21
Operation
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
EN TME20822 – 08/2023
About View UPS information:
UPS Model
UPS Part No.
UPS Serial No.
UPS Manufacture Date
Battery Part No.
Battery Install Date
Replace Battery by
Running UPS FW
Available UPS FW
Note: Enabled only if a UPS
firmware update is available.
UPS MAC
UPS IP Address
UPS Product Key
SmartSlot Card (if installed)
Menu General Functions
22
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
Configuration
EN TME20822 08/2023
Configuration
General configuration settings
Configuration settings may be changed at any time using the LCD interface or
PowerChute software. This table provides a brief description of the general settings,
for more detailed information on each of these parameters consult application note 80
at www.apc.com.
Setting
Factory
Default
Options Description
High Transfer 253 Vac 253 Vac - 265 Vac To avoid unnecessary battery usage, set the
transfer point higher if the AC voltage is
chronically high and the connected equipment is
known to work under this condition. The Power
Quality setting will automatically change this
setting.
NOTE: Use the Advanced Menus to configure
this setting.
Low Transfer 207 Vac 195 Vac - 207 Vac Sets the transfer point lower if the AC voltage is
chronically low and the connected equipment can
tolerate this condition. This setting may also be
adjusted using the power quality setting.
NOTE: Use the Advanced Menus to configure
this setting.
Sensitivity Normal Normal
Reduced
•Low
Selects the level of sensitivity to power events
that the UPS will tolerate.
Normal: The UPS will go on battery power more
often to provide the cleanest power supply to
the connected equipment.
Low: The UPS will tolerate more fluctuations in
power and will go on battery power less often.
If the connected load is sensitive to power
disturbances, set the sensitivity to Normal.
Date of Last
Battery
Replacement
Date set at factory. Reset this date when the battery module is replaced.
Display Auto Off Auto Off
Auto Dim
•Always On
The UPS can be configured to change the LCD
brightness when the interface has not been used
for 4 minutes.
Auto Off: The LCD turns off. This is used as the
default to extend LCD lifetime.
Auto Dim: The LCD switches to a lower
brightness.
Always On: The LCD is always at the lower
brightness and does not change due to
inactivity.
Audible Alarm On On
•Off
The UPS will mute all audible alarms if this is set
to Off or when the display buttons are pressed.
23
Configuration
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
EN TME20822 – 08/2023
Outlet group configuration settings
The Main Outlet Group and the Controlled Outlet Group can be configured to
independently turn off, turn on, shut down, and reboot connected equipment.
The Main and Controlled Outlet Groups can be configured to do the following:
Turn OFF: Disconnect from power immediately and restart only with a manual
command.
Turn ON: Connect to power immediately.
Shutdown: Disconnect power in sequence, and automatically reapply power in
sequence when AC power becomes available.
Reboot: Shut down and restart.
Auto Self Test On start-up
and every 14
days since the
last test
Never
Start-up only
Frequency of test (every 7 to
14 days)
The interval at which the UPS will execute a self-
test.
Reset to
Factory
Default
No Yes/No Restores the UPS factory default settings.
Site Wiring
Fault
Enable Enable/Disable/
Can Ack
Sets the Site Wiring Fault detection to Enable,
Disable or User Can Acknowledge
Output voltage 230 V 220Vac
230Vac
240Vac
Selects the output voltage. This is only settable
when the UPS is turned off.
Select the output voltage appropriate to the
location.
Green Mode Enable Enable
Disable
This will enable or disable Green mode function.
Green Mode conserves energy while the UPS is
operating on line.
SmartConnect
Control
Enable Enable
Disable
This will permit remote configuration changes.
Low Battery
Setting
150 sec Set the value in seconds The UPS will emit an audible alarm when the
remaining runtime has reached this level.
FW Update
Interfaces
Enable Enable
Disable
Enable or disable FW updates.
Serial port
SmartConnect Ethernet port
•SmartSlot
•USB
Communication port through which the FW is to
be updated.
NOTE: This option will get enabled only when
FW Update Interfaces is set to Enable.
Install FW? Don’t Install Next off (Updates the UPS
Firmware next time that the
UPS is turned off)
Now (Updates the UPS
firmware immediately
without interrupting
operations)
•Don't Install
Firmware update: this only appears when new
firmware is available in the flash memory of the
UPS and is ready to be installed
Setting
Factory
Default
Options Description