3.2. Connecting the Power Supply
D79MEC-11-020-A0
This section includes the method of connecting the power cable to the machine.
Refer to Wiring Diagram in the separate manual for more information.
3.2.1 Overview
The AV131 is provided with a step-down transformer.
The machine is wired as in the following:
1) Main switch Breaker
2) Breaker Step-down transformer
3) Step-down transformer Subsequent equipment
The voltage of the step-down transformer is
factory-configured to the value specified by the customer.
Connect the factory power supply (A) and the main switch (B).
This cable should be provided by the user.
=REMARKS=
Should the voltage of factory power supply be changed
due to transfer of the machine, etc., the voltage setting of
the step-down transformer (C) need be changed.
Factory power supply: Provide an appropriate overcurrent
protective fuse for the step-down transformer.
Step-down transformer:
Can be switched to 480V, 420V, 400V, 380V,
220V and 200V.
Make sure that the voltage shown on the
SUPPLY VOLTAGE label agrees with the setting
of the factory power supply. (The label shown on
the right is an example of supply voltage of
200V.)
Ground terminal is labeled as PE.
Factory power supply Machine
Main switch Breaker
Step-down
transformer
Breaker
Circuit protector
A
C
B
This cable
should be
provided by the
user.
D
Step-down
transformer
Main switch
AV131
MAINTENANCE MANUAL
3.2 Connecting the Power Supply
D79MEC-11-020-A0
3.2-2
3.2.2 Connecting Factory Power Supply with Main Power Switch
Preparations
Check that the power voltage of the factory falls within the voltage range shown on the label of the
step-down transformer.
Use of captyre cable (Oil-resistant) is recommended for the power cable.
In order to fix the cable securely with the cable gland, prepare a cable with outer size of 18.5 to 20.5
mm.
It is recommended to use a yellow-and-green spiral stripe coating wire for the ground cable.
The conductor size should be equivalent to the supply power cable.
Use an H sleeve to avoid trouble caused by raveled core.
Recommended terminal Conductor size
H6/20 Weidmuller make AWG10 (6 mm
2
)
Cable gland
3-core cable and
1-core ground cable
L1
L2
L3
PE
Cable gland
4-core cable
L1
L2
L3
PE