6. Troubleshooting 6 - 19 Alarm No. 34 Communication or CRC error between NC and dri ve unit An error was detected in the data received from the NC. Investigation det ails In vestigation results Remedies SV SP The state …

6. Troubleshooting
6 - 18
Alarm No.
31
Overspeed
A rotation speed exceeding the motor's tolerable rotation speed was detected.
Investigation details Investigation results Remedies SV SP
The rapid traverse rate is too fast. Set within the motor's maximum
rotation speed.
1 Check the rapid traverse rate (rapid)
and motor maximum rotation speed.
The speed is within the motor's
maximum rotation speed.
Investigate item 2.
{
The settings are incorrect. Correctly set. 2 Check the settings for the servo
parameters SV001 (PC1), SV002
(PC2), SV018 (PIT) and SV025
(MTYP).
Correctly set. Investigate item 5.
{
The setting is incorrect.
The alarm is detected at 115% of
SP017.
Correctly set. 3 Confirm the spindle parameter
SP017 (TSP) setting.
Correctly set. Investigate item 4.
{
There is a problem. Adjust the PLG output waveform. 4 Confirm the PLG output waveform.
Normal. Investigate item 5.
{
The waveform is overshooting. Increase the acceleration/
deceleration time constant.
5 Check whether the speed waveform
is overshooting.
The waveform is not overshooting. Check if there is any abnormality in
the unit's ambient environment.
(Ex.: Ambient temperature, noise,
grounding)
{ {
Alarm No.
32
Power module overcurrent
The power module's overcurrent protection function activated.
Investigation details Investigation results Remedies SV SP
The alarm occurs before READY ON.
(The drive unit is faulty.)
Check investigation item 2 and
following, and remove the cause of
the fault. Then replace the drive unit.
1 Check the repeatability.
The alarm occurs after READY ON. Investigate item 2.
{ {
The setting is incorrect.
Servo : SV025
Spindle : SP034, SP040, SP257 to
SP384
Correctly set.
2 Check the parameter setting.
• Motor type
The setting is correct. Investigate item 3.
{ {
The setting is large compared to the
standard value.
Set the standard value. 3 Check the parameter settings.
• Current loop gain
• Speed loop gain
The standard value is set. Investigate item 4.
{ {
The power cable is short-circuited. Replace the motor's power cable. 4 Disconnect the UVW phase wiring
from the terminal block, and the
cannon plug from the motor. Check
the insulation with a tester.
There is no problem. Investigate item 5.
{ {
The power cable is short-circuited. Replace the motor's power cable. 5 Check the insulation between the
motor power cable and FG.
There is no problem. Investigate item 6.
{ {
The motor is short-circuited. Replace the motor.
(With the absolute position system,
the zero point must be established.)
6 Connect the cannon plug, and check
the insulation between the power
cable and FG.
There is no problem. Investigate item 7.
{ {
No abnormality is found in particular. Replace the drive unit. 7 Check for any abnormalities in the
motor's ambient environment.
(Ex.: Ambient temperature, cutting
water)
An abnormality was found in the
ambient environment.
Replace the motor and improve the
motor installation environment.
(With the absolute position system,
the zero point must be established.)
{ {

6. Troubleshooting
6 - 19
Alarm No.
34
Communication or CRC error between NC and drive unit
An error was detected in the data received from the NC.
Investigation details Investigation results Remedies SV SP
The state is improved. Replace the cause of the fault. 1 Try replacing the terminator or battery
unit.
The state is not improved. Investigate item 2.
{ {
The connection is incorrect. Replace the cable. 2 Check the NC bus communication
cable connection.
• Is the cable disconnected?
• Is the communication pair cable
connected in reverse?
There is no problem. Investigate item 3.
{ {
The alarm is on the cable
connections.
Replace the cable. 3 Change the order of the connected
drive units.
(The rotary switch does not need to
be changed.)
The alarm is on the unit connections. Investigate item 4.
{ {
No abnormality is found in particular. Replace the unit. 4 Check if there is any abnormality in
the unit's ambient environment.
(Ex. Ambient temperature, noise,
grounding)
An abnormality was found in the
ambient environment.
Take remedies according to the
causes of the abnormality.
Ex. High temperature:
Check the cooling fan.
Incomplete grounding:
Additionally ground.
{ {
Alarm No.
35
NC command error
The movement command data received from the NC was excessive.
Investigation details Investigation results Remedies SV SP
The rapid traverse rate is large. Check the rapid traverse rate limit. 1 Is the rapid traverse rate large for
using a sub-micron system or rotary
axis?
The rate is not especially large. Look for problems on the NC side,
such as not being able to follow up
the position FB.
{ {
Alarm No.
36
Communication or transmission error between NC and drive unit
Communication from the NC was cut off.
Investigation details Investigation results Remedies SV SP
The connector is disconnected (or
loose).
Connect correctly. 1 Check whether the NC bus
communication cable connectors
(CN1A, CN1B) are disconnected.
The state is not improved. Investigate item 2.
{ {
The connection is incorrect. Replace the cable. 2 Check the NC bus communication
cable connection.
• Is the cable disconnected?
• Is the communication pair cable
connected in reverse?
There is no problem. Investigate item 3.
{ {
The alarm is on the cable
connections.
Replace the cable. 3 Change the order of the connected
drive units.
(The rotary switch does not need to
be changed.)
The alarm is on the unit connections. Investigate item 4.
{ {
No abnormality is found in particular. Replace the unit. 4 Check if there is any abnormality in
the unit's ambient environment.
(Ex. Ambient temperature, noise,
grounding)
An abnormality was found in the
ambient environment.
Take remedies according to the
causes of the abnormality.
Ex. High temperature:
Check the cooling fan.
Incomplete grounding:
Additionally ground.
{ {

6. Troubleshooting
6 - 20
Alarm No.
37
Initial parameter error
An illegal parameter was detected in the parameters received from the NC at NC power ON.
"S02 initial parameter error ####" is displayed on the NC screen. #### indicates the incorrect
parameter No.
Investigation details Investigation results Remedies SV SP
SV001 to SV065 (M60S Series: 2201
to 2265)
SP001 to SP384 (M60S Series: 3201
to 3584)
Set the value within the designated
setting range.
1 Check the error parameter No.
SV101 (M60S Series: 2301)
The electronic gears are overflowing.
Check SV001, SV002 and SV018.
{ {
SV102 (M60S Series: 2302)
The absolute position detection
parameter is valid when OSE104 and
OSE105 are connected.
Absolute position control cannot be
used. To use, change to an absolute
position detector.
SV104 (M60S Series: 2304)
No SHG control operation is
provided.
SHG control cannot be used.
{
SV105 (M60S Series: 2305)
No adaptive filter option is provided.
The adaptive filter cannot be used.
{
(Note) Refer to "6-3-4 Parameter numbers at initial parameter error".
Alarm No.
38
Communication or protocol error 1 between NC and drive unit
An error was detected in the communication frame received from the NC.
Investigation details Investigation results Remedies SV SP
1 Check the alarm No. "34" items.
{ {
Alarm No.
39
Communication or protocol error 2 between NC and drive unit
An error was detected in the axis information data received from the NC.
Investigation details Investigation results Remedies SV SP
1 Check the alarm No. "34" items.
{ {
Alarm No.
3A
Overcurrent
An excessive current was detected in the motor drive current.
Investigation details Investigation results Remedies SV SP
Vibration is occurring.
• Set a filter.
• Lower the speed loop gain
(SV005).
1 Check whether vibration is occurring.
There is no vibration. Investigate item 2.
{
The setting is too large. Set an appropriate value. 2 The speed loop gain (SV005) setting
is larger than the standard value.
The setting is approximately the
same as the standard value.
Investigate item 3.
{
The setting is incorrect. Set the standard value. 3 Check the current loop gain.
(SV009, SV010, SV011, SV012)
The standard value is set. Investigate item 4.
{
The power cable is short-circuited. Replace the motor power cable. 4 Disconnect the UVW phase wiring
from the terminal block, and the
cannon plug from the motor. Check
the insulation with a tester.
There is no problem. Investigate item 5.
{
There is a ground fault at the power
cable.
Replace the motor power cable. 5 Check the insulation between the
motor power cable and FG.
There is no problem. Investigate item 6.
{
There is a ground fault in the motor. Replace the mot or.
(With the absolute position system,
the zero point must be established.)
6 Connect the cannon plug, and check
the insulation between the power
cable and FG.
There is no problem. Investigate item 7.
{
No abnormality is found in particular. Replace the drive unit. 7 Check if there is any abnormality in
the motor's ambient environment.
(Ex. Ambient temperature, cutting
water)
An abnormality was found in the
ambient environment.
Improve the installation environment.
(With the absolute position system,
the zero point must be established.)
{