Technical data P1 and P3 Switch- dis connectors P1-25 P1-32 P1-40 P3-63 P3-80 P3-100 General Standards IE C/ EN 6 09 47, VDE 0 6 60, I EC /E N 60 20 4, CS A , UL , s wit ch -d isc onn ec tor t o IEC / EN 6 09 47-3 IE C/ …

Characteristic curves
Component lifespan based on breaking current and utilisation category AC-3 and AC-21 at 400 V a.c., AC-15 at 230 V.
To ensure a reasonable service life in utilisation category AC-4 (extreme load: 100% inching, reversing or plug braking) the motor’s
standstill current must not exceed the rated operational current of the switch AC-21A.
T0 - Characteristic curve
1 2 3 4 5 6 7 8 10 20 A
T0
0.5
1
2
3
4
5
6
8
10
Breaking current
As control switch
(AC-15)
As motor load switch
(AC-3)
As load-break switch
(AC-21)
Component lifespan (operations 10
5
)
T3 - Characteristic curve
Breaking current
As motor load switch
(AC-3)
As load-break switch
(AC-21)
T3
Component lifespan (operations 10
5
)
1
2 3 4 6 128 30 40 A
0.5
1
2
3
4
5
6
8
10
16 20 25
0.6
0.8
T5, T5B - Characteristic curve
0.5
T5B
T5B
T5
T5
1
2 3 4 6 128 30 40
1
2
3
4
5
6
8
10
16 20
0.6
0.8
60 80 100 A
T5B
T5
T5B
T5
T5B, T5
Breaking current
As motor load switch
(AC-3)
As load-break switch
(AC-21)
Component lifespan (operations 10
5
)
T6, T8 - Characteristic curve
Breaking current
As motor load switch
(AC-3)
As load-break switch
(AC-21)
T6, T8
Component lifespan (operations 10
5
)
4 6 8 1612
0.1
0.2
0.3
0.5
1
2
3
5
6020 30 40 100 250A
T6 T8
T6 T8
T6
T8
T6
T8
P1 - Characteristic curve
Breaking current
As motor load switch
(AC-3)
As load-break switch
(AC-21)
P1
Component lifespan (operations 10
5
)
1
2 3 4 6 128 30 40 A
0.5
1
2
3
4
5
6
8
10
16 20 25
0.6
0.8
P1-32
P1-25
P1-25 P1-32
P1-25
P3 - Characteristic curve
Breaking current
As motor load switch
(AC-3)
As load-break switch
(AC-21)
P3
Component lifespan (operations 10
5
)
1
2
3 5 2010 80 100 A
0.1
40 60
0.2
0.3
0.4
0.5
0.6
0.8
1
2
P3-100
P3-63
P3-63 P3-100
P3-100
P3-63
182
EATON P Switch-disconnectors and T Rotary cam switches CA042001EN

Technical data
P1 and P3 Switch-disconnectors
P1-25 P1-32 P1-40 P3-63 P3-80 P3-100
General
Standards IEC/EN 60947, VDE 0660, IEC/EN 60204,
CSA, UL, switch-disconnector to IEC/
EN 60947-3
IEC/EN 60947,
IEC/EN 60204
IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL, switch-
disconnector to IEC/EN 60947-3
Lifespan mechanical Operations x 10
6
0.3 0.3 0.3 0.1 0.1 0.1
Maximum operating frequency Operations/h 50 50 50 50 50 50
Climatic proofing Damp heat: constant to IEC 60068-2-78 / cyclical to IEC 60068-2-30
Ambient temperature (for derating details please contact
buletechnical@eaton.com)
Open
o
C -25 - 50 -25 - 50 -25 - 50 -25 - 50 -25 - 50 -25 - 50
Enclosed
o
C -25 - 40 -25 -40 -25 - 40 -25 - 40 -25 - 40 -25 - 40
Mounting position Any Any Any Any Any Any
Mechanical shock resistance
(IEC/EN 600068-2-27)
Half-sinusoidal shock 20 ms g 15 15 15 15 15 15
Contacts
Rated operational voltage U
e
V A C 690 690 690 690 690 690
Rated impulse withstand voltage U
imp
V A C 6000 6000 6000 6000 6000 6000
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3
Rated uninterrupted current I
u
A 25 32 40 63 80 100
Load rating with intermittent operation, class 12 AB 60% DF x I
e
1.3 1.3 1.3 1.3 1.3 1.3
AB 40% DF x I
e
1.6 1.6 1.6 1.6 1.6 1.6
AB 25% DF x I
e
2 2 2 2 2 2
Short-circuit rating Fuse A gG/gL 25 50 50 80 100 100
Rated conditional short-circuit current Load side I
q
kA 50 80 80 4 4 4
Supply side I
q
kA - - - 100 80 80
Rated short-time withstand current (1s current) I
cw
A
rms
640 640 640 1260 1260 1260
Isolating characteristics to IEC/EN 60947 V AC ≤ 690 ≤ 690 ≤ 690 ≤ 690 ≤ 690 ≤ 690
Safe isolation according to EN 61140
Safe isolation to VDE 0106 Part 101 and Part 101 A1 between
the auxiliary contacts and main circuits
VAC 440 440 440 440 440 440
Switching angle
o
90 90 90 90 90 90
Contacts Number Max. 3 (+N) Max. 3 (+N) Max. 3 (+N) Max. 3 (+N) Max. 3 (+N) Max. 3 (+N)
Current heat loss per contact at I
e
W 1.1 1.8 1.9 4.5 6 7.5
Terminal capacity
Solid or stranded mm
2
1 x (1.5-6)
2 x (1.5-6)
1 x (1.5-6)
2 x (1.5-6)
1 x (1.5-10)
2 x (1.5-10)
1 x (2.5-35)
2 x (2.5-10)
1 x (2.5-35)
2 x (2.5-10)
1 x (2.5-35)
2 x (2.5-10)
Flexible with ferrule to DIN 46228 mm
2
1 x (1-4)
2 x (1-4)
1 x (1-4)
2 x (1-4)
1 x (1-4)
2 x (1-4)
1 x (1.5-25)
2 x (1.5-6)
1 x (1.5-25)
2 x (1.5-6)
1 x (1.5-25)
2 x (1.5-6)
Fork terminal - - 1 x (1.5-10)
2 x (1.5-10)
- - -
Terminal screw M4 M4 M4 M5 M5 M5
Tightening torque Nm 1.6 1.6 1.6 3 3 3
Switching capacity
AC Voltage
Rated making capacity cos φ = 0.35 *P1-40 φ = 0.45
A 240 320 360* 800 875 950
Rated breaking capacity, motor load switch cos φ = 0.35
*P1-40 φ = 0.45
230 V A 190 260 X 640 700 760
400/415 V A 150 300 290* 600 675 740
500 V A 170 290 X 590 750 880
690 V A 150 250 130* 340 440 520
Rated operational current 440V, load-break switch AC-21A I
e
A 25 32 40 63 80 100
AC-3 motor load switch motor load 230 V P kW 5.5 7.5 7.5 15 18.5 22
400/415 V P kW 7.5 13 15 30 33.5 37
500 V P kW 7.5 18.5 X 30 38 45
690 V P kW 7.5 15 15 30 33.5 37
Notes: Main switch characteristics to IEC/EN 60204; positive opening of contacts, operator element positively located on shaft. Rated uninterrupted current Iu is specified for max cross-section. For terminal capacity solid, stranded
and flexible: Max. 2 cross-section sizes difference admissible when using 2 conductors.
183EATON P Switch-disconnectors and T Rotary cam switches CA042001EN

Technical data
P1 and P3 Switch-disconnectors
P1-25 P1-32 P1-40 P3-63 P3-80 P3-100
Switching capacity
AC-23A motor load switch motor load 230 V P kW 7 8.5 11 18.5 30 30
400/415 V P kW 13 15 22 30 50 50
500 V P kW 11 18.5 X 37 65 65
690 V P kW 11 18.5 18.5 30 45 45
DC Voltage
DC-1, load switch L/R = 1 ms Rated operational current I
e
A 25 32 X 63 80 100
Voltage per contact connected in series V 60 60 X 60 60 60
DC-23A, motor load switch
L/R = 15 ms
24 V Rated operational current I
e
A 25 25 X 50 50 50
Contacts Number 1 1 X 1 1 1
48 V Rated operational current I
e
A 25 25 X 50 50 50
Contacts Number 2 2 X 2 2 2
60 V Rated operational current I
e
A 25 25 X 50 50 50
Contacts Number 3 3 X 3 3 3
120 V Rated operational current I
e
A 12 12 X 25 25 25
Contacts Number 3 3 X 3 3 3
Rating data for approved types
UL File No E36332 (Devices for world markets IEC, UL/CSA)
Contacts
Rated operational voltage U
e
V a.c. 600 600 600 600 600 600
Rated operational current I
u
Rated current A 20 30 40 60 80 100
Pilot duty A 600 P 600 A 600 P 600 A 600 P 600 - - -
Switching capacity
AC-3: max, rated power, 40-60 Hz AC motors
3-phase 200 V a.c. HP 5 7½
X
15 15 20
230 V a.c. HP 5 10 X 15 20 25
460 V a.c. HP 10 20
X
40 50 60
575 V a.c. HP 15 25 X 50 60 75
Single-phase 200 V a.c. HP 1½ 2
X
3 5 5
230 V a.c. HP 3 3 X 7½ 10 10
460 V a.c. HP 3 5
X
10 15 15
Short-circuit rating
Standard 600 V a.c. kA 5 5 5 10 10 10
With back-up fuse A 110 110 110 150 150 150
With circuit-breakers Part no. NZMH6 NZMH6 NZMH6 NZMH6 NZMH6 NZMH6
Current setting A 125 125 125 125 125 125
Disconnect in motor circuits 600 V a.c. kA 10 10 10 10 10 -
With back-up fuse Class 50 A/J 50 A/J 50 A/J 100 A 100 A 100 A
Terminal capacity
Terminal capacity
Cu cable Min./ AWG 14 14 14 14 14 14
Max AWG 8 8 8 2 2 2
Tightening torque Max in-lb 14.1 14.1 14.1 26.5 26.5 26.5
H1 11
Auxiliary contacts (1 N/O + 1 N/C)
Pilot duty P 600
Heavy pilot duty A 600
General use 10 A - 600 V AC
184