semi合集-English.pdf - 第6966页
SEMI S9-1101 © SE MI 1995, 2001 3 NOTE 4: C onsideration of the toler ance on a nom inal rated frequenc y (e.g., 50 ± 0.5 Hz) is not u sually necessary. 8.4 As an alternati ve to carry i ng out test s on the complete equ…

SEMI S9-1101 © SEMI 1995, 2001 2
4.2 IEC Standard
1
IEC 61010-1 — Safety Requirements for Electrical
Equipment for Measurement, Control, and Laboratory
Use, Part 1: General Requirements
NOTE 1: Unless otherwise indicated, all documents cited
shall be the latest published versions.
5 Terminology
5.1 1500 ohm impedance network — a network
consisting of a 1500 ohm resistor in parallel with a 0.15
µF capacitor.
5.2 accessible — capable of being contacted by an IEC
accessibility probe (IEC standard test finger, as
described in IEC 61010).
NOTE 2: The test finger is also known, in various IEC
documents, as the “jointed test finger” and “jointed standard
test finger”.
5.3 full load current — current when the equipment is
operated at the maximum manufacturer's specified
operating conditions including all motors and heaters
designed to operate simultaneously.
5.4 hazardous energy — energy of 20 J (Joules) or
more, or an available power level of 240 V*A or more.
5.5 least favorable condition — the condition which is
most likely to result in a test failure.
5.6 permanently connected equipment — Equipment
that is intended to be electrically connected to a supply
by means of connection which can be detached only by
the use of tools.
5.7 primary circuit — an internal circuit which is
directly connected to the external supply mains or other
equivalent source (such as a motor-generator set) which
supplies the electric power. It includes the primary
windings of transformers, motors, other load devices
and the means of connection to the supply mains.
5.8 safe condition a condition in which all relevant
hazardous energy sources are removed or suitably
contained and all relevant hazardous production
materials are removed or contained, unless this results
in additional hazardous conditions.
5.9 PE Terminal — a terminal which is bonded to
conductive parts of a piece of equipment for safety
purposes and is intended to be connected to an external
protective earthing system.
1 International Electrotechnical Commission, 1, rue de Varembé,
Case Postale 131, CH-1211 Geneva 20, Switzerland. Website:
www.iec.ch
5.10 standby condition — condition in which
equipment is energized and in its idle state.
5.11 tool — an external device used to aid a person in
performing a mechanical function. As used in this
document, tool includes devices such as keys.
5.12 V*A — Volt-ampere.
6 Safety Precautions
6.1 The tests outlined in this document are to be
performed by trained and qualified personnel who have
knowledge of the techniques and the test apparatus
described herein.
7 Calibration and Standardization
7.1 All test equipment should be calibrated and
traceable to a calibration standards organization (e.g.,
National Institute of Standards and Technology (NIST)
in the United States or the National Metrology Institute
in Japan).
7.2 The calibration interval for test equipment should
not exceed one year.
8 Test Conditions
8.1 Except where noted otherwise, the equipment
should be tested under the least favorable conditions
within the manufacturer's operating specifications.
These conditions include:
• supply potential
• supply frequency
• position of movable parts
• operating mode (e.g. full temperature conditions,
motors in operation)
• adjustment of thermostats, regulating devices, or
similar controls in operator-accessible areas
8.2 Test Supply Potential — To determine the least
favorable supply potential for a test, consider:
• multiple-nominal rated potentials (e.g., 120/240 V)
• extremes of nominal rated potential ranges (e.g.,
208–240 V)
8.2.1 Consideration of the tolerance on a nominal rated
potential (e.g., 120 ± 5%) is not necessary.
NOTE 3: Some standards (e.g., IEC 61010-1 and IEC 60950)
may specify 90% and 110% of any rated supply voltage.
8.3 Test Supply Frequency — To determine the least
favorable supply frequency for a test, consider the
nominal frequencies as specified (e.g., 50 Hz, 60 Hz, or
50/60 Hz).

SEMI S9-1101 © SEMI 1995, 20013
NOTE 4: Consideration of the tolerance on a nominal rated
frequency (e.g., 50 ± 0.5 Hz) is not usually necessary.
8.4 As an alternative to carrying out tests on the
complete equipment, tests may be conducted on
circuits, components and sub-assemblies independent of
the equipment, provided that the results of the tests
would be representative of those performed as part of
the assembled equipment.
EXCEPTION: The leakage current and grounding
continuity tests identified in Sections 9.1 and 9.2 should
be completed only on fully assembled equipment.
9 Electrical Tests
9.1 Leakage Current Test for Cord-and-Plug
Equipment
9.1.1 Test Equipment A 1500 ohm impedance
network and a true RMS voltmeter with an accuracy of
1.0%. The impedance network can be a separate
assembly or incorporated within a leakage current
measuring instrument.
9.1.2 Procedure For equipment connected to the
facility branch circuit with a cord-and-plug (plug/socket
combination), ensure that the equipment is isolated
(e.g., by placing the equipment on a wooden or other
isolating surface). Connect the equipment to its rated
source of supply with the equipment grounding (PE)
conductor disconnected and operate it at the least
favorable conditions specified by the manufacturer.
Connect the 1500 ohm impedance network between
each accessible metal part and the supply equipment
grounding (PE) conductor. In determining accessibility
of live parts, remove all doors, panels, etc. that are to be
removed by the operator during normal operation.
Using a true RMS voltmeter, measure the voltage drop
across the impedance network. Calculate the leakage
current using the formula:
I
leaka
g
e
=
Voltage
measured
1500 ohms
9.1.3 Acceptable Results The maximum calculated
leakage current does not exceed 3.5 mA.
9.2 Grounding Continuity Test
9.2.1 Test Equipment Low range ohmmeter with a
range to measure 0.10 ohm with an accuracy of 1.0%.
9.2.2 Procedure
Disconnect the equipment from the
supply. For equipment installed with fixed wiring
methods, disconnect the supply equipment grounding
conductor (protective earthing conductor) from the
main equipment grounding terminal (PE Terminal).
Measure the resistance between the power supply
equipment grounding terminal (PE Terminal) and each
accessible metal part (handle, monitor, doors, etc.) on
the equipment using a low-range ohm-meter. Upon test
completion, reconnect the supply equipment grounding
conductor (protective earthing conductor).
EXCEPTION: Grounding Continuity Test is not
required to be measured where accessible metal
surfaces are not likely to become energized in a single
fault condition.
NOTE 5: Some standards (e.g., IEC 60204-1, IEC 61010-1)
may specify this test to be performed using a current injection
method.
9.2.3 Acceptable Results The resistance between the
grounding conductor terminal and each accessible part
shall not exceed 0.1 ohm.
9.3 Starting Current Test
9.3.1 Test Equipment None.
9.3.2 Procedure — Start the equipment in accordance
with manufacturer's instructions three times from a
completely stopped condition. Ensure that the time
interval between successive starts is sufficient to allow
the equipment return to ambient conditions.
9.3.3 Acceptable Results None of the equipment's
overload or overcurrent protections activates during this
test.
NOTE 6: It is recommended that the peak inrush starting
current be measured using an appropriate current measuring
device and recorded in the test report.
9.4 Input Test
9.4.1 Test Equipment True RMS current measuring
equipment, with accuracy of 3.0%.
9.4.2 Procedure — Measure the input current to the
equipment under the maximum normal operating load
conditions (i.e., with all motors, heaters, etc. running at
manufacturer’s specified maximum loading conditions).
9.4.3 Acceptable Results The measured current does
not exceed 110% of the rated full load current value
specified on the equipment nameplate.
9.5 Dielectric Test
9.5.1 Test Equipment Timer with accuracy of ± 5
seconds. Dielectric Withstand Tester with means of
indicating test potential, as well as an audible or visual
indicator of electrical breakdown, or an automatic-
reject feature for any unacceptable unit. In an
alternating current test, the test equipment should
include a transformer having sinusoidal output. This
transformer should have a rating of 500 VA or greater
unless it is provided with a voltmeter that directly
measures the applied output potential.

SEMI S9-1101 © SEMI 1995, 2001 4
9.5.2 Procedure — With the equipment disconnected
from its supply, apply a dielectric withstand potential of
1500 Volts AC or 2121 Volts DC between live metal
parts of primary circuit(s) and dead metal parts. Surge
suppression components and devices, and electronic
components certified by an accredited testing laboratory
that may be damaged may be disconnected from the
circuit for this test. For this test, the following
conditions need to be set:
• The equipment should be at its maximum operating
temperature
• Switches should be placed in the “on” position
• Circuits through contactors be completed by
manually engaging the contacts or bypassing the
contactor terminals.
9.5.2.1 Achieve the test potential gradually, starting
from zero and holding at the maximum value for a
period of one minute.
NOTE 7: A grounded circuit (neutral) conductor, if used in
the circuit, is considered a live part.
NOTE 8: Where line-to-ground filter components are
installed in the equipment, the DC dielectric potential
specified above may be used as an equivalent.
9.5.3 Acceptable Results The equipment does not
have a dielectric breakdown as indicated by a puncture,
flashover or sparkover.
NOTE 9: Breakdown is often indicated by an abrupt decrease
or nonlinear advance of voltage as the voltage is increased.
Similarly, a breakdown is often indicated by an abrupt
increase in current. Partial discharge (corona) and similar
phenomena are disregarded during application of the test
voltage.
9.6 Strain Relief Test
9.6.1 Test Equipment — Timer with accuracy of ± 5
seconds. A calibrated weight to apply a force of 156
Newtons (35 lb) ± 1.56 Newtons (0.35 lb). A
supporting surface to secure the equipment.
9.6.2 Procedure — For cord-and-plug connected
equipment, strain relief is provided to prevent
mechanical stress such as a pull or twist being
transmitted to terminals, splices or interior wiring.
Support the equipment on a surface so it will not move
when the force is applied to the cord. Apply a direct
pull of 156 N (35 pounds) to the equipment supply cord
from the least favorable angle. If necessary use pulleys
or other means to adjust the angle of force applied to
the strain relief on the equipment. Apply the force
gradually by slowly suspending the weight on the cord
and maintain the applied force for a period of one
minute.
9.6.3 Acceptable Results The equipment supply
cord does not displace to the extent that stress could be
applied to the internal connections.
9.7 Transformer Output Short Circuit Test
9.7.1 Test Equipment Timer with accuracy of ± 5
minutes. A substantial conductor suitable for carrying
the short circuit current.
9.7.2 Procedure — With the equipment in its standby
condition, short circuit the output of each power
transformer.
NOTE 10: If overcurrent protection is connected to the output
of the transformer under test, connect the short-circuit jumper
after this protective device.
EXCEPTION 1: Where the overcurrent protective
devices on the input or output of the transformer are
rated at not more than 125% of the rated current of the
transformer respectively and the overcurrent protective
devices are certified by an accredited testing laboratory,
the transformer need not be subjected to this test.
EXCEPTION 2: A thermally-protected or impedance-
protected transformer that is certified by an accredited
testing laboratory need not be subjected to this test.
9.7.3 Acceptable Results A hazardous condition
(e.g., smoke, fire, or molten material) does not exist
within 8 hours or before activation of overcurrent
protection, thermal protection, or other protective
circuit/device whichever occurs first.
9.8 Power Supply Output Short Circuit Test
9.8.1 Test Equipment Timer with accuracy of ± 5
minutes. A substantial conductor suitable for carrying
the short circuit current.
9.8.2 Procedure — With the equipment in its standby
condition, short circuit the output of each power supply,
one at a time.
NOTE 11: If overcurrent protection is connected to the output
of the power supply under test, connect the short circuit
jumper after this protective device.
EXCEPTION: A power supply that is certified by an
accredited testing laboratory and used in accordance
with its certification and the manufacturer’s instructions
need not be subjected to this test.
9.8.3 Acceptable Results A hazardous condition
(e.g., smoke, fire, or molten material) does not exist
within 8 hours or before activation of overcurrent
protection, thermal protection, or other protective
circuit/device whichever occurs first.