Pyramax 10 zone STD
Pyramax 125/150 STD HEATER
S
PURCHASER TO SUPPLY CIRCUIT BREAKER OR FUSED DISCONNECT SWITCH FOR:
240 Volts 250 Amperes 3 Phase 3 Wires
95 Kilovolt-amperes 50/60HZ
Furnaces case must be grounded per local codes
Line Total htr Avg htr Typical
Voltages L1 L2 L3 Neutral Total KVA Power load [30%] oper. pwr.
200 173 173 184 n/a 64 56 17 24 not std offering
208 180 180 192 n/a 70 61 18 26
220 191 191 203 n/a 78 68 20 28
230 199 199 212 n/a 85 74 22 30
240 208 208 221 n/a 93 81 24 32
Typical Operating Power 32 KVA Typical Oper Pwr = Avg. Htr. Load + 0.8 x (6KVA+1.5KVA+2KVA)
Average heater load 24 KW Average heater load = 30% of Total Htr Load
Overtemp T/C's in zones
Pyramax 125/150 STD HEATER
S
PURCHASER TO SUPPLY CIRCUIT BREAKER OR FUSED DISCONNECT SWITCH FOR:
480 Volts 125 Amperes 3 Phase 3 Wires
95 Kilovolt-amperes 50/60HZ
Furnaces case must be grounded per local codes
Line Total htr Avg htr Typical
Voltages L1 L2 L3 Neutral Total KVA Power load [30%] oper. pwr.
440 95 95 101 n/a 78 68 20 28
460 100 100 106 n/a 85 74 22 30
480 104 104 111 n/a 93 81 24 32
Typical Operating Power 32 KVA Typical Oper Pwr = Avg. Htr. Load + 0.8 x (6KVA+1.5KVA+2KVA)
Average heater load 24 KW Average heater load = 30% of Total Htr Load
Overtemp T/C's in zones
Pyramax 125/150 STD HEATER
S
PURCHASER TO SUPPLY CIRCUIT BREAKER OR FUSED DISCONNECT SWITCH FOR:
415/240 Volts 160 Amperes 3 Phase 4 Wires
95 Kilovolt-amperes 50/60HZ
Furnaces case must be grounded per local codes
Line Total htr Avg htr Typical
Voltages L1 L2 L3 Neutral Total KVA Power load [30%] oper. pwr.
380/220 103 117 117 117 78 68 20 28
400/230 108 122 122 122 85 74 22 30
415/240 112 128 128 128 93 81 24 32
Typical Operating Power 32 KVA
Typical Oper Pwr = Avg. Htr. Load + 0.8 x (6KVA+1.5KVA+2KVA)
Average heater load 24 KW Average heater load = 30% of Total Htr Load
Overtemp T/C's in zones
LINE CURRENT- [AMPERES]
MAXIMUM LOAD DATA
LINE CURRENT- [AMPERES]
MAXIMUM LOAD DATA
LINE CURRENT- [AMPERES]
MAXIMUM LOAD DATA
52089671.xls
Prepared by Rich Tarczon
2/13/06
1 of 1