Power supply Conversion Instructions S-20/S-23 HM/F4/F5 6 4 or 5-c onductor connection for the mains supply 09/99 edition 30 6 4 o r 5-co nducto r connection f or the mains suppl y The connec tions c onsist of either 4 o…

Conversion Instructions S-20/S-23 HM/F4/F5 Power supply
09/99 edition
29
Fig. 5 - 3 Front panel of the power supply unit - connecting the inrush current limiter (003429988-01)
(1) - (9) Numbers of the connecting wires
(A1) Inrush current limiter 5
12 22
14 24 34
32
230
230
150
120
N
+5%
P
E
-5%
24
8
0
8
24
A1
1 L1 3 L2 5 L3 21 NC
SIEMENS
01
2 T1 4 T2 6 T3 22 NC
V1
V4
V5
V3
11 21 31
13 23 33
A1
12 22 32
14 24 34
11
21
31
13 23 33
1
7
4
2 8
5
3
9
6
A1
12 22 32
14 24 34
11
21
31
13 23 33
1
7
4
2
5
8
63 9
T2
Three-phase
transformer
T1
Single-phase
transformer
3x208VAC
3x400VAC

Power supply Conversion Instructions S-20/S-23 HM/F4/F5
6 4 or 5-conductor connection for the mains supply 09/99 edition
30
6 4 or 5-conductor connection for the mains supply
The connections consist of either 4 or 5-conductor cables, as specified by the electricity company.6
4-conductor connection 6
For the 4-conductor connection, the neutral (N) and protective earth (PE) conductors are com-
bined in a common wire PEN. 6
Å Insert the yellow-green wires BR3 and BR4 between the N and PE terminals in the right-hand
terminal panel of terminal strip X206 (see Fig. 6 - 1).
5-conductor connection 6
For the 5-conductor connection, the neutral (N) and protective earth (PE) conductors run in sep-
arate wires. 6
Å Remove the yellow-green wires BR3 and BR4 between the N and PE terminals in the right-
hand terminal panel of terminal strip X206 (see Fig. 6 - 1).
Placement
system
Terminal panel
Terminal strip X206
Jumpers BR3 and BR4 set between PE and N
4-conductor connection 5-conductor connection
S-20 00321510-xx yes no
S-23 HM 00337342-xx yes no
F4/F5 00321512-xx yes no

Conversion Instructions S-20/S-23 HM/F4/F5 Power supply
09/99 edition
31
Fig. 6 - 1 Terminal panel, right-hand side, terminal strip X206
XX
D
A5
A4A3
PE
X
X
X1rd
X2rdX2rc
L2
L3
X206
6
A2
X
X1rcX1rb
X2re
X
N
N
N
N
N
L2
X206
L1
L1
L1
L2
L2
XX
N
5
4
PE
PE
PE
PE
L3
L3
L3
X2rb
l=120mm
L1
PE
PE
PE
PE
PE
Cable duct 65x46 l=155mm
Cable duct 65x30
Cable duct 65x46 l=430mm
BR4 (yegn)
BR3 (yegn)