CP030电流探头规格书.pdf

Current Pr obes Key F eatures • ProBus active pr obe interface with automatic scaling in A/div • Auto zer o and degauss capabilities built into instrument’ s user interface • CP030B – 30 A rms continuous current – 50 A p…

100%1 / 4
Current Probes
Key Features
•
ProBus active probe interface with
automatic scaling in A/div
•
Autozero and degauss capabilities
built into instrument’s user interface
•
CP030B
–
30 A
rms
continuous current
–
50 A
peak
current
–
50 MHz bandwidth
–
1 mA/div sensitivity
•
CP031
–
30 A
rms
continuous current
–
50 A
peak
current
–
100 MHz bandwidth
•
CP031A
–
30 A
rms
continuous current
–
50 A
peak
current
–
100 MHz bandwidth
–
1 mA/div sensitivity
•
CP150B
–
150 A
rms
continuous current
–
300 A
peak
current
–
10 MHz bandwidth
•
CP500
–
500 A
rms
continuous current
–
700 A
peak
current
–
2 MHz bandwidth
Wide Range of Applications
Teledyne LeCroy current probes are
available in a variety of models for a
wide range of applications. The full
range of Teledyne LeCroy current probes
includes models with bandwidths up
to 100 MHz, peak currents up to 700 A
and sensitivities to 1 mA/div. Teledyne
LeCroy current probes are often used
in applications such as the design
and test of switching power supplies,
motor drives, electric vehicles, and
uninterruptible power supplies.
High Sensitivity
The CP030B and CP031A provide a high
sensitivity of 1 mA/div. When used with
HDO high denition oscilloscopes with
HD4096 technology, users will obtain
highly accurate, low current waveforms
with unmatched 12-bit resolution for
improved debug and analysis.
Fully Integrated
All Teledyne LeCroy current probes
are powered through the Teledyne
LeCroy ProBus
®
connection and
require no additional hardware. Along
with providing power, the ProBus
connection allows the current probe and
oscilloscope to communicate, resulting
in current waveforms automatically
displayed on screen in Amps, and
calculated power traces scaled correctly
in Watts. This full integration also allows
for Degauss and Autozero functions to
be done directly from the oscilloscope’s
user interface.
Deskew Calibration Source
The DCS025 deskew calibration
source has both voltage and current
time-aligned signals, which enables the
precise deskew of voltage and current
probes. Most voltage probes along
with 30, 150 and 500 Amp current
probes are compatible with the DSC025.
Teledyne LeCroy current probes do not require the breaking of a circuit
or the insertion of a shunt to make accurate and reliable current
measurements. Based on a combination of Hall effect and transformer
technology, Teledyne LeCroy current probes are ideal for making accurate
AC, DC, and impulse current measurements.
2
Maximum Input Current vs. Frequency*
Insertion Impedance vs. Frequency*
(typical)
CP031/ CP031A CP030B
Maximum Input Current vs. Frequency
Insertion Impedance vs. Frequency
(typical)
*
This performance does not apply to CP030-3M model.
Current
(A
rms
)
Frequency (Hz)
3
CP150B CP500
Maximum Input Current vs. Frequency*
Insertion Impedance vs. Frequency*
(typical)
Maximum Input Current vs. Frequency
Insertion Impedance vs. Frequency
(typical)
*This performance does not apply to CP150-6M model.