4 Converting the power supply on the MTC2 Asse mbly Instructions, Converting the Power Supply 4.5 Converting the power supply from 3 x 208 VAC to 3 x 400 VAC 12/2013 Edition 186 4.5.1 Conversion work on the electronic p …

Assembly Instructions, Converting the Power Supply 4 Converting the power supply on the MTC2
12/2013 Edition 4.5 Converting the power supply from 3 x 208 VAC to 3 x 400 VAC
185
4.4.2 Checking the protective wire connections, fitting the covers
Check that the detached protective earth wires have been reconnected correctly.
Fit the cover.
4.4.3 Carry out the safety check to DIN EN 60 204
When the conversion is complete, carry out a safety check to DIN EN 60 204.
Follow the procedure described in section 2, page 146 onwards.
4
4.5 Converting the power supply from 3 x 208 VAC to 3 x 400 VAC
Dock the MTC2 out of the placement machine.
RISK OF DEATH 4
Disconnect the MTC2 from the main power supply.
Remove the plug for the communication cable from the placement machine.
Take suitable action to ensure that the MTC2 cannot be connected to the power supply during
the conversion work.
Put up warning signs to indicate that work is being carried out on the electrical system.

4 Converting the power supply on the MTC2 Assembly Instructions, Converting the Power Supply
4.5 Converting the power supply from 3 x 208 VAC to 3 x 400 VAC 12/2013 Edition
186
4.5.1 Conversion work on the electronic panel
4
Fig. 4 - 4 Position of the electronic panel
(1) Electronic panel
(2) Terminal block X01
(3) Motor contactor Q01
(4) Door, left-hand side
Open the left door.
Release the screws for the electronic panel cover.
Lift off the cover.

Assembly Instructions, Converting the Power Supply 4 Converting the power supply on the MTC2
12/2013 Edition 4.5 Converting the power supply from 3 x 208 VAC to 3 x 400 VAC
187
Remove the six transverse jumpers from feed-through terminals 1-2, 3-4, 5-6, 7-8, 9-10 and
11-12 on terminal block X01 (point 2 in Fig. 4 - 4
).
On terminal block X01, plug in three transverse jumpers between feed-through terminals 2-3,
6-7 and 10-11 (BR see Fig. 4 - 5
).
Leave the tripping current setting unchanged at 3.5 A on motor contactor Q01.
4
Fig. 4 - 5 MTC2 electronic panel - jumper set for 3 x 400 VAC
JMPJumper, 3 x 4
Q01 Motor contactor 4
X01 terminal block 4
JMP (3 x 400 VAC) 4