ELECTROVA P ® E LMC 47 6 MAINTENA NCE 6.1 GENERAL INFORMATION Periodic checks • After an hour of operat ion, check for no water leaks in the middle and foot of the cylinder. • After 50 hours of operat ion, check the c on…

100%1 / 56
ELECTROVAP® ELMC
46
Meaning: Draining is not properly done
In this case:
When this message appears, the cylinder is drained, the general fault contact is activated, and the device is stopped.
Causes and remedies:
1. The drain system is clogged. Press the manual drain button, and check for the proper flow of water. Then clean
the inside of the cylinder. Check if there is limestone in the valve.
Alarm
P8
Information "CLEAN CYLINDER + DRAIN VALVE"
TO CARRY OUT A RESET FOR THE ABOVE
MESSAGES, FOLLOW THIS PROCEDURE:
-Switch the unit to drain by pressing the manual drain button (4).
-Press button 3 for at least 5 seconds.
5
1
2
3
4
ELECTROVAP® ELMC
47
6 MAINTENANCE
6.1 GENERAL INFORMATION
Periodic checks
• After an hour of operation, check for no water leaks in the middle and foot of the cylinder.
• After 50 hours of operation, check the condition of the cylinder. Make sure no arcing or flicker occurs between
the electrodes during operation.
Check the filter inside the water inlet valve as well as the drain system.
Please re-examine all the power cable connection terminals, as well as the clamps of the various pipes (steam,
drain, inside the wet part).
WARNING! Tighten the clamps when the cylinder is cold.
• After a year of operation, please check the condition of your steam hose, water drain and the internal pipes of the
unit. If some pipes seem damaged, it is essential to change them. Please tighten all connection terminals.
Warnings
After a prolonged use or with the use of high TH water, may be solid deposits on the electrodes which can increase
the concentration of water.
If electrical arcs appear inside the cylinder, your humidifier works under abnormal conditions and these arcs can cause:
• A significant heat increase that could overheat the plastic and even melt it, causing a hole and then a leak into the
unit.
• A disjunction of the device due to a high intensity created by the electrical arcs.
• Premature deterioration of heating electrodes.
• Burning of electrodes power cables.
In case of electric arcs
Check any points in case electrical arcs appear inside the cylinder:
• If your water is running with softened water, make sure your softener does not release salt into the appliance's
water supply pipes.
• Make sure the drain valve is working properly and maintain it.
• Check F3 drain valve fuse on the main board.
The humidifier has powered electrical components and the cylinder has heated elements.
Therefore, all work must be carried out by qualified and competent personnel.
Before working on the cylinder, make sure that the humidifier is switched off.
ELECTROVAP® ELMC
48
6.2 STEAM CYLINDER CLEANING
ESTIMATED CYLINDER MAINTENANCE CURVE
X – steam demand
Hours of operation
Example: for a humidifier operating at 100% capacity, using water with TH20, the cylinder will need to be cleaned or
changed after 800-900 hours of operation.
• The water hardness is expressed in French degrees. The value thus expressed refers to the Total Hardness
of the water (TH).
• The water quality must be specified when choosing your unit in order to adapt the cylinder to your
type/quality of water.
ELECTRODE CHANGE
Original length
Type
ELMC 5 to 15
ELMC 20 to 90 and ELMC 10 MONO
Length [mm]
160
250
The electrodes must be changed when their length is less than 1/3 of the original length.
ElectroVap ELMC are equipped as standard with cleanable cylinders that can be disassembled using two 8 keys.
300 H
800 H
1000 H
2000 H
4000 H