ELECTROVAP® ELMC
41
CONTROL SIGNAL IN
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXX
MENU: CHANGING
UNIT CONFIGURATION
STEAM CAPACITY
LIMIT XX%
Any press on enter key
from any of these menus
MENU: HUMIDIFIER
STATUS
VALUE: 1 step (ON/OFF) / CTRL or Digital Probe / 0-10V,
4-20mA, 1-5V controller / 0-10V, 0-5V humidity sensor
VALUE: If ON/OFF control between 20 and 100 %,
Otherwise between 50-100 %
ADJUST SET POINT
XX%HR
ADJUST PROP BAND
XX%
MAINTENANCE FRE-
QCY XXXXXKG
MAINTENANCE
INTERVAL 300H
FOAM / SCALE
CONTROL XX sec
POWER OFF IF
DRAINING: Xxx
VALUE: between 0 and 999000kg or between 0 and
2000h
Adjusts the estimated number of kg of steam or number
of hours of operation before a visual check of the
cylinder. If you need to clean it, please refer to the
maintenance pages of the manual, if not you can then
increase this maintenance frequency.
Set at 300h out of the factory
VALUE: between 0 and 10 seconds
Allows you to set the time for a small drain. If there is
foam inside the cylinder, increase the time. This foam
phenomenon usually appears with softened water
VALUE: YES or NO
Cuts the contactor(s) during a drain and avoids leakage
currents
VALUE: between 10 and 99 %
VALUE: between 1 and 50%
ADJUST STEAM BY:
XXXXXXXXXX
VALUE: EVAPORATION (necessary for demineralized
water) or DRAINING

ELECTROVAP® ELMC
42
CYLINDER SELECT
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXX
IDENTIFICATION
OF ELMC XX
VALUE: CLEANABLE(EV), CLEANABLE (EA), CLEANABLE
(ED).
EV: Tap water, EA: softened water, ED: demineralized
water
VALUE between 1 and 32: Identifies humidification when
it is connected to a communication bus
PROTOCOL
NETWORK
SPEED DATA
XXXXb/s
VALUE: MODBUS RTU 8-N-1, MODBUS RTU 8-N-2,
BACNET MS/TP
VALUE: 1200/2400/4800/9600 b/s: Syncs the speed of
communication between the ELMC and the
communication system
SETTING TEMP
WATER 65°C: XXX
VALUE: YES or NO: Allows to activate the function of
keeping water temperature at 65°C when the device is
stopped.
WARNING this option requires additional accessories
DRAINING AFTER
SHUT DOWN? Xxx
Value: YES or NO
DRAINING AFTER Xxx
HRS
Value: between 1 and 168 hours
If the end-of-season drain is active
BACK TO THE BEGINNING

ELECTROVAP® ELMC
43
5.4 MAINTENANCE ALERTS
M4: CONTACTOR TO
REPLACE
After 10,000 hours of operation, it is recommended to
replace the contactor. The unit is not stopped
M3: MAINTENANCE
NOT DONE: PURGE
This message appears if 100 hours elapsed between the
appearance of the M2 and M3 message and no
maintenance has been done.
Then the unit is shut down and follows the procedure:
1. 1. Emptying the cylinder
2. 2. Cooling the cylinder
3. 3. Ready for maintenance
M2: MAINTENANCE
TO DO
The maintenance timer has arrived at 0, it is necessary to
do the maintenance of the device. The unit is not stopped
M1: 50 HOURS
CONTROL
This message will appear 50 Hrs after the first start.
It is then necessary to check the correct tightening of
electrical and hydraulic connections (steam pipe, drain
system, water supply...). The unit is not stopped
TO CARRY OUT A RESET FOR THE ABOVE
MESSAGES, FOLLOW THIS PROCEDURE:
-Switch the unit to drain by pressing the manual drain button (4).
-Press button 3 for at least 5 seconds.
5
1
2
3
4