rsen_e.pdf - 第2页
RSEN Series 2 Notes (1) With inverse time circuit breaker . See UL 508 report on website See website for detailed specications, test methods and installation manual RSEN technical le s * Separate mounting bracket Click…

RSEN Series
Single phase 250Vac 3 to 300A EMC Filters
with DIN rail option
RSEN Series
1
The RSEN single-phase EMC lters are enclosed in a compact case and part numbers up to 30A can be either chassis or DIN rail mounted (up to 30A) with low
leakage current options. They are rated for 250Vac with fteen current ratings of 3 to 300A enabling the optimum attenuation to match the current rating. The series
uses TDK’s ferrite core material to provide noise attenuation. The connection terminals are integrated into the case with both the screws and terminal covers captive.
This avoids dropped or lost hardware. The RSEN 3A to 30A models are UL certied for a short circuit current rating of up to 14kA and the 40, 50 and 60A models
35kA with the appropriate breaker.
Features Benets
• 3 to 300A Current Ratings
• DIN Rail Bracket Option
• Captive Hardware
• Safety Certied
• Optimizes the Attenuation for the Current Rating
• Flexible Mounting
• No Lost Screws or Terminal Covers
• Global Use
https://product.tdk.com/en/search/emc/emc/power-line/tec_data/nf_rsen
https://www.emea.lambda.tdk.com/uk/products/r-series
Model Selector
Model Selector
Rated HV Leakage Current Maximum Attenuation frequency range (MHz)
Model Current SCCR Pulse 250V/60Hz DC Resistance
Common mode Common mode Differential mode
(A) (kA)
(1)
Protection (mA) (mΩ) at 25dB at 10dB at 25dB
RSEN-2003 3 14 N 1.0 250 0.1 to 20 - 0.2 to 30
RSEN-2006 6 14 N 1.0 110 0.1 to 10 - 0.2 to 30
RSEN-2010 10 14 N 1.0 40 0.2 to 20 - 0.2 to 30
RSEN-2016 16 14 N 1.0 20 0.3 to 20 - 0.3 to 30
RSEN-2020 20 14 N 1.0 10 0.4 to 20 - 0.3 to 30
RSEN-2030 30 14 N 1.0 6 2 to 30 - 0.4 to 30
RSEN-2040 40 35 N 1.0 6 2 to 10 - 0.2 to 30
RSEN-2050 50 35 N 1.0 4 2 to 10 - 0.2 to 30
RSEN-2060 60 35 N 1.0 3 2 to 10 - 0.2 to 30
RSEN-2080 80 - N 1.0 3.4 2 to 10 - 0.1 to 30
RSEN-2100 100 - N 1.0 2.7 2 to 10 - 0.1 to 30
RSEN-2150 150 - N 1.0 2 2 to 10 - 0.1 to 30
RSEN-2200 200 - N 1.0 1.4 - 0.4 to 30 0.1 to 30
RSEN-2250 250 - N 1.0 1 - 1 to 20 0.1 to 30
RSEN-2300 300 - N 1.0 0.7 - 2 to 20 0.1 to 30
Rated HV Leakage Current Maximum Attenuation frequency range (MHz)
Model Current SCCR Pulse 250V/60Hz DC Resistance
Common mode Common mode Differential mode
(A) (kA)
(1)
Protection (mA) (mΩ) at 25dB at 10dB at 25dB
RSEN-2003L 3 14 N 0.01 250 0.1 to 3 - 0.2 to 30
RSEN-2006L 6 14 N 0.01 110 0.1 to 3 - 0.2 to 30
RSEN-2010L 10 14 N 0.01 40 - 0.1 to 10 0.2 to 30
RSEN-2016L 16 14 N 0.01 20 - 0.1 to 10 0.2 to 30
RSEN-2020L 20 14 N 0.01 10 - 0.2 to 10 0.3 to 30
RSEN-2030L 30 14 N 0.01 6 - 0.3 to 5 0.3 to 30

RSEN Series
2
Notes
(1) With inverse time circuit breaker. See UL 508 report on website
See website for detailed specications, test methods and installation manual
RSEN technical les
* Separate mounting bracket
Click here for TDK-Lambda three phase lters,
Specication
Model
Input
Rated Voltage Vac/Vdc 250 (Safety certied for AC input only)
Input Frequency Hz 47 - 63
Leakage Current - See model selector
Safety Certications and Markings - UL1283, CSA C22.2 No.8 (cUL), EN60939-1, -2), conforms to RoHS Directive
Environmental
Operating Temperature °C -25 to +85, derating above 50-55. See derating curves below
Storage Temperature °C -25 to +85
Humidity (non condensing) %RH Operating and storage 15 - 85
Cooling - Convection
Withstand Voltage Vac 2,500 input to earth
Isolation Resistance (For 1 minute) MΩ >100 at 500Vdc
Vibration - 10-55Hz Amplitude 1.5mm, Sweep for 1 min. X, Y and Z directions for 2 hours each
Other
Weight (Typ) g RSEN2003: 170, RSEN2006-2030: 230, RSEN2040-2060: 870, RSEN2080: 360
RSEN2100: 380, RSEN2150: 580, RSEN2200: 840, RSEN2250: 810, RSEN2300: 780
Size (LxWxH) mm See outline drawings
Size (LxWxH) Inches -
Connectors See outline drawings
MIL-HDBK-217F NOTICE2 Hours RSEN2003: 6,914,673, RSEN2300: 5,235,054
Warranty Years 5
Related Products
Type Current Series Low Faston on Wire DIN Rail Fused Discharge Metal
Rating (A) Leakage Terminals Leads Mount Resistor Case
Board mount line lter, HV Pulse 0.5 - 6 RSAG
Board mount line lter 0.5 - 6 RSEG
General purpose with faston terminals 6 RSEC
General purpose 0.5 - 6 RSEL Y Y Y Y
HV pulse protection 0.5 - 6 RSAL Y Y Y
Power Entry Module with line lter 3, 6, 10 RPE Y Y Y
Power Entry Module with line lter, HV Pulse 3, 6, 10 RPA Y Y
Compact size with screw terminals 6 - 30 RSEV DIN-RSEV*
Multipurpose 3 - 300 RSEN Y (Up to 30A) Y (Up to 30A)
Multipurpose with HV pulse protection 3 - 60 RSAN Y (Up to 30A) Y (Up to 30A)
High attenuation 3 - 300 RSHN Y (Up to 30A) Y (Up to 30A)
High attenuation with pulse protection 3 - 300 RSMN Y (Up to 30A) Y (Up to 30A)
Wide band, high attenuation 6 - 30 RSKN
RSEN - 2 003 L D
Rated Voltage
2 = 250Vac
Series Name DIN Rail MountLow Leakage Current
Rated Current
003 = 3A
300 = 300A

RSEN Series
3
Mechanical Specication
Derating Curve RSEN-2003 to 2060 Derating Curve RSEN-2080 to 2300
Schematic standard leakage current Schematic low leakage current (L option)
RSEN2003-2060 Outline Drawing