3. TECHNICAL DA T A ENGLISH T ranslation of the original 22 451820.66.03_EN 2020-05-05

100%1 / 560
Translation of the original ENGLISH 3. TECHNICAL DATA
451820.66.03_EN
2020-05-05
21
3. TECHNICAL DATA
See technical section
3. TECHNICAL DATA ENGLISH Translation of the original
22
451820.66.03_EN
2020-05-05
Translation of the original ENGLISH 4. TRANSPORT AND ST ORAGE
451820.66.03_EN
2020-05-05
23
4. TRANSPORT AND STORAGE
Follow the safety notes in chapter 1!
As a rule, the cooling unit must be transported in an upright position and without any water
inside!
Internal transport is performed using a forklift truck, lift truck or crane.
The cooling unit must be set down on an even surface to prevent the lower frame from deforming.
Hazardous goods regulations apply when transporting the cooling unit with a refrigerant fill
quantity > 12 kg (see UN 2857).
4.1 Transport specifications
- Weight (see "Technical data")
- Main dimensions (see "Technical data")
- Ambient temperatures -20°C to +60°C
At ambient temperatures < 0°C, the water circuits, evaporators, pump(s), water filters and tank(s)
must be completely drained.
(See chapter 8 "Decommissioning/shutdown")
In the case of transport after operation with water, we recommend rinsing the cooling unit
with a water-glycol mixture of 60% : 40% after draining!