semi合集-English.pdf - 第858页
SEMI E115-0302 E © SEMI 2002 4 RLOAD = Re( Z ou t *) − 2 RLOS S (6) X LOAD =− Im( Z ou t *) (7) where Effc is the calculated power efficiency based on the measurement of Re( Zout * ) and Effm , RLO AD is the real part of…

SEMI E115-0302
E
© SEMI 2002 3
8 Test Setup for Determining Load Impedance
and Efficiency
8.1 Two test methods are described for analyzing
matching networks. The first method for determining
the load impedance and efficiency measures the
complex conjugate of the load impedance and then
corrects for the matching network losses to determine
the load impedance and efficiency. A schematic of the
Test Setup is shown in Figure 1. The method uses a
Network Analyzer to measure the reflection coefficient,
which is related to the load impedance, and the
transmission coefficient, which is related to the
efficiency. The Test Setup for this approach consists of
the Network Analyzer, the matching network to be
tested (DUT), coaxial test cables, and the appropriate
adapters (if any) to connect the DUT to the Network
Analyzer.
8.2 The second method for determining the load
impedance and efficiency uses a Load Impedance
Simulator attached to the output of the matching
network. A schematic of the Test Setup is shown in
Figure 2. The Test Setup for this approach consists of
the Network Analyzer, the matching network to be
tested (DUT), the load simulator, coaxial test cables,
the appropriate adapter (if any) to connect the DUT to
the Network Analyzer, and the appropriate adapter to
connect the load simulator to the DUT.
8.3 Prior to making any measurements, the Network
Analyzer shall be turned on and allowed to warm up
before the testing is to take place. This time will allow
for electronics to come to a stable operating condition
for the measurements.
9 Test Procedure for Determining Load
Impedance and Efficiency
9.1 Two test procedures can be used to determine the
load impedance and efficiency of the matching
network. The first method is designed for “L” type
matching networks, where the losses are dominated by
the loss resistance of the inductor that is in series with
the load impedance. For the case where there are finite
losses in the shunt capacitor, the capacitor losses can be
lumped in with the inductor losses without introducing
significant error (usually less than 0.5% for typical
values of < 0.1 ohms). Lumping the total losses into an
overall series loss will also cause a slight shift in the
reactive part of the impedance, but the magnitude of the
shift is on the same order as the impedance
measurement uncertainty and can be ignored.
9.2 The second method is designed for other matching
network types and uses a load simulator to determine
the load impedance and efficiency.
9.3 Test Method 1 for Determining Matching Network
Load Impedance and Efficiency
9.3.1 This test method shall be used for “L” type
matching networks of the type shown schematically in
Figure 1, where the losses in the network are dominated
by the loss resistance of the inductor, RLOSS. The
efficiency for this type of matching network is given as
Eff =
RLOAD
RLOAD + RLOSS
(1)
where RLOAD refers to the real part of the load
impedance and RLOSS refers to the losses of the
matching network.
9.3.2 For this type of network, the real part of the
complex conjugate impedance, Re(Zout*), contains the
real part of the load impedance plus twice the loss
resistance, RLOSS.
Re(
Z
ou
t
*)
=
RLOAD + 2RLOS
S
(2)
9.3.3 The load impedance, therefore, is equal to the
complex conjugate impedance less twice the loss
resistance (along with the sign change of the reactive
part of the conjugate impedance). For example, if the
conjugate impedance is measured as 3 + j20 and
RLOSS is determined to be 0.5 ohms, then the load
impedance is 2 – j20 ohms.
9.3.4 The efficiency of the matching network and the
loss resistance, RLOSS, can be determined by
measuring both the transmission coefficient, S21, and
the reflection coefficient, S11, in the Test Setup shown
in Figure 1. Note that the reflection coefficient
measurement, S11, is equivalent to measuring the
complex conjugate impedance. If the matching
network is considered as a test load with an impedance
equal to the complex conjugate impedance, then the
loss resistance is found by measuring the efficiency of
the test load. This efficiency, Effm, can be expressed as
Effm =
Re(
Z
out*) − RLOSS
Re(Zout*)
(3)
where Re(Zout*) is the real part of the complex
conjugate load impedance, Zout*. The measured
efficiency, Effm, can be determined from the S21 and
S11 measurements (as shown later in this section).
Thus, the measurements of Re(Zout*) and Effm can be
used to determine RLOSS as
)1(*)Re( EffmZoutRLOSS −×
=
(4)
and the load impedance and power efficiency of the
matching network can then be determined from
Effc =
Re(
Z
out*) − 2RLOSS
Re(Zout*) − RLOSS
(5)

SEMI E115-0302
E
© SEMI 2002 4
RLOAD = Re(
Z
ou
t
*) − 2RLOS
S
(6)
X
LOAD =−Im(
Z
ou
t
*) (7)
where Effc is the calculated power efficiency based on
the measurement of Re(Zout*) and Effm, RLOAD is the
real part of the load impedance, and XLOAD is the
imaginary part of the load impedance.
9.3.5 Calibrate the Network Analyzer at the desired
operating frequency (e.g., 13.56 MHz). The Network
Analyzer shall be calibrated for measuring the
reflection coefficient at test Port 1 and for measuring
the transmission coefficient at test Port 2 (see Figure 1)
using the calibration kit provided with the Network
Analyzer. This measurement requires measuring the
S11 and S21 S-parameters and requires a full 2-port
calibration. The calibration shall be performed at fixed
frequency (continuous-wave operation) using the
lowest bandwidth possible (typically 10 Hz). The
calibration for each port shall include the additional test
cables and any additional adapters.
9.3.6 After calibration of the Network Analyzer, the
cable connected to Port 1 of the Network Analyzer shall
be connected to the output of the DUT. The cable
connected to Port 2 of the Network Analyzer shall be
connected to the input of the DUT.
9.3.7 The tuning elements shall be moved to their
minimum positions before the measurement is initiated.
After all connections are visually inspected for proper
contact and the Network Analyzer has stabilized, the
value of the complex conjugate impedance (Zout*), the
magnitude of the reflection coefficient (S11), and the
magnitude of the transmission coefficient (S21) shall be
recorded.
9.3.8 The efficiency when the DUT is viewed as a test
load, Effm, is determined from both the reflection and
transmission coefficients. The efficiency can be
calculated by taking the ratio of the output power
divided by the input power. The output power is
simply (S21)
2
and the input power is (1-(S11)
2
).
()
()
2
2
111
21
S
S
Effm
−
=
Typically, the reflection and transmission coefficients
are expressed in terms of dB (decibels). The conversion
between dB and efficiency is expressed as
)10/dBin 11S(
)10/dBin 21S(
101
10
−
=Effm
For example, if the transmission coefficient is measured
to be –10.2 dB and the reflection coefficient is
measured to be –0.61 dB, then Effm would be 0.7288.
The efficiency based on this measurement can then be
used to calculate RLOSS, Effc, RLOAD, and XLOAD by
using the equations previously shown. All of these
calculated numbers using equations 3–6 shall be
recorded, as well as the positions of the tuning elements
of the matching network.
9.3.9 For the next measurement, Tune Position shall
remain fixed, and the Load Position shall be increased
by an increment equal to no more than 10% of the full-
scale range of the tuning element position. For
example, if the range of the tuning element is 10 volts,
then the tuning element should be moved in increments
of no greater than 1 volt. A smaller increment shall be
used for the case where the incremental change in Load
Position results in an incremental impedance change of
more than 20% of the total impedance variation
measured by the full-scale variation of the Load
Position. For example, if the real part of the load
impedance varies 15 ohms over the 10 volt variation of
the Load Position, then a smaller Load Position
increment shall be used if the real load impedance
varies by more than 3 ohms between increments (0.2 ×
15 = 0.3). After the tuning elements have been moved
to their new values, the previous measurement steps
shall be repeated.
9.3.10 After the Load Position has been varied over its
entire range, the Tune Position shall be increased by an
increment equal to no more than 10% of the full-scale
range of the tuning element position. The Load
Position shall be moved back to its minimum position
and the above steps shall be repeated until the entire
tuning range of the matching network is measured.
9.3.11 The data shall be recorded and then presented in
both graphical and tabular forms. An example of a
typical impedance range graph is shown in Figure 3 for
the real load impedance and in Figure 4 for the reactive
load impedance. An example of a typical efficiency
plot is shown in Figure 5. An example of data
presented in tabular form is shown in Table I.
9.4 Test Method 2 for Determining Matching Network
Load Impedance and Efficiency
9.4.1 This test method shall be used for matching
networks that are not necessarily dominated by a series
loss resistance as in an ideal “L” type network. This
method uses a Load Simulator(s) attached to the DUT
and assumes that the DUT has two tuning elements.
The Load Simulator(s) shall have a tuning range that
will cover no less than 80% of the tuning range of the
matching network. Details of a typical Load Simulator
can be found in the Related Information section of this
Test Method. The test method outlined here assumes
that the Load Simulator(s) contains variable tuning
elements with position indicators to allow the load

SEMI E115-0302
E
© SEMI 2002 5
impedance to vary. An example of a load simulator
would be a matching network used in reverse, where
the output of the DUT would attach to the output of
another matching network.
9.4.2 Calibrate the Network Analyzer at the desired
operating frequency (e.g., 13.56 MHz). The Network
Analyzer shall be calibrated for measuring the
reflection coefficient at test Port 1 and for measuring
the transmission coefficient at test Port 2 (see Figure 1)
using the calibration kit provided with the Network
Analyzer. This measurement requires measuring the
S11 and S21 S-parameters and requires a full 2-port
calibration. The calibration shall be performed at fixed
frequency (continuous-wave operation) using the
lowest bandwidth possible (typically 10 Hz). The
calibration for each port shall include the additional test
cables and any additional adapters.
9.4.3 After calibration of the Network Analyzer, the
test cable connected to Port 1 of the Network Analyzer
shall be connected to the input of the matching network
to be tested (DUT). The Load Simulator shall be
connected to the output of the DUT. The cable
connected to Port 2 of the Network Analyzer shall be
connected to the output of the Load Simulator.
9.4.4 The tuning elements shall be moved to their
minimum positions (or the positions that can match to
lowest tuning point of the Load Simulator(s)) before the
measurement is initiated. The variable elements in the
Load Simulator shall be adjusted until the input
impedance of the matching network is matched (i.e.,
input impedance = 50 ohms). After all connections are
visually inspected for proper contact and the Network
Analyzer has stabilized, the value of the input
impedance and the magnitude of the transmission
coefficient (S21) shall be recorded. In addition, the
positions of the tuning elements of the DUT and the
Load Simulator shall be recorded.
9.4.5 The load impedance of the DUT corresponds to
the input impedance of the Load Simulator. At this
point in the process, the Load Simulator can be
disconnected and its input impedance can be measured.
Alternatively, the input impedance can be measured
later by moving the Load Simulator tuning element
values to the positions recorded in Section 9.4.4.
9.4.6 The efficiency of the Test Setup, which includes
the DUT and the Load Simulator, is determined from
the transmission coefficient. Typically, the
transmission coefficient is expressed in terms of dB
(decibels). The conversion between dB and percentage
is expressed as:
Efficiency(%) = 100 × 10
(loss in dB
/
10)
For example, if the transmission coefficient is measured
to be –3 dB, then the power transfer efficiency would
be 50.1%. In other words, 49.9% of the power is lost in
the Test Setup.
9.4.7 The efficiency of the DUT is determined by
dividing the efficiency of the Test Setup by the
efficiency of the Load Simulator. For example, if the
efficiency of the Test Setup is 70% and the efficiency
of the Load Simulator is 90%, then the efficiency of the
DUT is 77.8% (0.7/0.9). The efficiency of the Load
Simulator is typically determined separately (see
Related Information Section at the end of this Test
Method).
9.4.8 For the next measurement, one tuning element
(element 1) shall remain fixed, and the other tuning
element (element 2) shall be increased by an increment
equal to no more than 10% of the full scale range of the
tuning element position. For example, if the range of
the tuning element is 10 volts, then the tuning element
shall be moved in increments of no greater than 1 volt.
A smaller increment shall be used for the case where
the incremental change in tuning element position
results in an incremental impedance change of more
than 20% of the total impedance variation measured by
the full-scale variation of the tuning element. For
example, if the real part of the load impedance varies
15 ohms over the 10 volt variation of the tuning
element, then a smaller tuning element increment shall
be used if the real load impedance varies by more than
3 ohms between increments (0.2 × 15 = 0.3). After the
tuning elements have been moved to their new values,
the previous measurement steps shall be repeated.
9.4.9 After the tuning element (element 2) has been
varied over its entire range, the other tuning element
(element 1) shall be increased by an increment equal to
no more than 10% of its full-scale range. Tuning
element 2 shall be moved back to its minimum position
and the above steps shall be repeated until the entire
tuning range of the matching network is measured.
9.4.10 The data shall be recorded and then presented in
both graphical and tabular forms. An example of a
typical impedance range graph is shown in Figure 3 for
the real load impedance and in Figure 4 for the reactive
load impedance. An example of a typical efficiency
plot is shown in Figure 5. An example of data
presented in tabular form is shown in Table 1.
10 Reporting Test Results
10.1 Report the type of Network Analyzer and the
details of the Network Analyzer parameters used for the
tests, including the bandwidth, the number of data
points, and the test frequency. Also report which Test
Method was used.