'操作说明 Hotflow THREE_26_zh.pdf - 第485页

4. TRANSPORT AND STORAGE ENGLISH Translation of the original 28 451820.66.03_EN 2020-05-05

100%1 / 560
Translation of the original ENGLISH 4. TRANSPORT AND ST ORAGE
451820.66.03_EN
2020-05-05
27
4.5 Storing the cooling unit
The cooling unit must be stored in a dry frost-free room on a flat surface or using additional beams.
Permissible storage temperatures: -20°C to +60°C.
The decommissioning steps must always be carried out if the unit is to be stored at ambient
temperatures below 0°C.
(See chapter 8 "Decommissioning/shutdown")
4. TRANSPORT AND STORAGE ENGLISH Translation of the original
28
451820.66.03_EN
2020-05-05
Translation of the original ENGLISH 5. INSTALLATION
451820.66.03_EN
2020-05-05
29
5. INSTALLATION
Follow the safety notes in chapter 1!
At storage temperatures < +10 °C, ensure acclimatization takes place before switching on
(condensate formation)!
Remove transport packaging!
5.1 Indoor installation (standard)
Observe the requirements set out in chapter 1.5.1 ("Installation") in relation to the minimum
room volume required for installing the cooling unit.
The cooling unit should be installed in a frost-free room on an even, horizontal surface with a
suitable load capacity (see weight specifications in technical section).
No foundation-side fastening, separators or vibration absorbers are required.
In a standard installation, the cooling unit and consumer should be installed on the same level.
In the case of different installation conditions, consult with the manufacturer.
To ensure error-free operation of the cooling unit and to permit necessary maintenance and repair
work, the minimum clearances and free spaces must be observed during installation. The air must
be free of dust and aggressive gases.
See technical section (dimension sheet)
These installation conditions must be observed to guarantee that the cooling air can be sucked in
and blown out freely. This largely prevents the heated air blown out at the top from being sucked in
(air short circuit).
In the area of the cooling unit, sufficient air exchange must be ensured to enable effective
heat dissipation.
Calculations must be based on the specified air volume of the fan as well as the quantity of thermal
energy, which is obtained by multiplying the refrigeration capacity by a factor of 1.3.
The air circulation must not be hindered by nearby building parts (walls, ceilings). Recirculation of
the ejected air must be avoided.
See technical section (dimension sheet)
5.2 Outdoor installation (optional)
See chapter 15.6 "Outdoor installation" under "Options"