Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
Configuration
EN TME20822 – 08/2023
Configuration
General configuration settings
Configuration settings may be changed at any time using the LCD interface or
PowerChute software. This table provides a brief description of the general settings,
for more detailed information on each of these parameters consult application note 80
at www.apc.com.
Setting
Factory
Default
Options Description
High Transfer 253 Vac 253 Vac - 265 Vac To avoid unnecessary battery usage, set the
transfer point higher if the AC voltage is
chronically high and the connected equipment is
known to work under this condition. The Power
Quality setting will automatically change this
setting.
NOTE: Use the Advanced Menus to configure
this setting.
Low Transfer 207 Vac 195 Vac - 207 Vac Sets the transfer point lower if the AC voltage is
chronically low and the connected equipment can
tolerate this condition. This setting may also be
adjusted using the power quality setting.
NOTE: Use the Advanced Menus to configure
this setting.
Sensitivity Normal • Normal
• Reduced
•Low
Selects the level of sensitivity to power events
that the UPS will tolerate.
• Normal: The UPS will go on battery power more
often to provide the cleanest power supply to
the connected equipment.
• Low: The UPS will tolerate more fluctuations in
power and will go on battery power less often.
If the connected load is sensitive to power
disturbances, set the sensitivity to Normal.
Date of Last
Battery
Replacement
Date set at factory. Reset this date when the battery module is replaced.
Display Auto Off • Auto Off
• Auto Dim
•Always On
The UPS can be configured to change the LCD
brightness when the interface has not been used
for 4 minutes.
• Auto Off: The LCD turns off. This is used as the
default to extend LCD lifetime.
• Auto Dim: The LCD switches to a lower
brightness.
• Always On: The LCD is always at the lower
brightness and does not change due to
inactivity.
Audible Alarm On • On
•Off
The UPS will mute all audible alarms if this is set
to Off or when the display buttons are pressed.

23
Configuration
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
EN TME20822 – 08/2023
Outlet group configuration settings
The Main Outlet Group and the Controlled Outlet Group can be configured to
independently turn off, turn on, shut down, and reboot connected equipment.
The Main and Controlled Outlet Groups can be configured to do the following:
• Turn OFF: Disconnect from power immediately and restart only with a manual
command.
• Turn ON: Connect to power immediately.
• Shutdown: Disconnect power in sequence, and automatically reapply power in
sequence when AC power becomes available.
• Reboot: Shut down and restart.
Auto Self Test On start-up
and every 14
days since the
last test
• Never
• Start-up only
• Frequency of test (every 7 to
14 days)
The interval at which the UPS will execute a self-
test.
Reset to
Factory
Default
No Yes/No Restores the UPS factory default settings.
Site Wiring
Fault
Enable Enable/Disable/
Can Ack
Sets the Site Wiring Fault detection to Enable,
Disable or User Can Acknowledge
Output voltage 230 V • 220Vac
• 230Vac
• 240Vac
Selects the output voltage. This is only settable
when the UPS is turned off.
Select the output voltage appropriate to the
location.
Green Mode Enable • Enable
• Disable
This will enable or disable Green mode function.
Green Mode conserves energy while the UPS is
operating on line.
SmartConnect
Control
Enable • Enable
• Disable
This will permit remote configuration changes.
Low Battery
Setting
150 sec Set the value in seconds The UPS will emit an audible alarm when the
remaining runtime has reached this level.
FW Update
Interfaces
Enable • Enable
• Disable
Enable or disable FW updates.
• Serial port
• SmartConnect Ethernet port
•SmartSlot
•USB
Communication port through which the FW is to
be updated.
NOTE: This option will get enabled only when
FW Update Interfaces is set to Enable.
Install FW? Don’t Install • Next off (Updates the UPS
Firmware next time that the
UPS is turned off)
• Now (Updates the UPS
firmware immediately
without interrupting
operations)
•Don't Install
Firmware update: this only appears when new
firmware is available in the flash memory of the
UPS and is ready to be installed
Setting
Factory
Default
Options Description

24
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
Configuration
EN TME20822 – 08/2023
In addition, the Main Outlet Group and the Controlled Outlet Group can be configured
to do the following:
• Turn ON or Turn OFF in a specified sequence
• Automatically turn OFF or shut down when various conditions occur
NOTE: If the Main and Controlled Outlet Groups are not configured, all the outlets on
the unit will still provide battery back-up power.
NOTE: The Main Outlet Group functions as a master switch. It will turn on first when
power is applied, and shut off last when there is a power outage and battery run-time
has been exhausted.
The Main Outlet Group must be turned on for the Controlled Outlet Group to turn on.
Setting Factory Default Options Description
Name String
Outlet Group
Outlet Group 1 Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name
String
UPS Outlets
Turn On Delay 0 sec Set the value in
seconds
The amount of time the UPS or the Controlled Outlet
Group will wait between receiving the command to turn on
and the actual startup.
Turn Off Delay • 0 sec (UPS
Outlets)
• 90 sec
(Controlled
Outlet Groups)
Set the value in
seconds
The amount of time the UPS or the Controlled Outlet
Group will wait between receiving the command to turn off
and the actual shut down.
Reboot
Duration
8 sec Set the value in
seconds
The amount of time that the UPS or the Controlled Outlet
Group must remain off before it will restart.
Minimum
Return Time
0 sec Set the value in
seconds
The amount of battery runtime that must be available
before the UPS or the Controlled Outlet Group will turn
on.
Load Shed On
Battery
Disabled • Shutdown with
Delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with
delay
• Disabled
When the unit switches to battery power, the UPS can
disconnect power to the Controlled Outlet Group to save
runtime.
To configure this delay time, use the L
OAD SHED TIME
WHEN ON BATTERY setting.
Load Shed
Time when On
Battery
Disabled Set the value in
seconds
The amount of time the outlets will function on battery
power before they will turn off.