11. OPTI ONS AND P ERI PHER AL E QUIP MENT 11 - 126 MEMO

11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 125
(3)
Fuses (between P/+ and P4, between N/- and N-)
The following table shows the recommended fuses which are to be installed between the FR-XC-(H) a
nd
servo amplifier.
Servo amplifier capacity
[kW]
200 V class 400 V class
Fuse rating [A] Model (Note) Fuse rating [A] Model (Note)
0.1 20 6.900CPGR10.38 0020
0.2 20 6.900CPGR10.38 0020
0.4 25 6.900CPGR10.38 0025
0.6 25 6.900CPGR10.38 0025 20 6.900CPGR10.38 0020
0.75 30 6.900CPGR10.38 0030
1 32 6.900CPGR10.38 0032 20 6.900CPGR10.38 0020
2 63 6.9URD30TTF0063 25 6.900CPGR10.38 0025
3.5 80 6.9URD30TTF0080 63 6.9URD30TTF0063
5 160 6.9URD30TTF0160 80 6.9URD30TTF0080
7 200 6.9URD30TTF0200 100 6.9URD30TTF0100
11 250 6.9URD30TTF0250 160 6.9URD30TTF0160
15 315 6.9URD30TTF0315 160 6.9URD30TTF0160
22 350 6.9URD30TTF0350 200 6.9URD30TTF0200
Note. Manufacturer: Mersen Fma Japan KK
Service inquiries: Sun-wa Technos Corp.
(4) Mol
ded-case circuit breakers/earth-leakage current breakers and magnetic contactors
Recommended molded-case circuit breakers/earth-leakage current breakers and magnetic contactors
are listed in the table below.
(a) 200 V class
Item
FR-XC-_
7.5K 11K 15K 22K 30K 37K 55K
Molded-case circuit
breaker or earth-
leakage current
breaker (Note)
100AF 60A
(30AF 30A)
100AF 75A
(50AF 50A)
225AF 125A
(100AF 75A)
225AF 175A
(100AF 100A)
225AF 225A
(125AF 125A)
400AF 250A
(125AF 125A)
400AF 400A
(225AF 175A)
Magnetic contactor
(Note)
S-T35
(S-T21)
S-T50
(S-T35)
S-T65
(S-T50)
S-T100
(S-T65)
S-N125
(S-T80)
S-N150
(S-T100)
S-N220
(S-N125)
Note. Models in parentheses can be used when the rated capacity of multifunction regeneration converter ≥ total capacity of connected
servo amplifiers × 2.
(b) 400
V class
Item
FR-XC-H_
7.5K 11K 15K 22K 30K 37K 55K
Molded-case circuit
breaker or earth-
leakage current
breaker (Note)
30AF 30A
(30AF 15A)
50AF 50A
(30AF 20A)
100AF 60A
(30AF 30A)
100AF 100A
(50AF 50A)
225AF 125A
(60AF 60A)
225AF 150A
(100AF 75A)
225AF 200A
(100AF 100A)
Magnetic contactor
(Note)
S-T21
S-T25
(S-T21)
S-T35
(S-T21)
S-T50
(S-T25)
S-T65
(S-T35)
S-T80
(S-T50)
S-N125
(S-T65)
Note. Models in parentheses can be used when the rated capacity of multifunction regeneration converter ≥ total capacity of connected
servo amplifiers × 2.

11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 126
MEMO

12. ABSOLUTE POSITION DETECTION SYSTEM
12 - 1
12. ABSOLUTE POSITION DETECTION SYSTEM
CAUTION
If [AL. 25 Absolute position erased] or [AL. E3 Absolute position counter warning]
has occurred, always perform home position setting again. Otherwise, it may
cause an unexpected operation.
If [AL. 25], [AL. 92], or [AL. 9F] occurs due to such as short circuit of the battery,
the MR-BAT6V1 battery can become hot. Use the MR-BAT6V1 battery with case
to prevent getting burnt.
POINT
Refer to section 11.8 for the replacement procedure of the battery.
There are three types of batteries, MR-BAT6V1SET, MR-BAT6V1BJ, and MR-
BT6VCASE available to construct the absolute position detection system. MR-
BAT6V1BJ has the following advantages compared to other batteries.
You can disconnect the encoder cable from the servo amplifier.
You can replace the battery with the control circuit power supply off.
When absolute position data is erased from the encoder, always execute home
position setting before operation. The absolute position data of the encoder will
be erased in the followings. Additionally, when the battery is used out of
specification, the absolute position data can be erased.
MR-BAT6V1SET and MR-BT6VCASE
The encoder cable was disconnected.
The battery was replaced when the control circuit power supply was off.
MR-BAT6V1BJ
A connector or cable was disconnected between the servo motor and battery.
The battery was replaced with procedures other than those of (6) in section
11.8.3.
12.1 Summary
12.1.1 Features
For normal operation, the encoder consists of a detector designed to detect a position within one revolution
and a cumulative revolution counter designed to detect the number of revolutions.
The absolute position detection system always detects the absolute position of the machine and keeps it
battery-backed, independently of whether the servo system controller power is on or off. Therefore, once
home position return is made at the time of machine installation, home position return is not needed when
power is switched on thereafter.
Even at a power failure or a malfunction, the system can be easily restored.