Service Work
3.1.10 LED Assignment on the Main Distributor Electrics and Control
Service Manual SIPLACE X Series 73
3.1.10
3.1.10 LED Assignment on the Main Distributor
LED Assignment on the Main Distributor
3.1.10.1
3.1.10.1 I/O Module, Main Distributor (Inputs) [old: 03010004-04]
I/O Module, Main Distributor (Inputs) [old: 03010004-04]
nc = not connected (reserve)
1. LEDs Do 0 to Do 15 (digital outputs)
2. LEDs Di 0 to Di 23 (digital inputs)
► Remove the cover on the main distributor (3) in
sector 2.
► The following table shows the assignment of LEDs at
the CAN input/output module.
If the arrangement of LEDs is active, the LED will
shine.
Terminals I / O Description / Note
X3_1 Di0 M_NotAusSchleife1ok or M_Security Loop ("high" if all safety loops are closed
(protective hoods, emergency STOP buttons, component flaps, changeover
tables).
X3_2 Di1 nc
X3_3 Di2 nc
X3_4 Di3 M_BeKlappe ("high" if one or more flaps open.)
X3_5 Di4 nc
X3_6 Di5 nc
X3_7 Di6 nc
X3_8 Di7 nc
X4_1 Di8 nc
X4_2 Di9 M_Bereit/Message changes from "low" to "high" if the SSK (K6) triggers, only
possible if "Steuerung_EIN" is on (control on).
X4_3 Di10 M_Drucksensor (reserved)
X4_4 Di11 M_PortalCrash1 "low" signal that gantries 1 and 4 are too close,"high" signal
is normal status
X4_5 Di12 nc
X4_6 Di13 M_ServoEnable1 or Control ON/ "high" signal - intermediate circuit voltage for
X/Y servo on axis unit 1 switched through. (K4 message)
X4_7 Di14 nc
X4_8 Di15 M_Drucksensor RV/TwinHead "high" signal if compressed air level reached.
X5_1 Di16 M_NotAusSchleife2ok or M_Security Loop ("high" if all safety loops are closed
(protective hoods, emergency STOP buttons, component flaps, changeover
tables).
X5_2 Di17 M_Haube2 "high" signal if cover 2 is closed
X5_3 Di18 M_BE-Tisch2 "high" signal if changeover table 2 is docked
X5_4 Di19 M_HaubeLP-Ausgabe "high"signal if the cover above the PCB output is
closed.

Service Work
Electrics and Control 3.1.10 LED Assignment on the Main Distributor
74 Service Manual SIPLACE X Series
3.1.10.2
3.1.10.2 I/O Module, Main Distributor (Inputs) [new from B323: 03046225-01]
I/O Module, Main Distributor (Inputs) [new from B323: 03046225-01]
nc = not connected (reserve)
X5_5 Di20 M_NotAusTasteLP-Ausgabe "high" signal if the emergency STOP button is
unlocked.
X5_6 Di21 M_Haube3 "high" signal if cover 3 is closed.
X5_7 Di22 M_BE-Tisch3 "high" signal if changeover table 3 is docked
X5_8 Di23 nc
X6_1 5 V
X6_2 GND
X6_3 GND
X6_4 GND
X6_5 nc
X6_6 nc
X6_7 nc
X6_8 nc
Terminals I / O Description / Note
Terminals I / O Description / Note
X3_1 Di0 M_NotAusSchleife1ok or M_Security Loop ("high" if all safety loops are closed
(protective hoods, emergency STOP buttons, component flaps, changeover
tables).
X3_2 Di1 nc
X3_3 Di2 nc
X3_4 Di3 M_BeKlappe ("high" if one or more flaps open.)
X3_5 Di4 nc
X3_6 Di5 nc
X3_7 Di6 nc
X3_8 Di7 nc
X4_1 Di8 nc
X4_2 Di9 M_Bereit/Message changes from "low" to "high" if the SSK (K6) triggers, only
possible if "Steuerung_EIN" is on (control on).
X4_3 Di10 M_Vakuum OK
X4_4 Di11 M_PortalCrash1 "low" signal that gantries 1 and 4 are too close,"high" signal
is normal status
X4_5 Di12 nc
X4_6 Di13 M_ServoEnable1 or Control ON/ "high" signal - intermediate circuit voltage for
X/Y servo on axis unit 1 switched through. (K4 message)
X4_7 Di14 nc
X4_8 Di15 M_Drucksensor RV/TwinHead "high" signal if compressed air level reached.
X5_1 Di16 24 V M_NotAus-Schleife 2 OK
X5_2 Di17 M_Haube2 "high" signal if cover 2 is closed
X5_3 Di18 M_BE-Tisch2 "high" signal if changeover table 2 is docked
X5_4 Di19 M_HaubeLP-Ausgabe "high"signal if the cover above the PCB output is
closed.

Service Work
3.1.10 LED Assignment on the Main Distributor Electrics and Control
Service Manual SIPLACE X Series 75
3.1.10.3
3.1.10.3 I/O Module for Main Distributor (Outputs) (old)
I/O Module for Main Distributor (Outputs) (old)
nc = not connected (reserve)
X5_5 Di20 M_NotAusTasteLP-Ausgabe "high" signal if the emergency STOP button is
unlocked.
X5_6 Di21 M_Haube3 "high" signal if cover 3 is closed.
X5_7 Di22 M_BE-Tisch3 "high" signal if changeover table 3 is docked
X5_8 Di23 nc
X6_1 nc
X6_2 nc
X6_3 GND
X6_4 nc
X6_5 nc
X6_6 nc
X6_7 nc
X6_8 nc
Terminals I / O Description / Note
Terminals I / O Description / Note
X7_1 Do0 nc
X7_2 Do1 St_Ein or software release
When a "high" signal is permanently supplied to this port (24 V), the HF
can be put into operation. The message M_Ready changes from "low"
to "high" (IO1/Di9), if relay K5 has latched (24 V). The emergency stop
loop1 and the start buttons to the protective contactor combination -
SSK (K6). Once all 6 hoods are closed, all 4 component flaps are
closed, the two EMERGENCY STOP buttons unlocked and all compo-
nent trolleys docked into place, the protective contactor combination
can be activated with one of the start buttons. The SSK (protective con-
tactor combination) switches:
1. The contactors K2, K3 and K4 on and the intermediate circuit volt-
age (somewhat delayed) is supplied to the X, Y and star servo axis
boards.
2. The operating voltage,
3. The compressed air (valve) to the tape cutters.
4. Two safety loops for the MTCs.
5. The operating voltage for the "PCB conveyor" motors on.
X7_3 Do2 St_Druckluft (VHS)
X7_4 Do3 St_DruckluftRV/TwinHead pneumatic OFF (a "low" signal opens the
compressed air main valve. A "high" signal closes this.
X7_5 Do4 St_BauteilZähler/Each "high" pulse increases the counter by one.
X7_6 Do5 nc
X7_7 Do6 nc
X7_8 Do7 nc
X8_1 Do8 nc
X8_2 Do9 nc
X8_3 Do10 nc
X8_4 Do11 nc