SU_UM_TME20822_EN.pdf - 第21页
21 Operat ion Smart-UPS SMTL 220 0/3000 RMI2UC/RMI2UCNC EN T ME2 0822 – 08 /202 3 About View UPS information: • UP S Model • UPS Part No. • UPS Seri al No. • UPS Manuf acture Date • Battery Part No. • Bat ter y Inst all …

20
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
Operation
EN TME20822 – 08/2023
Advanced menus
The Advanced menus provide additional options for the UPS and are available only if
the display interface is configured to use the Advanced menus.
Menu General Functions
Status View detailed UPS information:
• Operating Mode
• Efficiency
• Load Power
• Load VA
• Load Amps
• Load Energy
• Battery Charge State
• Estimated Runtime
• Battery Voltage
•Battery Temp
• Input
• Output
• Outlet Groups
• SmartConnect
• Probe 1, Probe 2, when NMC
and sensor probes are
installed
Control Controls the Main and Controlled Outlet Group to turn on, turn off,
shutdown, or reboot:
• UPS Control
• Outlet Group Control
Configuration Configure advanced UPS
settings:
• Language
• Output Voltage
Note: Setting can be
configured only when UPS
output is turned off.
• Green Mode
• Local Power Quality
• Menu Type
• Audible Alarm
• Display
• Sensitivity
• Low Transfer
• High Transfer
• Low Battery Setting
• Auto Self Test
• Reset Energy Meter
• Enter Setup Wizard
• Reset to Factory Defaults
• Site Wiring Fault
• Config Main Group Outlets
• Config Group Outlets (if
Controlled Outlet is available)
• ModBus Settings
• SmartConnect Control
• UPS IP Address Setting
• NMC IP Address Settings (if
NMC is available)
• FW Update Interfaces
• Install FW? (only available if a
firmware update is available)
Test & Diag Perform UPS tests and
diagnostics functions:
• UPS Self Test
•UPS Alarms Test
Logs View the error log for information about UPS errors that have
occurred.

21
Operation
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
EN TME20822 – 08/2023
About View UPS information:
• UPS Model
• UPS Part No.
• UPS Serial No.
• UPS Manufacture Date
• Battery Part No.
• Battery Install Date
• Replace Battery by
• Running UPS FW
• Available UPS FW
Note: Enabled only if a UPS
firmware update is available.
• UPS MAC
• UPS IP Address
• UPS Product Key
• SmartSlot Card (if installed)
Menu General Functions

22
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
Configuration
EN TME20822 – 08/2023
Configuration
General configuration settings
Configuration settings may be changed at any time using the LCD interface or
PowerChute software. This table provides a brief description of the general settings,
for more detailed information on each of these parameters consult application note 80
at www.apc.com.
Setting
Factory
Default
Options Description
High Transfer 253 Vac 253 Vac - 265 Vac To avoid unnecessary battery usage, set the
transfer point higher if the AC voltage is
chronically high and the connected equipment is
known to work under this condition. The Power
Quality setting will automatically change this
setting.
NOTE: Use the Advanced Menus to configure
this setting.
Low Transfer 207 Vac 195 Vac - 207 Vac Sets the transfer point lower if the AC voltage is
chronically low and the connected equipment can
tolerate this condition. This setting may also be
adjusted using the power quality setting.
NOTE: Use the Advanced Menus to configure
this setting.
Sensitivity Normal • Normal
• Reduced
•Low
Selects the level of sensitivity to power events
that the UPS will tolerate.
• Normal: The UPS will go on battery power more
often to provide the cleanest power supply to
the connected equipment.
• Low: The UPS will tolerate more fluctuations in
power and will go on battery power less often.
If the connected load is sensitive to power
disturbances, set the sensitivity to Normal.
Date of Last
Battery
Replacement
Date set at factory. Reset this date when the battery module is replaced.
Display Auto Off • Auto Off
• Auto Dim
•Always On
The UPS can be configured to change the LCD
brightness when the interface has not been used
for 4 minutes.
• Auto Off: The LCD turns off. This is used as the
default to extend LCD lifetime.
• Auto Dim: The LCD switches to a lower
brightness.
• Always On: The LCD is always at the lower
brightness and does not change due to
inactivity.
Audible Alarm On • On
•Off
The UPS will mute all audible alarms if this is set
to Off or when the display buttons are pressed.