ThermoFlex-Manual.pdf - 第64页

Section 4 4-6 ThermoFlex Thermo Scientific Setu p Loop ( ) Use the Setup Loop to adjust/v erify the following controller settings . • Scales: temperature in °C or °F , ow in liters per minute or gallons per minute (only …

100%1 / 138
Section 4
ThermoFlex 4-5
Thermo Scientific
SP
xx.x C
xx.x C
mode
enter
enter
Setpoint Loop
( )
• Ensure the controller is either a blank screen or displaying the process
uid temperature.
• Press the
key and the controller display will alternate between SP
and the setpoint value.
• If no change is required press the
key to return the controller to
the previous display.
• If a setpoint change is required, use the
keys.
The setpoint range is +5°C to +40°C (41°F to 104°F).
Note If the are not used within one minute the controller will time
out and return to the previous display, any changes will not be saved.
• Once the desired value is displayed press the key to conrm the
change.
• The controller will return to the process uid temperature display or a
blank screen.
indicates the controller
display is alternating between the
two displays.
Figure 4-5 Setpoint Loop
or
Section 4
4-6 ThermoFlex
Thermo Scientific
Setup Loop
( )
Use the Setup Loop to adjust/verify the following controller settings.
• Scales: temperature in °C or °F, ow in liters per minute or gallons per
minute (only chillers with an optional ow transducer), and pressure in
PSI, bar or kPa
• High and low temperature alarm limits
• High and low pump discharge pressure alarm limits and time delays
• Chiller reaction to a temperature, pressure or ow (optional) alarm limit
(continue to run or shut down)
• Audible alarm enabled/disabled
• View/change the fan speed (ThermoFlex2500 air-cooled only)
• Auto restart feature enabled/disabled
• Preventive care cleaning frequency reminder for air and uid lters
Optional Features:
• Global voltage
• Analog I/O
• Auto rell alarm
• DI lter cartridge preventive maintenance interval
• High/low ow alarm limits
• Serial communications
• Anti drainback valve position
• Save or not save
all
changes
To enter the Setup Loop ensure the controller display is either a blank
screen (chiller off) or displaying the process uid temperature. Press the
key and the display will indicate SP, press it again to display SEtuP.
Press the
key to continue, or press twice to return to the
process uid temperature or blank display.
Use
to sequence down through the loop. Use to
sequence back through the loop up to the Hi t display, see next page.
To change any parameter:
Press the
key.
Use the keys to change a displayed value.
Press
key to conrm the change and bring up the next display.
Section 4
ThermoFlex 4-7
Thermo Scientific
diA9
SP
SEtuP
enter
mode
mode
mode
mode
xx.x C
xx.x C
xx
xx
Hi t
UnitS
Lo t
Lo t
xx
xx
xx
xx
Hi P1
Lo P1
Hi P1
dELAY
enter
enter
enter
enter
enter
enter
enter
enter
enter
Hi t
UnitS
degx
Lo P1
Figure 4-6 Setup Loop (All Chillers)
or
or
Continued on next page.
• UnitS are the temperature, uid ow (only chillers with an
optional ow transducer) and pressure display scales.
Scales:
°C or °F Defaults: °C
GPM or LPM GPM
PSI, Bar or kPa PSI
• Hi t is the uid's High Temperature alarm limit.
Range:
+3°C to +42°C Default: +42°C
Exceeding this limit ashes Hi t and, if enabled, sounds the
alarm. The chiller reaction depends on the alarm conguration
(see ALr on next page).
• Lo t is the uid's Low Temperature alarm limit.
Range: +3°C to +42°C
Default: +3°C
Falling below this limit ashes Lo t and, if enabled, sounds
the alarm. The chiller reaction depends on the alarm
conguration (see ALr on next page).
• Hi P1 is the pump's High Pressure discharge alarm limit.
T 1 T 0 Pump Range: 3 to 100 PSI Default: 100 PSI
T 5 Pump Range: 2 to 105 PSI Default: 105 PSI
P 1 P 2 Pump Range: 3 to 100 PSI Default: 100 PSI
P 3 Pump 60Hz Range: 3 to 46 PSI Default: 46 PSI
P 3 Pump 50Hz Range: 3 to 32 PSI Default: 32 PSI
P 4 Pump 60Hz Range: 3 to 85 PSI Default: 85 PSI
P 4 Pump 50Hz Range: 3 to 60 PSI Default: 60 PSI
P 5 Pump 60Hz Range: 3 to 87 PSI Default: 87 PSI
P 5 Pump 50Hz Range: 3 to 56 PSI Default: 56 PSI
Exceeding this limit ashes Hi P1 and, if enabled, sounds
the alarm (see Sound on next page).
• dELAY is the length of time the pump can exceed the
Hi P1 alarm limit. Note This feature is only active if the
chiller is congured to shut down with a pressure alarm.
P
1, P 2, T 0 and T 1 Range: 0 to 30 seconds
Default: 0 seconds
P 3 - P 5, T 5 Range: 0 to 60 seconds Default: 0 seconds
Exceeding this limit ashes Hi P1 and, if enabled, sounds
the alarm. The chiller reaction depends on the alarm
conguration (see ALr on next page).