'操作说明 Hotflow THREE_26_zh.pdf - 第480页

T ranslation of the original ENGLISH 4. TRANSPORT AND ST ORAGE 451820.66.03_EN 2020-05-05 23 4. TRANSPORT AND STORAGE Follow the safety notes in chapter 1! As a rule, the cooling unit must be transported in an upright po…

100%1 / 560
3. TECHNICAL DATA ENGLISH Translation of the original
22
451820.66.03_EN
2020-05-05
Translation of the original ENGLISH 4. TRANSPORT AND ST ORAGE
451820.66.03_EN
2020-05-05
23
4. TRANSPORT AND STORAGE
Follow the safety notes in chapter 1!
As a rule, the cooling unit must be transported in an upright position and without any water
inside!
Internal transport is performed using a forklift truck, lift truck or crane.
The cooling unit must be set down on an even surface to prevent the lower frame from deforming.
Hazardous goods regulations apply when transporting the cooling unit with a refrigerant fill
quantity > 12 kg (see UN 2857).
4.1 Transport specifications
- Weight (see "Technical data")
- Main dimensions (see "Technical data")
- Ambient temperatures -20°C to +60°C
At ambient temperatures < 0°C, the water circuits, evaporators, pump(s), water filters and tank(s)
must be completely drained.
(See chapter 8 "Decommissioning/shutdown")
In the case of transport after operation with water, we recommend rinsing the cooling unit
with a water-glycol mixture of 60% : 40% after draining!
4. TRANSPORT AND STORAGE ENGLISH Translation of the original
24
451820.66.03_EN
2020-05-05
4.2 Transport – forklift truck
When transporting the cooling unit with a forklift truck, only the relevant openings on the wide side in
the lower frame of the device must be used. Ensure that the forks are inserted horizontally under the
entire unit depth and that they are positioned symmetrically with regard to the cooling unit's centre of
gravity before starting to lift.
The unit must be lifted slowly!
Transport with a forklift truck
Example figure