UPS 8 – 15 kV A, 230V 50/60 Hz output User ’ s Guide 1 022403 Revision D 44 Figure 46. T ie Cabinet’ s wiring diagram with two UPSs and bypass connected. UPS Module Bypass input X1 Rectifier input F2 Cable A Cable C Fuse …

100%1 / 54
UPS 8 – 15 kVA, 230V 50/60 Hz output
Users Guide
1022403
Revision D
43
Figure 44 Cable routing of Tie Cabinet
Figure 45. Tie Cabinet’s wiring diagram with three UPSs.
UPS 8 – 15 kVA, 230V 50/60 Hz output
Users Guide
1022403
Revision D
44
Figure 46. Tie Cabinet’s wiring diagram with two UPSs and bypass connected.
UPS Module
Bypass input X1 Rectifier input F2
Cable A Cable C Fuse 1 Cable B Fuse 2
8 kVA 10 mm
2
10 mm
2
50 A 2,5 mm
2
16 A
10 kVA 10 mm
2
10 mm
2
50 A 4 mm
2
20 A
12 kVA 16 mm
2
16 mm
2
63 A 6 mm
2
25 A
15 kVA 25 mm
2
16 mm
2
80 A 6 mm
2
32 A
TC Module Cable B Cable D Cable E
8 kVA 10 mm
2
10 mm
2
10 mm
2
10 kVA 10 mm
2
10 mm
2
10 mm
2
12 kVA 16 mm
2
16 mm
2
16 mm
2
15 kVA 25 mm
2
16 mm
2
25 mm
2
16 kVA 35 mm
2
16 mm
2
(35 mm
2
)*
20 kVA 35 mm
2
16 mm
2
(35 mm
2
)*
24 kVA 70 mm
2
35 mm
2
(70 mm
2
)*
30 kVA 70 mm
2
35 mm
2
(70 mm
2
)*
36 kVA 95 mm
2
50 mm
2
-
45 kVA 120 mm
2
70 mm
2
-
Table 47. Minimum cable and fuse rating for the different parallel system with installation procedure C
* (system bypass not allowed)
Note!
Protection fuses need to be used for load cabling if manufacturers Tie Cabinet (or
similar) not used.
UPS 8 – 15 kVA, 230V 50/60 Hz output
Users Guide
1022403
Revision D
45
Required parallel system wiring length should be in accordance with the following rule, as
referenced to the diagram below to ensure approximately equal current sharing when in static
bypass mode (see Figure below:
Total length of 1A + 1B = Total length of 2A + 2B
= Total length of 3A + 3B
= Total length of 4A + 4B
This rule has a tolerance of approximately ± 10% for the combined input and output wire
lengths. If installing only two UPS modules, this requirement is no longer required as each
UPS is capable of supporting the full bypass requirement. However, this would preclude future
expansion.
Figure 48. Bypass wiring diagram and cable length notes.
Note!
Signal input cables need to be connected to all UPS when used.