1. Material
NBR: Nitrile rubber
FKM: Fluororubber
EPDM: Ethylene propylene rubber
2. Oil-free treatment
The degreasing and washing of wetted parts
3. Symbol
In the symbol ( ), when the valve is closed, flow is blocked
from port 1 to port 2. However, if the pressure in port 2 is higher
than port 1, the valve will not be able to block the fluid and it will
flow from port 2 to port 1.
Pressure Terminology
1. Maximum operating pressure differential
The maximum pressure differential (the difference between
the inlet and outlet pressure) which is allowed for operation.
When the outlet pressure is 0 MPa, this becomes the maxi-
mum operating pressure.
2. Minimum operating pressure differential
The minimum pressure differential (the difference between the
inlet pressure and outlet pressure) required to keep the main
valve fully open.
3. Maximum system pressure
The maximum pressure that can be applied inside the pipe-
lines (line pressure).
[The pressure differential of the solenoid valve portion must
not exceed the maximum operating pressure differential.]
4. Withstand pressure
The pressure in which the valve must be withstood without a
drop in performance after holding for one minute under pre-
scribed pressure and returning to the operating pressure
range. [value under the prescribed conditions]
Electrical Terminology
Electrical Terminology
1. Apparent power (VA)
Volt-ampere is the product of voltage (V) and current (A).
Power consumption (W): For AC, W = V·A·cos θ.
For DC, W = V·A.
Note) cos θ shows power factor. cos θ ≈ 0.9
2. Surge voltage
A high voltage which is momentarily generated by shutting off
the power in the shut-off area.
3. Degree of protection
A degree defined in the “JIS C 0920: Waterproof test of elec-
tric machinery/appliance and the degree of protection against
the intrusion of solid foreign objects.”
Verify the degree of protection for each product.
Second
characteristic
numeral
IP
First
characteristic
numeral
First Characteristics:
Degrees of protection against solid foreign objects
0
1
2
3
4
5
6
Non-protected
Protected against solid foreign objects of 50 mmø and greater
Protected against solid foreign objects of 12 mmø and greater
Protected against solid foreign objects of 2.5 mmø and greater
Protected against solid foreign objects of 1.0 mmø and greater
Dust-protected
Dust-tight
Example) IP65: Dust-tight, Water-jet-proof type
“Water-jet-proof type” means that no water intrudes
inside an equipment that could hinder from operating
normally by means of applying water for 3 minutes in
the prescribed manner. Take appropriate protection
measures, since a device is not usable in an environ-
ment where a droplet of water is splashed constantly.
Second Characteristics:
Degrees of protection against water
0
1
2
3
4
5
6
7
8
—
VX21/22/23 Series
Glossary of Terms
Others
Flat Terminal
Dripproof type 1
Dripproof type 2
Rainproof type
Splashproof type
Water-jet-proof type
Powerful water-jet-proof type
Immersible type
Submersible type
Non-protected
Protected against vertically falling water drops
Protected against vertically falling water drops
when enclosure tilted up to 15°
Protected against rainfall when enclosure tilted up to 60°
Protected against splashing water
Protected against water jets
Protected against powerful water jets
Protected against the effects of temporary immersion in water
Protected against the effects of continuous immersion in water
Flat terminal/Electrical connection size of molded coil
0.8
8
3.4
6.35
Chamfer
65
VX2
VXK
VXD
VXZ
VXS
VXB
VXE
VXP
VXR
VXH
VXF
VX3
VXA
VX2

C, b
Indication by
international standard
S
Cv
Cv
Conformed standard
ISO 6358: 1989
JIS B 8390: 2000
JIS B 8390: 2000
Equipment: JIS B 8379, 8381-1, 8381-2
IEC60534-1: 2005
IEC60534-2-3: 1997
JIS B 2005-1: 2012
JIS B 2005-2-3: 2004
Equipment: JIS B 8471, 8472, 8473
ANSI/(NFPA)T3.21.3 R1-2008
Table (1) Indication of Flow Rate Characteristics
Kv
—
—
—
—
Pneumatic
equipment
Process fluid
control
equipment
Corresponding
equipment
Other
indications
1.
Indication of flow rate characteristics
The flow rate characteristics in equipment such as a solenoid valve, etc. are indicated in their specifications as
shown in Table (1).
2.
Pneumatic equipment
2.1 Indication according to the international standards
(1) Conformed standard
ISO 6358: 1989
: Pneumatic fluid power—Components using compressible fluids—
Determination of flow rate characteristics
JIS B 8390: 2000 : Pneumatic fluid power—Components using compressible fluids—
How to test flow rate characteristics
(2) Definition of flow rate characteristics
The flow rate characteristics are indicated as a result of a comparison between sonic conductance C and
critical pressure ratio b.
Sonic conductance C
:
Value which divides the passing mass flow rate of an equipment in a choked flow
condition by the product of the upstream absolute pressure and the density in a
standard condition.
Critical pressure ratio
b : Pressure ratio (downstream pressure/upstream pressure) which will turn to a choked
flow when the value is smaller than this ratio.
Choked flow : The flow in which the upstream pressure is higher than the downstream pressure and
where sonic speed in a certain part of an equipment is reached.
Gaseous mass flow rate is in proportion to the upstream pressure and not dependent
on the downstream pressure.
Subsonic flow : Flow greater than the critical pressure ratio
Standard condition
: Air in a temperature state of 20°C, absolute pressure 0.1 MPa (= 100 kPa = 1 bar),
relative humidity 65%.
It is stipulated by adding the “(ANR)” after the unit depicting air volume.
(standard reference atmosphere)
Conformed standard: ISO 8778: 1990 Pneumatic fluid power—Standard reference
atmosphere, JIS B 8393: 2000: Pneumatic fluid power—Standard reference atmosphere
(3) Formula for flow rate
It is described by the practical units as following.
When
P2 + 0.1
————
≤ b, choked flow
P1 + 0.1
293
Q = 600 x C (P1 + 0.1)
————
·····························································(1)
273 + T
When
P2 + 0.1
———— > b, subsonic flow
P1 + 0.1
P2 + 0.1
———— – b
P1 + 0.1
Q = 600 x C (P1 + 0.1) 1 –
—————— ———— ····························
(2)
1 – b
2
293
273 + T
VX21/22/23 Series
Solenoid Valve Flow Rate Characteristics
(How to indicate flow rate characteristics)
66

ød2
ød1
3d3
3d210d23d110d1≥10d3
ød3≥3d1
Q
: Air flow rate [L/min (ANR)]
C
: Sonic conductance [dm
3
/(s·bar)], dm
3
(Cubic decimeter) of SI = L (liter).
b
: Critical pressure ratio [—]
P1
: Upstream pressure [MPa]
P2
: Downstream pressure [MPa]
T
: Temperature [°C]
Note) Formula of subsonic flow is the elliptic analogous curve.
Flow
rate characteristics are shown in Graph (1) For details, please use the calculation software available from SMC website.
Example)
Obtain the air flow rate for P1 = 0.4 [MPa], P2 = 0.3 [MPa], T = 20 [°C] when a solenoid valve is performed in
C = 2 [dm
3
/(s·bar)] and b = 0.3.
293
According to formula 1, the maximum flow rate = 600 x 2 x (0.4 + 0.1) x ————— = 600 [L/min (ANR)]
273 + 20
0.3 + 0.1
Pressure ratio = ————— = 0.8
0.4 + 0.1
Based on Graph (1), it is going to be 0.7 if it is read by the pressure ratio as 0.8 and the flow ratio to be b = 0.3.
Hence, flow rate = Max. flow x flow ratio = 600 x 0.7 = 420 [L/min (ANR)]
(4) Test method
Attach a test equipment with the test circuit shown in Fig. (1) while maintaining the upstream pressure to a
certain level which does not go below 0.3 MPa. Next, measure the maximum flow to be saturated in the first
place, then measure this flow rate at 80%, 60%, 40%, 20% and the upstream and downstream pressure. And
then, obtain the sonic conductance C from this maximum flow rate. In addition, calculate b using each data of
others and the subsonic flow formula, and then obtain the critical pressure ratio b from that average.
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Equipment
C, b
P2
Q
P1
b = 0.1
0.2
0.5
0.6
0.3
0.4
Pressure ratio (
P2 + 0.1) / (P1 + 0.1)
Air
supply
Pressure control
equipment
Thermometer
Pressure gauge or
pressure convertor
Differential pressure gauge or
differential pressure converter
Flow control
valve
Filter
Pipe for measuring
temperature
Pipe for
measuring
pressure in the
upstream side
Pipe for
measuring
pressure in the
downstream side
Equipment
for test
Shut off
valve
Flow meter
Fig. (1) Test circuit based on ISO 6358: 1989, JIS B 8390: 2000
Graph (1) Flow rate characteristics
Flow rate ratio
Example
67
Solenoid Valve Flow Rate Characteristics