Page 70 Vision XP+ V AC 3 Setup Instructions 3.2 T emperature Channels Operating Instructions V ersion 1.5 List: [T emperaturRegle r] 0=Ht.Cont[0] ; zone 1 top 1=Ht.Cont[1] ; zone 2 top 2=Ht.Cont[2] ; zone 3 top 3=Ht.Con…

100%1 / 142
Vision XP+ VAC Page 69
3 Setup Instructions
3.2 Temperature Channels
Operating Instructions
Version 1.5
If the cooling is located in another zone the control channel has to be en-
tered from the list (see page40).
Example 1
An system has cooling in zone 4 bottom instead of standard „cooling last
pre-heating zone“.
CoolPre_1: 13
CoolPre_2: 0
CoolPre_3: 0
Example 2
An system has cooling in zone 4 bottom instead of standard „cooling last
pre-heating zone“ and cooling in zone 1 bottom instead of cooling zone1
top.
CoolPre_1: 13
CoolPre_2: 10
CoolPre_3: 0
Page 70 Vision XP+ VAC
3 Setup Instructions
3.2 Temperature Channels
Operating Instructions
Version 1.5
List: [TemperaturRegler]
0=Ht.Cont[0] ; zone 1 top
1=Ht.Cont[1] ; zone 2 top
2=Ht.Cont[2] ; zone 3 top
3=Ht.Cont[3] ; zone 4 top
4=Ht.Cont[4] ; zone 5 top
5=Ht.Cont[5] ; zone 6 top
6=Ht.Cont[6] ; zone 7 top
7=Ht.Cont[7] ; zone 8 top
8=Ht.Cont[8] ; zone 9 top
9=Ht.Cont[9] ; zone 10 top
10=Ht.Cont[10] ; zone 1 bottom
11=Ht.Cont[11] ; zone 2 bottom
12=Ht.Cont[12] ; zone 3 bottom
13=Ht.Cont[13] ; zone 4 bottom
14=Ht.Cont[14] ; zone 5 bottom
15=Ht.Cont[15] ; zone 6 bottom
16=Ht.Cont[16] ; zone 7 bottom
17=Ht.Cont[17] ; zone 8 bottom
18=Ht.Cont[18] ; zone 9 bottom
19=Ht.Cont[19] ; zone 10 bottom
20=Ht.Cont[20] ; peak 1 top
21=Ht.Cont[21] ; peak 2 top
22=Ht.Cont[22] ; peak 3 top
23=Ht.Cont[23] ; peak 4 top
24=Ht.Cont[24] ; peak 5 top
25=Ht.Cont[25] ; peak 1 bottom
26=Ht.Cont[26] ; peak 2 bottom
27=Ht.Cont[27] ; peak 3 bottom
28=Ht.Cont[28] ; peak 4 bottom
29=Ht.Cont[29] ; peak 5 bottom
30=Ht.Cont[30] ; monitoring zone 1
31=Ht.Cont[31] ; monitoring zone 2
32=Ht.Cont[32] ; monitoring zone 3
33=Ht.Cont[33] ; monitoring zone 4
34=Ht.Cont[34] ; monitoring zone 5
35=Ht.Cont[35] ; monitoring zone 6
36=Ht.Cont[36] ; monitoring zone 7
37=Ht.Cont[37] ; monitoring zone 8
38=Ht.Cont[38] ; monitoring zone 9
39=Ht.Cont[39] ; monitoring zone 10
40=Ht.Cont[40] ; monitoring peak 1
41=Ht.Cont[41] ; monitoring peak 2
42=Ht.Cont[42] ; monitoring peak 3
43=Ht.Cont[43] ; monitoring peak 4
44=Ht.Cont[44] ; monitoring peak 5
50=Ht.Cont[45] ; monitoring cooling 1
Vision XP+ VAC Page 71
3 Setup Instructions
3.2 Temperature Channels
Operating Instructions
Version 1.5
51=Ht.Cont[46] ; monitoring cooling 2
52=Ht.Cont[47] ; monitoring cooling 3
53=Ht.Cont[48] ; monitoring cooling 4
54=Ht.Cont[49] ; monitoring cooling 5
55=Ht.Cont[50] ; monitoring cooling 6
56=Ht.Cont[51] ; monitoring cooling 7
60=Ht.Cont[52] ; monitoring water 1
61=Ht.Cont[53] ; FMX pipe
65=Ht.Cont[54] ; monitoring flux 1
66=Ht.Cont[55] ; monitoring flux 2
70=Ht.Cont[56] ; monitoring meassuring 1
71=Ht.Cont[57] ; monitoring meassuring 2
72=Ht.Cont[58] ; monitoring meassuring 3
73=Ht.Cont[59] ; monitoring meassuring 4
74=Ht.Cont[60] ; monitoring meassuring 5
75=Ht.Cont[61] ; monitoring meassuring 6