161页面.pdf - 第193页

T ec hnic al data T6-3-8212/E/HI12 T6-160-... T8-... Switching capacity AC Voltage Rated makin g capacit y cos φ = 0.35 A 16 0 0 160 0 2390 Ra ted b rea ki ng c apa ci ty, m oto r lo ad s wi tch cos φ = 0.35 23 0 V A 12 …

100%1 / 236
Technical data
T6 and T8 Cam switch-disconnectors
T6-3-8212/E/HI12 T6-160-... T8-...
General
Standards IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL
switch-disconnector to IEC/EN 60947-3
Load break switch according to IEC/EN60947-3
Lifespan mechanical Operations x 10
6
0.1 0.1 0.1
Maximum operating frequency Operations/h 50 50 50
Climatic proofing Damp heat. constant to IEC 60068-2-78;
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature
(for derating information contact buletechnical@eaton.com)
Open
o
C -25 -50 -25 -50 -25 -50
Enclosed
o
C -25 -40 -25 -40 -25 -40
Mounting position Any Any Any
Mechanical shock resistance to IEC 60068-2-27 Half-sinusoidal shock
to 20 ms
g >15 >15 >15
Contacts
Rated operational voltage U
e
V A C 690 690 690
Rated impulse withstand voltage U
imp
V A C 6000 6000 6000
Overvoltage category/pollution degree III/3 III/3 III/3
Rated uninterrupted current Open I
u
A 200 160 315
Load rating with intermittent operation, class 12 AB 60% DF x I
e
2 2 2
AB 40% DF x I
e
1.6 1.6 1.6
AB 25% DF x I
e
1.3 1.3 1.3
Rated conditional short-circuit current Load side I
q
kA 5 30 5
Supply side I
q
kA - - -
Short-circuit rating Fuse A gG/gL 20 35 80
Rated short-time withstand current (1s current) I
cw
A
rms
320 650 1300
Safe isolation according to EN 61140
Between the contacts VAC 440 440 440
Switching angle
o
90
60
90
60
90
60
Contact units Number Max. 3 Max.3 Max.3
Contacts with double-break Max. 6 Max. 6 Max. 6
Current heat loss per contact at I
e
W 11 11 11
Terminal
Solid or stranded mm
2
1 x 70
2 x 25
1 x 95
2 x 25
150
Flexible with ferrule to DIN 46228 mm
2
1 x 50
2 x 16
1 x 50
2 x 16
120
Flat terminals for rails mm
2
1 x (25 x 5)
2 x (20 x-3)
Terminal screw M6 M5, hexagon screw M12
Tightening torque Nm 5.6 14 25
192
EATON P Switch-disconnectors and T Rotary cam switches CA042001EN
Technical data
T6-3-8212/E/HI12 T6-160-... T8-...
Switching capacity
AC Voltage
Rated making capacity cos φ = 0.35 A 1600 1600 2390
Rated breaking capacity, motor load switch
cos φ = 0.35
230 V A 1280 1280 1910
400 V A 900 900 1800
500 V A 880 880 1200
690 V A 340 340 420
Rated operational current, load-break
switch AC-21A
440 V I
e
A 125 160 315
Motor rating
Motor load switch AC-3
230 V P kW 22 22 22
230 V star-delta P kW 22 22 37
400/415 V P kW 37 45 55
400 V star-delta P kW 37 45 55
500 V P kW 37 37 37
500 V star-delta P kW 37 37 37
690 V P kW 22 22 37
690 V star-delta P kW 22 22 37
Motor rating
Motor load switch AC-23A
230 V P kW 37 37 75
400/415 V P kW 45 55 132
500 V P kW 55 75 132
690 V P kW 30 30 37
Motor rating
Motor load switch AC-15
230 V P kW - - -
400/415 V P kW - - -
500 V P kW - - -
DC Voltage
DC-1, load switch L/R = 1 ms Rated operational current I
e
A 125 125 315
Voltage per contact connected in series V 42 42 42
DC-23A, motor load switch
L/R = 15 ms
24 V Rated operational current I
e
A 125 125 250
Voltage per contact connected in series Number 1 1 1
48 V Rated operational current I
e
A 125 125 250
Contacts Number 2 2 2
60 V Rated operational current I
e
A 125 125 125
Contacts Number 3 3 3
120 V Rated operational current I
e
A 50 50 50
Contacts Number 3 3 3
DC-13, control switch L/R = 50 ms Rated operational current I
e
A 125 125 250
Voltage per contact connected in series Number 24 24
Control circuit reliability at 24 V d.c., 10 mA Fault probabilty H
F
< 10-5, < 1 failure for 100,000 switching operations
Auxiliary contact
Standards Control circuit isolator to IEC/EN 60947-5 f
Rated insulation voltage Ui V a.c. 500 500 -
Rated uninterrupted current I
u
A 10 10 -
Rated operational current AC-15 at 230 V 6 -
400 V/415 V 4 -
Short-circuit rating Max fuse A gG/gL 10 -
Terminal capacity Solid mm
2
0.75-2.5 0.75-2.5 -
Flexible with ferrule to DIN 46228 mm
2
0.5-1.5 0.5-1.5 -
Tightening torque Nm 0.35 0.35 -
Control cirucit reliability at 24 V d.c., 10 mA Fault probability HF < 10-5, < 1 failure for 100,000 switching operations
T6 and T8 Cam switch-disconnectors
193EATON P Switch-disconnectors and T Rotary cam switches CA042001EN
Dimensions
Drilling dimensions
1)
30
30
5.5
28
c20 3512
17/19
1.7
17.9
3.2
24.1
+0.4
0
22.3
+0.4
0
16.2
+0.2
0
Part no. c20 c21
TM-1
TM-2
TM-3
TM-4
TM-5
TM-6
TM-7
TM-8
39
51
63
75
87
99
111
123
42
54
66
Depth of one contact unit: 12 mm
Drilling dimensions
1)
F 5.5
28
c20 2312
30
30
17/19
1.7
17.9
3.2
24.1
+0.4
0
22.3
+0.4
0
16.2
+0.2
0
Drilling dimensions
28
c20
3
o 4.8
30
30
28
28
M3
M3
3.2
20
8
TM Flush mounting /E - mm
TM Flush mounting TM.../E/SVB-(SW) - mm
Drilling dimensions
28
c20
3
o 4.8
30
30
28
28
M3
M3
3.2
20
8
Control circuit isolators for 2 padlocks Ø 4 mm or 1 padlock Ø 6 mm
TM Centre mounting /EZ - mm
TM Centre mounting with key operation TM-...+EZ/S - mm
TM-.../IVS/S
c1 c2
35.5
60
45
Part no. c1 c2
TM-1
TM-2
44
46
21
26.5
Depth of one contact unit 12 mm
42
21.5
24
35.5
60
45
TM Service distribution board mounting /IVS - mm
Drilling dimensions optionally: 16.2 mm = without reduction RMQ16; 22.3 mm = with reduction RMQ Titan
194
EATON P Switch-disconnectors and T Rotary cam switches CA042001EN