoperable”
includes the equipment states after an EMO is activated
and after the equipment has had its hazardous energies
isolated (i.e., has been “locked out”). Therefore, the
detection system should not require hazardous voltages
(e.g., line alternating current) to operate anything other
than the equipment within the detection system’s
control enclosure. Sensors and other devices outside
the detection system’s control enclosure should not
require hazardous voltage.
EXCEPTION: Operability is not required during
maintenance of the fire detection system.
14.4.4.7.1 Power at a hazardous voltage may be
supplied to the detection system controller enclosure
after the equipment EMO is activated or after the
equipment has had its hazardous energies isolated only
if the wiring providing the hazardous voltage is
separated from other wiring and is suitably labeled.
14.4.4.7.2 If the hazardous voltage supply to the
detection system controller is not disconnected by the
energy isolation method that removes the other
hazardous voltages from the equipment, there must also
be separate hazardous energy isolation capability for
the hazardous voltage supplies to the detection system
controller enclosure.
14.4.4.8 A battery or other regulatory agency
acceptable emergency power alternative, capable of
sustaining the detection system for 24 hours, should be
provided.
NOTE 57: Back-up power must be provided in accordance
with local regulations. The requirements for back-up power
vary among jurisdictions.
14.4.4.9 The fire detection system should remain active
following EMO activation.
14.4.4.10 There may be cases where the internal power
supply for a detection system cannot supply power for
the full length of extended maintenance procedures
(i.e., procedures longer than the expected duration of
the back-up power supply). In such cases, the supplier
should provide written procedures for either removing
the fire hazard or safely supplying power to the fire
detection system.
14.4.4.11 Activation of the fire detection system
should shut down the equipment within the shortest
time period that allows for safe equipment shutdown.
This includes shutdown of any fire-related hazard
source that could create additional fire risks for the
affected module or component.
NOTE 58: See Sections 14.4.3.3 and 14.4.3.4 for related
provisions.
EXCEPTION 1: A non-recycling, deadman abort
switch is acceptable on detection systems that are used
for equipment shutdown, but not on those used for
activation of a suppression system.
EXCEPTION 2: Activation of the fire detection system
should not remove power from fire and safety systems.
14.4.4.12 The equipment design and configuration
should not prevent licensed parties from certifying the
design and installation of fire detection systems.
NOTE 59: This is not meant to suggest installation by
licensed parties; however, some jurisdictions require fire
detection and suppression system installers to be licensed as
specified by the jurisdiction.
14.4.5 Fire Suppression — The following criteria
apply to any fire suppression system determined to be
appropriate by the fire risk assessment.
NOTE 60: As a fire detection system is generally required to
provide the initiating sequence for the suppression system, it
is the intention of this guideline that this be the same fire
detection system described in Section 14.4.4.
14.4.5.1 The fire suppression system, which includes
nozzles, actuators, and their associated controls, should
be certified by an accredited testing laboratory and
suitable for the application and for the environment in
which it to be used.
NOTE 61: Such certifications typically require that the
components of fire suppression systems are readily
identifiable and distinguishable from other components in the
equipment. This includes adequate labeling of piping.
14.4.5.2 The fire suppression agent should be accepted
for the application by an accredited testing laboratory.
The suppression agent selection process should include
an evaluation of the amount and storage location of the
suppression agent and of potential damage to a
cleanroom and the environment. The least damaging
effective agent should be selected. If more than one