UPS 8 – 15 kV A, 230V 50/60 Hz output User ’ s Guide 1 022403 Revision D 51 Figure 55. External battery cabinet models with (2) and (3) sections. Figure 56. UPS models with middle battery and bottom transformer sections.

100%1 / 54
UPS 8 – 15 kVA, 230V 50/60 Hz output
Users Guide
1022403
Revision D
50
11. Dimensional drawings
Figure 52. UPS models with no battery sections.
Figure 53. UPS models with (1) and (2) battery bottom sections.
Figure 54. UPS models with (1) and (2) battery bottom sections plus integrated MBS.
UPS 8 – 15 kVA, 230V 50/60 Hz output
Users Guide
1022403
Revision D
51
Figure 55. External battery cabinet models with (2) and (3) sections.
Figure 56. UPS models with middle battery and bottom transformer sections.
UPS 8 – 15 kVA, 230V 50/60 Hz output
Users Guide
1022403
Revision D
52
12. Technical data
Standards
Environment
Mechanical configuration
Characteristics
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Safety IEC 62040-1-1, EN 62040-1-1 and EN 60950
EMC EN 50091-2
Product IEC 62040-3 and EN 62040-3
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Amb. temperature 0 to +40°C (electronics), 15 to +25°C (batteries)
Relative humidity 0 to 95%, no condensation allowed
Altitude <1000 m above sea level at +40°C
Vibration IEC 68-2-6; max. 0.3 mm (2 to 9 Hz), max. 1 m/s2 (9 to 200 Hz) sinusoidal
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Dimensions
- Width
- Depth
- Height
305 mm
702 mm
817 mm (32 bat) or 1214 mm (2x32 bat)
Weight
- no battery
- 32 battery
- 64 battery
- 32 battery and transformer
65 kg
155 kg
265 kg
270 kg
70 kg
160 kg
270 kg
275 kg
- MBS +15 kg
Colour RAL 9005 black
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Efficiency
- nominal load
Up to 92% Up to 93% Up to 92% Up to 93%
Heat losses <580 W <720 W <870 W <1050 W
Backup time
- load pf 0.7
(+25°C amb.)
10 min (32 bat 7 Ah)
15 min (32 bat 9 Ah)
28 min (64 bat 7 Ah)
33 min (64 bat 9 Ah)
6 min (32 bat 7 Ah)
10 min (32 bat 9 Ah)
20 min (64 bat 7 Ah)
25 min (64 bat 9 Ah)
8 min (32 bat 9 Ah)
15 min (64 bat 7 Ah)
20 min (64 bat 9 Ah)
5 min (32 bat 9 Ah)
10 min (64 bat 7 Ah)
15 min (64 bat 9 Ah)
Noise (ISO 7779) 50 - 53 dB(A) depending on the load