Multifunction_RIO_Specs.pdf - 第8页

Multifunction Reconfigurable I/O Specifi cations 8 ni.com Storage Enviro nment PCI/PXI-781 x /783 x .. ....................... –20 °C to 70 °C, tested in accordance with IEC-60068- 2-1 and IEC-60068-2- 2. PCIe-784 x /785…

100%1 / 11
© National Instruments Corporation 7 Multifunction Reconfigurable I/O Specifications
To calculate the total current sourced by the digital outputs,
use the following equation:
Power available at I/O connectors
.. 4.50 to 5.25 VDC at 1 A
total, 250 mA per I/O
connector pin
Physical
Dimensions (not including connectors)
PCI-781x/783x............................ 17 cm by 11 cm
(6.7 in. by 4.3 in.)
PCIe-784x/785x .......................... 17 cm by 11 cm
(6.7 in. by 4.3 in.)
PXI-78xx..................................... 16 cm by 10 cm
(6.3 in. by 3.9 in.)
Weight
PCI-781x/783x............................ 112 g
PCIe-784x/785x .......................... 127 g
PXI-78xx..................................... 152 g
I/O connectors
NI 781x ....................................... Four 68-pin female
high-density VHDCI type
NI 7830....................................... Two 68-pin female
high-density VHDCI type
NI 783x/784x/785x ..................... Three 68-pin female
high-density VHDCI type
Disk drive power connector
(PCIe devices)................................. Standard ATX peripheral
connector (not serial
ATA)
Maximum Working Voltage
(NI 783x /784x /785x Only)
Maximum working voltage refers to the signal voltage plus the
common-mode voltage.
Channel-to-earth ............................. ±12 V, Measurement
Category I
Channel-to-channel......................... ±24 V, Measurement
Category I
Caution Do not use the NI 783x/784x/785x for
connection to signals in Measurement Categories II,
III, or IV.
Environmental
The NI 78xx is intended for indoor use only.
Operating Environment
NI 781x ............................................0 °C to 55 °C,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
NI 7830, NI 7831
40 MHz or 80 MHz timebase .....0 °C to 55 °C,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
PCI/PXI-7833
40 MHz timebase ........................0 °C to 55 °C,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
80 MHz timebase ........................0 °C to 55 °C except the
following: 0 °C to 45 °C
when installed in an
PXI-1000/B or
PXI-101X,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
PXI-7841/7842/7851/7852/7853/7854
40 MHz timebase ........................0 °C to 55 °C,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
80 MHz timebase ........................0 °C to 55 °C except the
following: 0 °C to 45 °C
when installed in an
PXI-1000/B or
PXI-101X,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
PCIe-7841/7842/7851/7852
40 MHz or 80 MHz timebase .....0 °C to 40 °C,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
Relative humidity range ..................10% to 90%,
noncondensing,
tested in accordance with
IEC-60068-2-56.
Altitude............................................2,000 m at 25 °C ambient
temperature
current sourced on channel i
i 1=
j
Multifunction Reconfigurable I/O Specifications 8 ni.com
Storage Environment
PCI/PXI-781x/783x .........................–20 °C to 70 °C,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
PCIe-784x/785x ...............................–20 °C to 70 °C,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
PXI-784x/785x.................................–40 °C to 70 °C,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
Ambient temperature range.............–20 °C to 70 °C,
tested in accordance with
IEC-60068-2-1 and
IEC-60068-2-2.
Relative humidity range ..................5% to 95%,
noncondensing,
tested in accordance with
IEC-60068-2-56.
Note Clean the device with a soft, non-metallic
brush. Make sure that the device is completely dry
and free from contaminants before returning it to
service.
Shock and Vibration (for PXI-78xx Only)
Operational shock............................30 g peak, half-sine,
11 ms pulse;
tested in accordance with
IEC-60068-2-27. Test
profile developed in
accordance with
MIL-PRF-28800F.
Random vibration
Operating ....................................5 Hz to 500 Hz, 0.3 g
rms
Nonoperating ..............................5 Hz to 500 Hz, 2.4 g
rms
,
tested in accordance with
IEC-60068-2-64.
Nonoperating test profile
exceeds the requirements
of MIL-PRF-28800F,
Class 3.
Safety
The NI 78xx is designed to meet the requirements of the
following standards of safety for electrical equipment for
measurement, control, and laboratory use:
IEC 61010-1, EN 61010-1
UL 61010-1, CSA 61010-1
Note For UL and other safety certifications,
refer to the product label or the Online Product
Certification section.
Electromagnetic Compatibility
The NI 78xx is designed to meet the requirements of the
following standards of EMC for electrical equipment for
measurement, control, and laboratory use:
EN 61326 (IEC 61326): Class A emissions;
Basic immunity
EN 55011 (CISPR 11): Group 1, Class A emissions
AS/NZS CISPR 11: Group 1, Class A emissions
FCC 47 CFR Part 15B: Class A emissions
ICES-001: Class A emissions
Note For the standards applied to assess the EMC
of this product, refer to the Online Product
Certification section.
Note For EMC compliance, operate this device
with shielded cabling.
CE Compliance
This product meets the essential requirements of applicable
European Directives as follows:
2006/95/EC; Low-Voltage Directive (safety)
2004/108/EC; Electromagnetic Compatibility Directive
(EMC)
© National Instruments Corporation 9 Multifunction Reconfigurable I/O Specifications
Online Product Certification
Refer to the product Declaration of Conformity (DoC) for
additional regulatory compliance information. To obtain
product certifications and the DoC for this product, visit
ni.com/certification, search by model number or
product line, and click the appropriate link in the Certification
column.
Environmental Management
NI is committed to designing and manufacturing products in
an environmentally responsible manner. NI recognizes that
eliminating certain hazardous substances from our products is
beneficial to the environment and to NI customers.
For additional environmental information, refer to the NI and
the Environment Web page at
ni.com/environment. This
page contains the environmental regulations and directives
with which NI complies, as well as other environmental
information not included in this document.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers At the end of their life cycle, all
products must be sent to a WEEE recycling center.
For more information about WEEE recycling
centers and National Instruments WEEE initiatives,
visit
ni.com/environment/weee.htm.
⬉ᄤֵᙃѻક∵ᶧ᥻ࠊㅵ⧚ࡲ⊩ ˄Ё೑
RoHS
˅