5 Automatic Conveyor Width Adjustment
5.1 Architecture and Function
l The Automatic Conveyor Width Adjustment function allows the conveyor width to be
adjusted directly through the HCI buttons. During programming the conveyor width
adjustment results can be recorded in the main program, so the next time the program is
launched it will automatically adjust the conveyor width to the previously stored location.
l Motor Driver Dip Switch jumps to point 1 and 2.
5.2 Automatic Conveyor Width Settings
l For configuring the PLC please refer to 1.2-1.3.1.
51
6 Service
6.1 PC/PLC Connecting
l First confirm that the main program has begun testing. If not running, please start the
program and repeat a test of the PLC. If there is still a problem, please launch the main
program and the PLC I/O TEST to test the system manually to see if the I/O is operating
normally (the settings and procedure are as the figures below). If there is still no response,
please carry out Step 2 and Step 3 to examine the wiring and system. If manual testing
shows that everything is normal, check the program version or contact support personnel for
assistance.
6.1.1 Opening the PC I/O Testing Display
52
6.1.2 Open the PLC I/O Testing Display.
l Both hidden buttons must be pressed simultaneously.
Hidden button Hidden button