12. Technical data
Standards
Environment
Mechanical configuration
Characteristics
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Safety IEC 62040-1-1, EN 62040-1-1 and EN 60950
EMC EN 50091-2
Product IEC 62040-3 and EN 62040-3
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Amb. temperature 0 to +40°C (electronics), 15 to +25°C (batteries)
Relative humidity 0 to 95%, no condensation allowed
Altitude <1000 m above sea level at +40°C
Vibration IEC 68-2-6; max. 0.3 mm (2 to 9 Hz), max. 1 m/s2 (9 to 200 Hz) sinusoidal
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Dimensions
- Width
- Depth
- Height
305 mm
702 mm
817 mm (32 bat) or 1214 mm (2x32 bat)
Weight
- no battery
- 32 battery
- 64 battery
- 32 battery and transformer
65 kg
155 kg
265 kg
270 kg
70 kg
160 kg
270 kg
275 kg
- MBS +15 kg
Colour RAL 9005 black
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Efficiency
- nominal load
Up to 92% Up to 93% Up to 92% Up to 93%
Heat losses <580 W <720 W <870 W <1050 W
Backup time
- load pf 0.7
(+25°C amb.)
10 min (32 bat 7 Ah)
15 min (32 bat 9 Ah)
28 min (64 bat 7 Ah)
33 min (64 bat 9 Ah)
6 min (32 bat 7 Ah)
10 min (32 bat 9 Ah)
20 min (64 bat 7 Ah)
25 min (64 bat 9 Ah)
8 min (32 bat 9 Ah)
15 min (64 bat 7 Ah)
20 min (64 bat 9 Ah)
5 min (32 bat 9 Ah)
10 min (64 bat 7 Ah)
15 min (64 bat 9 Ah)
Noise (ISO 7779) 50 - 53 dB(A) depending on the load
UPS 8 – 15 kVA, 230V 50/60 Hz output
Users Guide
1022403
Revision D
53
AC input
DC circuit
AC output
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Rectifier input
- S/SC model
- N/NC model
1-phase
3-phases
-
3-phases
-
3-phases
Bypass input 1 phase
Voltage (L.-N) 192 to 253 Volts without using battery
Frequency 45 to 65 Hz
Power factor 0.99
Input distortion < 5% THD(I)
Rated input current
- 3-phases
- 1-phase
12 A
34 A
15 A
43 A
17 A
-
22 A
-
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Management Advanced Battery Management
Nominal voltage 384 Volts
Battery qty 32 pcs.
Float voltage 2.30 VPC
Battery type VRLA 12 Volts
Cut off voltage 1.75 VPC
Battery charging 3 amps, user selectable
UPS 8 kVA 10 kVA 12 kVA 15 kVA
Active power 7,2 kW 9 kW 10,8 kW 13.5 kW
Nro. of phases 1-phase
Frequency 50 Hz or 60 Hz, user selectable
Voltage 220, 230 or 240 Volts, user selectable
Short circuit capability 100 A, < 300 ms 144 A, < 300 ms
Overload capability
10 min >100-110% load
1 min > 110-125% load
5 sec >125-150% load
300 ms >150% load