XJ3-G-PHASE-FAILURE-AND-PHASE-SEQUENCE-PROTECTIVE-RELAY-Catalog.pdf - 第2页
614 B .3 Relay Protection R elays P - 3. T echnical data 4. Wiring diagram 5. Overall and mounting dimensions (mm) Note: In the example diagram for application circuit, protective relay can provide protection only under …

613
B.3 Relay Protection RelaysP-
XJ3 Series Phase Failure and
Phase Sequence Protection Relays
1. General
2. Type designation
Phase failure and phase sequence protective relay (hereinafter
referred to as relay) is applicable to control circuits with
frequency of AC 50Hz/60Hz and rated control power
supply voltage up to AC380V, for protection of phase
failure, phase sequence, overvoltage and undervoltage.
XJ3-G series phase failure and phase sequence protective
relay(“relay” in short) is mainly used in control circuit with AC
frequency of 50Hz/60Hz and rated control supply voltage up
to AC380V for the protection and control of fault status such as
open phase, phase sequence and three-phase voltage imbalance.
Standards:IEC/EN 60947-5-1.
Remodel(derived model)
Design sequence No.
XJ
3 -
G:monochrome luminotron fault indication type
(open-phase, phase sequence, three-phase voltage
imbalance)
G1:monochrome luminotron fault indication type
(open-phase, phase sequence)
D: multifunction protection,multimode indication type
Phase-failure and phase-sequence protective relay

614
B.3 RelayProtection Relays P-
3. Technical data
4. Wiring diagram
5. Overall and mounting dimensions (mm)
Note: In the example diagram for application circuit, protective relay can provide protection only under the condition of phase-failure
occurring at terminal 1, 2, 3 and among three phase of power supply A, B, C.
XJ3-G series,wiring diagram XJ3-D wiring diagram
XJ3-G series overall and mouting demensions
Type XJ3-G XJ3-G1 XJ3-D
Protection function
open-phase,phase sequence,three-phase
voltage imbalance,unbalance≥8%-13%
open-phase,phase sequence Phase failure, phase sequence, overvoltage, undervoltage
Overvoltage protection(AC)
AC380V~AC460V adjustable, operating time:1.5s~4s adjustable
Undervoltage protection(AC)
AC300V~AC380V adijustable, operating time:2s~9s adjustable
Operating voltage AC 380V 50Hz/60Hz, Allowable fluctuating range±10% AC380 50Hz/60Hz
Contact number 1 normally open & 1 normally close 1 group changeover
Contact capacity Ue/le: AC-15 240V/0.75A,415V/0.47A;; lth:5A Ue/le: AC-15 415V/0.47A; lth:3A
Phase-failure and
phase-sequence protection
Reacting time≤2s Reacting time≤1s
Electrical life 1×10
5
Mechanical life 1×10
6
Ambient temperature -5℃ ~40℃
Installation mode TH35-7.5(thickness 1.0 mm) rail 35mm Track installation or soleplate mounting
FU
A
B C
KM
KM
Load
KM
3
4 5
5
6
6
7
8
StopStart
XJ
XJ
2
1
FUI
QFI
L1 L2 L3
KM
KM
Load
KM
L2
L2
L3 Ta
Tb
Tc
Ta
Tc
STP
ST
L1
L1
82max
15.5
9
2×Φ4.5
8×Φ4
2×Φ5
≥90
53.7±0.37
35.1±0.28
60.8±0.37
84max
46max
81.5max
36±0.28
36±0.28
45.5max
76.5max

615
B.3 Relay Protection RelaysP-
XJ3 D AC380V
Functional code Control voltageProduct Series
D: phase sequence, phase failure, overvoltage, undervoltage
G: phase sequence, phase failure, three-phase unbalance
G1: phase sequence, phase failure
AC380V
Control
voltage
Contact ability
Operating time
(phase failure, phase
sequence)
Contact
group
Description Code
AC380V 240V/0.75A,Ith:5A ≤1s 1Z XJ3-D AC380V 284003
AC380V 240V/0.75A,Ith:5A ≤2s 1Z XJ3-G AC380V 284004
AC380V 240V/0.75A,Ith:5A ≤2s 1Z XJ3-G1 AC380V 328170