24 Smart-UPS S MTL 22 00/3000 RMI2UC/RMI2UCNC Config uration EN TME2 08 22 – 08/2 023 In add it ion, t he Main O utlet Grou p and the Controlled O ut let Group can be conf igured to do the following: • T urn ON or T urn …

100%1 / 34
23
Configuration
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
EN TME20822 – 08/2023
Outlet group configuration settings
The Main Outlet Group and the Controlled Outlet Group can be configured to
independently turn off, turn on, shut down, and reboot connected equipment.
The Main and Controlled Outlet Groups can be configured to do the following:
Turn OFF: Disconnect from power immediately and restart only with a manual
command.
Turn ON: Connect to power immediately.
Shutdown: Disconnect power in sequence, and automatically reapply power in
sequence when AC power becomes available.
Reboot: Shut down and restart.
Auto Self Test On start-up
and every 14
days since the
last test
Never
Start-up only
Frequency of test (every 7 to
14 days)
The interval at which the UPS will execute a self-
test.
Reset to
Factory
Default
No Yes/No Restores the UPS factory default settings.
Site Wiring
Fault
Enable Enable/Disable/
Can Ack
Sets the Site Wiring Fault detection to Enable,
Disable or User Can Acknowledge
Output voltage 230 V 220Vac
230Vac
240Vac
Selects the output voltage. This is only settable
when the UPS is turned off.
Select the output voltage appropriate to the
location.
Green Mode Enable Enable
Disable
This will enable or disable Green mode function.
Green Mode conserves energy while the UPS is
operating on line.
SmartConnect
Control
Enable Enable
Disable
This will permit remote configuration changes.
Low Battery
Setting
150 sec Set the value in seconds The UPS will emit an audible alarm when the
remaining runtime has reached this level.
FW Update
Interfaces
Enable Enable
Disable
Enable or disable FW updates.
Serial port
SmartConnect Ethernet port
•SmartSlot
•USB
Communication port through which the FW is to
be updated.
NOTE: This option will get enabled only when
FW Update Interfaces is set to Enable.
Install FW? Don’t Install Next off (Updates the UPS
Firmware next time that the
UPS is turned off)
Now (Updates the UPS
firmware immediately
without interrupting
operations)
•Don't Install
Firmware update: this only appears when new
firmware is available in the flash memory of the
UPS and is ready to be installed
Setting
Factory
Default
Options Description
24
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
Configuration
EN TME20822 08/2023
In addition, the Main Outlet Group and the Controlled Outlet Group can be configured
to do the following:
Turn ON or Turn OFF in a specified sequence
Automatically turn OFF or shut down when various conditions occur
NOTE: If the Main and Controlled Outlet Groups are not configured, all the outlets on
the unit will still provide battery back-up power.
NOTE: The Main Outlet Group functions as a master switch. It will turn on first when
power is applied, and shut off last when there is a power outage and battery run-time
has been exhausted.
The Main Outlet Group must be turned on for the Controlled Outlet Group to turn on.
Setting Factory Default Options Description
Name String
Outlet Group
Outlet Group 1 Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name
String
UPS Outlets
Turn On Delay 0 sec Set the value in
seconds
The amount of time the UPS or the Controlled Outlet
Group will wait between receiving the command to turn on
and the actual startup.
Turn Off Delay 0 sec (UPS
Outlets)
90 sec
(Controlled
Outlet Groups)
Set the value in
seconds
The amount of time the UPS or the Controlled Outlet
Group will wait between receiving the command to turn off
and the actual shut down.
Reboot
Duration
8 sec Set the value in
seconds
The amount of time that the UPS or the Controlled Outlet
Group must remain off before it will restart.
Minimum
Return Time
0 sec Set the value in
seconds
The amount of battery runtime that must be available
before the UPS or the Controlled Outlet Group will turn
on.
Load Shed On
Battery
Disabled Shutdown with
Delay
Shutdown
immediately
Turn off
immediately
Turn off with
delay
Disabled
When the unit switches to battery power, the UPS can
disconnect power to the Controlled Outlet Group to save
runtime.
To configure this delay time, use the L
OAD SHED TIME
WHEN ON BATTERY setting.
Load Shed
Time when On
Battery
Disabled Set the value in
seconds
The amount of time the outlets will function on battery
power before they will turn off.
25
Configuration
Smart-UPS SMTL 2200/3000 RMI2UC/RMI2UCNC
EN TME20822 – 08/2023
Modbus settings
Load Shed On
Runtime
Disabled Shutdown with
delay
Shutdown
immediately
Turn off
immediately
Turn off with
delay
Disabled
When the battery runtime falls below the specified value,
the Controlled Outlet Group will turn off.
Configure this time using the L
OAD SHED RUNTIME
R
EMAINING setting.
Load Shed On
Runtime
Remaining
Disabled Set the value in
seconds
When the remaining runtime reaches this level, the
Controlled Outlet Group will turn off.
Load Shed on
Overload
Disabled Disabled
Enabled
In the event of an overload (greater than 100% output
power), the Controlled Outlet Group will immediately turn
off to conserve power for critical loads. The Controlled
Outlet Group will only turn on again with a manual
command.
Setting Factory Default Options Description
Slave ID 1 1- 223 Sets the Modbus slave address of UPS
Ser+USB Disable Enable
Disable
Enables or disables UPS Modbus protocol over serial and
USB ports
TCP Settings
TCP
Protocols
Disable Disable
Read-Only
Read-Write
Enables or disables UPS Modbus TCP/IP protocol
provided by the embedded SmartConnect port.
Disable: Disables UPS Modbus TCP/IP protocol
Read-Only: Modbus master over TCP/IP protocol is only
allowed to get UPS status.
Read-Write: Modbus master over TCP/IP protocol is
allowed to get UPS status and control the UPS.
The port number of UPS Modbus TCP/IP protocol is fixed
at 502.
Master IP
Addr
000.000.000.000 A valid IPv4
address
Specifies the IPv4 address of the Modbus master that will
allow connection to the UPS via Modbus TCP/IP protocol
The Master IP Addr when set as 000.000.000.000 will allow
connection of external Modbus master with any IP address.
When not set as 000.000.000.000, only the Modbus master
with the specified IP address is allowed to connect to the
UPS.
Example: Master IP Address is set to 192.168.0.10, only
Modbus master with IP address 192.168.0.10 could
connect to the UPS.
Setting Factory Default Options Description