Advanced Software Me lter Configuration 7 -15 Part 1121836_03 E 1 1/2014 Nordson Corporation Defining Pu mp Remote Contro l Use pump remote control to manipulate the pump from a locatio n other than from the melte r itse…

100%1 / 230
Advanced Software Melter Configuration
7-14
Part 1121836_03
E 11/2014 Nordson Corporation
Modifying the Low to Empty Container Timer
You can configure the melter to switch the pump Off, after a predefined
number of seconds when the Low Level indicator appears.
Setting Default Options
Container Low to Empty Timer 0 Seconds
S
Minimum: 0 Seconds
S
Maximum: 120 Seconds
Pump - Advanced
Done
Pump Off Delay Infinite
Off
Pump Off Delay Time
0 Sec.
Pump Calibration
On
Container Low to Empty
Timer
0 Sec.
Auto Pump
Off
Remote Control
1. Access the Home screen, touch
Pump
GTL
45 RPM
then the Advanced button
2. Touch Container Low to Empty Timer and the number of seconds you
want to continue production before switching the pump Off.
3. Touch Done.
NOTE: When the melter detects a Low Level, the following melter status
appears:
System Status:
Ready Low Level
When time elapses, the pump switches off, and although the heaters remain
On, the Platen and all enabled external zones cool to their Standby
temperatures.
Advanced Software Melter Configuration
7-15
Part 1121836_03
E 11/2014 Nordson Corporation
Defining Pump Remote Control
Use pump remote control to manipulate the pump from a location other than
from the melter itself.
Pump - Advanced
Done
Pump Off Delay Infinite
Off
Pump Off Delay Time
0 Sec.
Pump Calibration
On
Container Low to Empty
Timer
0 Sec.
Auto Pump
Off
Remote Control
1. From the Home Display touch
Master
Controls
2. Touch Settings, then Input.
3. Touch the Input number corresponding to what you have already
hard-wired (step 1) and touch Pump Control.
4. Touch Done.
NOTE: The Pump Control button changes to half green, half
white, indicating the pump is controlled from a remote location.
Advanced Software Melter Configuration
7-16
Part 1121836_03
E 11/2014 Nordson Corporation
Calibrating Pumps
Use Pump Calibration to make sure the displayed pump RPM is accurate.
Pump - Advanced
Done
Pump Off Delay Infinite
Off
Pump Off Delay Time
0 Sec.
Pump Calibration
On
Container Low to Empty
Timer
0 Sec.
Auto Pump
Off
Remote Control
Done
Cancel
7 8 9
4 5 6
1 2 3
0
Pump Calibration RPM
Measured RPM:
Home
Pump RPM calibration should Only be
done by trained technicians. While the
pump is running from 70% to 95% of full
speed, use a tachometer to measure
actual pump RPM.
.
1. Wire a tachometer to the pump.
1. Access the Home screen, touch
Pump
GTL
45 RPM
then the Advanced button
2. Touch Pump Calibration and run the pump at approximately 7o to 95%
of full speed. Enter the RPM displayed on the tachometer.
3. Touch Done.
NOTE: Refer to the previous chapter, Configuring Pumps for more
information.