00194440-10_SM_X-Series_Customer_en - 第73页
Service Work 3.1.10 LED Assignment on the Main Distributor Electrics and Control Service Manual SIPLACE X Series 73 3.1.10 3 . 1 . 1 0 L E D A s s ig n m e n t o n t h e M a in D is t r ib u t o r LED Assignment on t he …

Service Work
Electrics and Control 3.1.9 LED Assignment on the Subdistributor
72 Service Manual SIPLACE X Series
3.1.9.4
3.1.9.4 I/O Module for Subdistributor (Outputs) (new)
I/O Module for Subdistributor (Outputs) (new)
nc = not connected (reserve)
X9_2 24 V
X9_3 24 V
X9_4 24 V
X9_5 GND
X9_6 GND
X9_7 GND
X9_8 GND
Terminals I / O Description / Note
Terminals I / O Description / Note
X7_1 Do0 nc
X7_2 Do1 nc
X7_3 Do2 nc
X7_4 Do3 nc
X7_5 Do4 nc
X7_6 Do5 St_Vakuumpumpe EIN
X7_7 Do6 nc
X7_8 Do7 nc
X8_1 Do8 nc
X8_2 Do9 nc
X8_3 Do10 nc
X8_4 Do11 nc
X8_5 Do12
X8_6 Do13
X8_7 Do14
X8_8 Do15
X9_1 24 V
X9_2 24 V
X9_3 24 V
X9_4 24 V
X9_5 GND
X9_6 GND
X9_7 GND
X9_8 GND

Service Work
3.1.10 LED Assignment on the Main Distributor Electrics and Control
Service Manual SIPLACE X Series 73
3.1.10
3.1.10 LED Assignment on the Main Distributor
LED Assignment on the Main Distributor
3.1.10.1
3.1.10.1 I/O Module, Main Distributor (Inputs) [old: 03010004-04]
I/O Module, Main Distributor (Inputs) [old: 03010004-04]
nc = not connected (reserve)
1. LEDs Do 0 to Do 15 (digital outputs)
2. LEDs Di 0 to Di 23 (digital inputs)
► Remove the cover on the main distributor (3) in
sector 2.
► The following table shows the assignment of LEDs at
the CAN input/output module.
If the arrangement of LEDs is active, the LED will
shine.
Terminals I / O Description / Note
X3_1 Di0 M_NotAusSchleife1ok or M_Security Loop ("high" if all safety loops are closed
(protective hoods, emergency STOP buttons, component flaps, changeover
tables).
X3_2 Di1 nc
X3_3 Di2 nc
X3_4 Di3 M_BeKlappe ("high" if one or more flaps open.)
X3_5 Di4 nc
X3_6 Di5 nc
X3_7 Di6 nc
X3_8 Di7 nc
X4_1 Di8 nc
X4_2 Di9 M_Bereit/Message changes from "low" to "high" if the SSK (K6) triggers, only
possible if "Steuerung_EIN" is on (control on).
X4_3 Di10 M_Drucksensor (reserved)
X4_4 Di11 M_PortalCrash1 "low" signal that gantries 1 and 4 are too close,"high" signal
is normal status
X4_5 Di12 nc
X4_6 Di13 M_ServoEnable1 or Control ON/ "high" signal - intermediate circuit voltage for
X/Y servo on axis unit 1 switched through. (K4 message)
X4_7 Di14 nc
X4_8 Di15 M_Drucksensor RV/TwinHead "high" signal if compressed air level reached.
X5_1 Di16 M_NotAusSchleife2ok or M_Security Loop ("high" if all safety loops are closed
(protective hoods, emergency STOP buttons, component flaps, changeover
tables).
X5_2 Di17 M_Haube2 "high" signal if cover 2 is closed
X5_3 Di18 M_BE-Tisch2 "high" signal if changeover table 2 is docked
X5_4 Di19 M_HaubeLP-Ausgabe "high"signal if the cover above the PCB output is
closed.

Service Work
Electrics and Control 3.1.10 LED Assignment on the Main Distributor
74 Service Manual SIPLACE X Series
3.1.10.2
3.1.10.2 I/O Module, Main Distributor (Inputs) [new from B323: 03046225-01]
I/O Module, Main Distributor (Inputs) [new from B323: 03046225-01]
nc = not connected (reserve)
X5_5 Di20 M_NotAusTasteLP-Ausgabe "high" signal if the emergency STOP button is
unlocked.
X5_6 Di21 M_Haube3 "high" signal if cover 3 is closed.
X5_7 Di22 M_BE-Tisch3 "high" signal if changeover table 3 is docked
X5_8 Di23 nc
X6_1 5 V
X6_2 GND
X6_3 GND
X6_4 GND
X6_5 nc
X6_6 nc
X6_7 nc
X6_8 nc
Terminals I / O Description / Note
Terminals I / O Description / Note
X3_1 Di0 M_NotAusSchleife1ok or M_Security Loop ("high" if all safety loops are closed
(protective hoods, emergency STOP buttons, component flaps, changeover
tables).
X3_2 Di1 nc
X3_3 Di2 nc
X3_4 Di3 M_BeKlappe ("high" if one or more flaps open.)
X3_5 Di4 nc
X3_6 Di5 nc
X3_7 Di6 nc
X3_8 Di7 nc
X4_1 Di8 nc
X4_2 Di9 M_Bereit/Message changes from "low" to "high" if the SSK (K6) triggers, only
possible if "Steuerung_EIN" is on (control on).
X4_3 Di10 M_Vakuum OK
X4_4 Di11 M_PortalCrash1 "low" signal that gantries 1 and 4 are too close,"high" signal
is normal status
X4_5 Di12 nc
X4_6 Di13 M_ServoEnable1 or Control ON/ "high" signal - intermediate circuit voltage for
X/Y servo on axis unit 1 switched through. (K4 message)
X4_7 Di14 nc
X4_8 Di15 M_Drucksensor RV/TwinHead "high" signal if compressed air level reached.
X5_1 Di16 24 V M_NotAus-Schleife 2 OK
X5_2 Di17 M_Haube2 "high" signal if cover 2 is closed
X5_3 Di18 M_BE-Tisch2 "high" signal if changeover table 2 is docked
X5_4 Di19 M_HaubeLP-Ausgabe "high"signal if the cover above the PCB output is
closed.