ELECTROVA P ® E LMC 10 3. INSTALL ATIO N 3.1 PROCEDU RE • Mark and drill where indicated (ho les size depend s on t he selected dowels and support materials). • Put t he dowels in t he holes. • Screw t he top sc rews int…

ELECTROVAP® ELMC
9
2.4 IMPORTANT INSTRUCTIONS
• Ambient temperature: between 5 and 40°C
• Ambient humidity: < 80% Relative humidity
• Back side: this component heats during operation (up to 60°C). Make sure that the support of the device is
not made of a heat-sensitive material.
• Wall mounting: Please be careful that the support material receiving the device (pillar, wall, etc.) can support
it.
• Fixation: use a fastening system adapted to the support material.
• Make sure that the mounting distances are met.
Please read and follow the enclosed safety information and the warning labels
inside the humidifier before installation or maintenance.
Some steps can be dangerous.
Visit our website or contact our operators for technical support.
Fig.2-4. Mounting distances

ELECTROVAP® ELMC
10
3. INSTALLATION
3.1 PROCEDURE
• Mark and drill where indicated (holes size depends on the selected dowels and support materials).
• Put the dowels in the holes.
• Screw the top screws into the dowels (M6 recommended), let them protrude by about 10 mm/0.39in.
• Hang the device to the top screws and align it vertically and horizontally with a bubble level.
• Tighten up all screws.
(*)
SC = Small Cylinder - MC= Medium Cylinder
ELMC
1 SC
(*)
ELMC
1 MC
(*)
ELMC
2 MC
(*)
ELMC
3 MC
(*)
Has:
400
450
750
1000
A1:
500
A2:
35
53
23
38
B:
400
510
510
510
B1:
81
81
81
81
Fig. 3-1. Installation holes

ELECTROVAP® ELMC
11
3.2 WATER SUPPLY
3.2.1 Recommendation
Our device is designed to be used with any following water type:
✓ drinking water (according to Directive 98/83/EEC, TH
(French grade) between 0°fH and 40°fH and conductivity
between 250 µS/cm and 1000 μS/cm)
✓ softened water,
✓ demineralized water, reverse osmosis water: use
possible under conditions. Please contact our services
The demineralized water is corrosive; use appropriate piping material: stainless steel, PVC.
Softened water: Its use is not necessary, but possible. TH should be between 0° fH and 2° fH.
Water analysis is recommended to determine the level of sodium chloride.
Do not hesitate to contact our services for support.
3.2.2 Recommendations on connection
Network water pressure: The pressure must be stable and between 2 bar and 8 bar MAX. in case the water pressure
exceeds 8 bar, a water regulator calve must be used.
Network water temperature: < 40 °C.
Please note that the water supply is connected at the lower part of the unit.
For easy maintenance, the water inlet valve is equipped with a filter strainer which should be checked periodically. It
is essential to install an isolation valve near the humidifier to facilitate maintenance.
OVERFLOW RISKS: it is recommended to install a collecting water tank under the humidifiers to
prevent overflow. This is essential if the unit is installed in false ceilings or above important rooms
(example: museum room, showroom, laboratory etc.). Make sure the container is connected to the
wastewater system.
An excess of sodium chloride may generate foam which disturbs the correct running of the humidifier.
It is mandatory to use a duplex softener.
Max. chloride content: 80 mg/l
Isolation valve
Water system
Fig. 3-2. Humidifier water supply
Flexible braided hose
with 3/4” FF thread