Manual-Tstep-087-Modbus.pdf - 第4页

Values are clamped, not refused. A parameter outside its range is silently brought into range at execute time. Read the register back if you need to know what was accepted. Acceleration is honoured exactly for any value …

100%1 / 8
complete frame = 01 03 00 00 00 04 44 09
The standard CRC-16/MODBUS check value for the ASCII string "123456789" is 0x4B37 - useful for confirming a
from-scratch implementation independently of anything specific to this product.
If your framing and CRC are correct, every request frame printed in the worked examples in this manual will
reproduce byte for byte. That is the fastest way to confirm an implementation before it goes anywhere near a real
device: compute the frame, compare it to the one printed here, and only then put it on the wire.
4. Function codes
Code Name Limit
0x03 Read Holding Registers 8 registers per request
0x04 Read Input Registers identical behaviour to 0x03
0x06 Write Single Register -
0x10 Write Multiple Registers 4 registers per request
Any other function code returns exception 01.
32-bit values
Most values on this drive are 32-bit - steps, speeds and positions. Each occupies two consecutive registers, starting
on an even address, high word first:
value = (register[n] << 16) | register[n+1]
That order is fixed and not configurable. Position is signed (two's complement across the pair); everything else is
unsigned.
The 4-register write limit means one transaction carries two 32-bit values.
5. Register map
Identity - read only
Register Name Value
0x0000 Product ID 0x0087
0x0001 Firmware version 0x0200 = version 2.00
0x0002 Unit address 1-16, as set by the switches
0x0003 Capabilities 0x0007 - bit 0 motion, bit 1 potentiometer, bit 2 IN1/IN2
Motion parameters - read/write
Registers Name Units Min Max
0x0200-0x0201 Acceleration steps/s² 1 1000000
0x0202-0x0203 Start speed steps/s 1 100000
0x0204-0x0205 Cruise speed steps/s 1 100000
0x0206-0x0207 Move distance steps 0 2147483647
0x0208-0x0209 Dwell ms - not implemented
0x020A Command - writing this executes
0x020B Command sequence - see section 8
Parameters are staged, not applied. Writing one changes nothing about the motor - they take effect when a command
is written. This is what makes a 32-bit value safe to write as two registers: a half-updated distance sits harmlessly in the
staging area until a command acts on it.
Values are clamped, not refused. A parameter outside its range is silently brought into range at execute time. Read the
register back if you need to know what was accepted.
Acceleration is honoured exactly for any value in range. The start speed is the speed a ramp begins and ends at -
deceleration returns to it rather than to zero.
The dwell registers do nothing. 0x0208-0x0209 accept a value, clamp it and read back correctly, but nothing acts on
it, and state word bit 0x0004 ("waiting on a dwell") can never be set. A master needing a pause between moves must
time it itself.
Live status - read only
Registers Name Units
0x0300-0x0301 Current speed steps/s
0x0302-0x0303 Position steps, signed
0x0304 State word bitmask, below
0x0305 Inputs bit 0 = IN1, bit 1 = IN2
Six contiguous registers in polling order - one 0x03 request with quantity 6 returns the drive's entire live state.
Position counts every step, in every mode - finite moves, continuous runs and seeks alike.
State word - 0x0304
Bit Meaning
0x0001 Moving
0x0002 Direction is clockwise
0x0004 Waiting on a dwell - never set, see above
0x0008 Potentiometer speed control enabled
0x0010 Driver fault - see section 7
Unmapped registers
0x0004-0x01FF, 0x020C-0x02FF and 0x0306 upward are holes and return exception 02.
6. Commands - write to 0x020A
Value Command Uses
0
Stop - ramps down,
never a hard stop
1 Move clockwise distance, speeds, acceleration
2 Move anticlockwise distance, speeds, acceleration
3
Run clockwise until
stopped
speeds, acceleration
4
Run anticlockwise until
stopped
speeds, acceleration
5 Seek input 1 speeds, acceleration
6 Seek input 2 speeds, acceleration
7
Reset position counter to
zero
8
Save parameters to
flash
refused while moving - see below
13 / 14
Potentiometer enable /
disable
17 / 18 Driver enable / disable
19
Clear a latched driver
fault
refused while the fault is live
Value Command Uses
20
Apply the staged cruise
speed
retargets a move already running
An unrecognised command returns exception 03 rather than being ignored.
Waiting for a move to finish
Poll 0x0300 quantity 6 and watch bit 0 of the state word. Polling every 50-100 ms is ample.
Command 8 - save parameters to flash
Stores acceleration, start speed, cruise speed and move distance to the drive's parameter page. They are reloaded at
every power-up.
Refused with exception 03 while the motor is moving. Erasing a flash page stalls the CPU for tens of milliseconds -
this save measured 42 ms against a normal 5 ms reply - and the step generator runs from that same flash. A save during
a move would starve the step interrupt and silently drop every step it should have emitted: roughly 40 at 1000 steps/s,
thousands at full speed, leaving the position counter wrong with nothing to indicate it. Stop first.
Budget 50 ms for the reply, not the usual 5 ms. A master with a tight timeout will call this a failure and may retry a save
that already succeeded.
The dwell registers are not persisted, and neither is anything else outside the four values above.
Changing speed while moving
Stage a new cruise speed in 0x0204-0x0205, then write command 20. The drive ramps to the new speed at the
configured acceleration - it is never asked for a jump it cannot follow.
Command 20 is refused while the potentiometer is enabled, because the potentiometer would overwrite the new
target within a fraction of a second.
Changing direction while moving
Sending command 3 or 4 while a continuous run is already going is a reversal: the drive winds down to its start speed,
changes direction at zero speed, and takes the motion back up. You do not have to sequence a stop yourself. Position
tracks correctly throughout.
A reversal during a finite move is refused (exception 03). Stop the move, then command the new direction.
Potentiometer
Command 13 enables it, 14 disables it. While enabled the potentiometer scales the cruise speed register, so it can
never ask for more than the axis is configured for, and it owns the speed target - use command 20 only with the
potentiometer disabled.
[!] Turning the knob to its minimum does not stop the motor. It commands 1 step/s, the motor keeps turning, and the
moving bit stays set. Only command 0 stops a move. If a machine needs the knob to mean stop, the master must
detect the speed floor and issue the stop itself.
[!] Seeks have no distance limit and no timeout
Commands 5 and 6 run until their input asserts. Nothing else stops them. If the input is not wired, not powered, or the
axis is already past it, the motor runs indefinitely.
A master issuing a seek must impose its own limit - a timeout, a travel budget, or both - and send command 0 when it
expires. Confirm that register 0x0305 actually changes before relying on a seek at all.
7. Safety and fault handling
These are properties of the drive that a master must design around.
The bus is the only source of commands. The drive is always online; nothing else can take the
motor away from a master mid-operation.
The drive answers while it is moving. Position reads and a stop work mid-move - this is what
makes a bus stop usable at all.
A stop over the bus is not a safety function. It travels over a wire, through a UART, into a
polled loop. The hardwired emergency-stop chain remains what makes a machine safe.