Page 36 GS-394-02 Environmental Requirements Ambient 10° C. to 35° C. Temperature (50° F. to 95° F.) Operating 10% to 90%, non-condensing Humidity Contaminants The machine, UPS included, carries an IP code rating of 20. …

Page 35GS-394-02
Service Requirements (including Uninterruptible
Power Supply)
Electrical (insertion machine)
Machine is shipped with a power cord from
machine to Uninterruptible Power Supply. A
mating connector is supplied to attach the user
provided power cord to the UPS.
The UPS has an external 5mm ground stud which
must be permanently connected to earth/building
ground with a 14 AWG or 2.5mm
2
wire that is
appropriately protected from mechanical damage.
A circuit breaker is the overcurrent device for both
the machine and the UPS. The machine breaker
has a short circuit interrupting capacity of
10,000A, and the UPS breaker has a short circuit
interrupting capacity of 1000A.
The branch circuit supplying the machine must be
protected by an approved 15 amp circuit breaker
with a delay suitable for "high inrush current" or
"transformer loads."
Air Consumption A quick disconnect with a male barbed fitting for
12.7mm (0.50") ID flexible hose is shipped with
each machine.
Pneumatic connection located in the back of the
machine, 228mm (9") from the right side and
558mm (22") from the floor.
Air Quality Non-lubricated, dry air, dewpoint must be at 11°C
(20°F) below ambient temperature. Dust
contamination: particle size of 5.0 microns or
smaller. Oil contamination: Lubricant should not
exceed 0.08 ppm at 28°C (82°F).
Note:
• Without loader, for voltages other than 230 VAC, current is 1150/
(input voltage). Power factor may vary with input voltage.
• With loader, for voltages other than 230 VAC, current is 1725 /
(input voltage). Power factor may vary with input voltage.
• CFM (Cubic Feet per Minute): Volumetric flow rate at a specified
pressure. This is used to describe the air flow requirement. This is
used to determine input air line requirements.
• SCFM (Standard Cubic Feet per Minute): Cubic foot of air at 20° C
(68º F) at atmospheric pressure. This is used to describe the
average air consumption flow requirement needed to determine
compressor capacity requirements.
PNEUMATIC REQUIREMENTS ELECTRICAL REQUIREMENTS
Minimum Air Flow
Requirements of
Machine
Air
Consumption
of Compressor
Input
Volt ag e
Input
Frequency
Input
Breaker
Actual Power
Draw Without
Loader/Unloader
Actual Power
Draw With
Loader/Unloader
Insertion Machine
Location
85 liters per minute @
6.2 bar
3.0 CFM @ 90 PSI
7.6 SCFM 180 - 264
VAC
47 - 63Hz 15A
1150 VA
5A @ 230 VAC
1725 VA
7.5A @ 230 VAC
Additional Sequencer
Location
64 liters per minute @
6.2 bar
2.25 CFM @ 90 PSI
No Additional
Air Consumption

Page 36 GS-394-02
Environmental Requirements
Ambient 10° C. to 35° C.
Temperature (50° F. to 95° F.)
Operating 10% to 90%, non-condensing
Humidity
Contaminants The machine, UPS included, carries an IP code
rating of 20. IP 20 signifies that the equipment
has limited protection against ingress of solid
foreign objects and is not protected against the
ingress of water. Consequently, the intended
environment is that of manufacturing/office
where the machine is not subject to such
elements.
Transportation -25° C to +55° C. (-13° F. to +131° F.); not
and Storage exceeding 24 hours up to 70° C. (158° F.), 10%
to 95%, non-condensing humidity.
Universal provides suitable means to prevent
damage from humidity, vibration, stress and
shock during transport.
Noise Level, 76.3 dbA in accordance with National Machine
Pass Through Toolbuilders Assoc. Noise Measurement
Configuration Technique Standard — June 1986.
Note: Maximum noise level measured at the
Sequencer, while the noise level in front of the
machine, at the operator controls, is 74 dbA.
Noise Level, 80.7 dbA in accordance with National Machine
Non Pass Through Toolbuilders Assoc. Noise Measurement
Configuration Technique Standard — June 1986.

A - 37GS-394-02, Appendix: Automatic Board Handling Systems
Index
Appendix: Automatic Board Handling Systems
Introduction .......................................................................................................... A-38
Technical Specifications for Internal Board Handling System (BHS) ............... A-40
Workboard Clearances at Table Rotation Locations .......................................... A-41
Technical Specifications for Loader/Unloader:
Elevator/Buffer Configuration ....................................................................... A-42
Magazine Specifications for use in Elevator Buffer System .............................. A-43
Technical Specifications for Loader/Unloader ................................................... A-43
Installation Considerations: Loader/Unloader .................................................... A-45
Service Requirements .......................................................................................... A-46