ELECTROVA P ® E LMC 32 3.9 CONTROL SIGNAL CONNECTI ON The wiring of th e optional equ ipment m ust be made w ith 0.75 mm 2 sh ielded cab le. T his cont rol signal wi re sh ould not be rout ed with a p ower cable. Control…

100%1 / 56
ELECTROVAP® ELMC
31
ELMC 90, Up[V] - 3x200-690V 50-60Hz
ELECTROVAP® ELMC
32
3.9 CONTROL SIGNAL CONNECTION
The wiring of the optional equipment must be made with 0.75 mm
2
shielded cable. This control signal wire should not
be routed with a power cable.
Control
signal
-
+
High Limit
Switch
Safety
PROPORTIONAL CONTROL
ELMC
3
4
1
2
Main board
33
18
19
20
X05
0
On
Off
SW2
ON/OFF CONTROL
ELMC
3
4
1
2
Control
Switch
CTRL SIGNAL TYPE
ON - OFF CONTROL
x
CTRL SIGNAL TYPE
4-20mA CONTROL
x
XXXX
0 - 5V CONTROL
x
XXXX
1 2 3 4
On
0-10V
CONTROL
1 2 3 4
On
4-20mA
CONTROL
1 2 3 4
On
0-5V
CONTROL
0-10V CONTROL
x
XXXX
SW2 Dip switch setting to do on main board
Control signal type setting in humidifier menu
ELECTROVAP® ELMC
33
HUMIDITY SENSOR CONTROL
ELMC
3
4
1
2
Main board
33
18
19
20
X05
0
On
Off
SW2
+24Vdc
+15Vdc
High Limit
Switch
Safety
V+
Humidity
sensor
1 2 3 4
GND
rH
SW2 Dip switch setting to do on main board
CTRL SIGNAL TYPE
Control signal type setting in humidifier menu
0 - 10V SENSOR
x
XXXX
1 2 3 4
On
0-10V
CONTROL
1 2 3 4
On
0-5V
CONTROL
CTRL SIGNAL TYPE
DIGITAL CONTROL
x
XXXX
0 - 5V SENSOR
x
XXXX
Control signal type setting in humidifier menu
WITH DIGITAL CONTROL (Modbus - BACnet)