ELECTROVAP® ELMC
18
3.5 CONDENSATE DRAINING WITH SIPHON
The condensate hose must not be directly connected to the public sewerage network.
H min. (mm) = P (Pa)/10
with P = absolute pressure of the air handling unit or the ventilation duct
Fig. A 3-5.
Fig. B 3-5.

ELECTROVAP® ELMC
19
3.6 DRAIN HOSE CONNECTION
The following drawing shows the drain hose connection that should be made.
Use a Ø 25 mm rubber drain hose with the 2 supplied hose clamps, heat-resistant (up to 100°C).
Connect the hose to the draining system. Regular replacement is recommended.
If rigid piping is used, it must be a heat-resistant PVC material (up to 100 °C).
The discharge hose must be free from any obstacle.
It is recommended that each humidifier has its own drain pipe.
If possible, use a collecting water tank with a lid (see the picture below).
Drain hose (optional)
Collecting water tank
(optional)
Condensate hose (optional)
Pipe - minimum Ø 60mm (optional)
Fig. A 3-6. Example of Installation

ELECTROVAP® ELMC
20
A funnel can also be used (see picture below), but it should be offset from the underside of the unit to prevent
any steam and/or condensation from getting into the cabinet.
CAUTION: keep a minimum downward slope of 10° for both the draining & overflow hoses of the humidifier
and for the general drain pipe.
Note: ELMC humidifiers are by design equipped with a condensate cooling system that guarantees the following
cooling performance:
Model
max T°C in
operation
(*)
max T°C with
manual draining
(*)
max T°C with
manual draining
aer 1hr
(*)
ELMC 1 SC/1MC
60°C
97°C
70°C
ELMC 2 MC
60°C
97°C
70°C
ELMC 3 MC
60°C
97°C
70°C
(*)
measurement made 1m after emptying the humidifier
Fig. B 3-6. Example of Installation with funnel