DeltaTherm IR Cure Module
Revision B / February 2020
Page 30 of 41
Fault Recovery Procedure
Several errors can cause a fault condition. They are:
The EMERGENCY STOP is engaged or there is an open door
There is an exhaust or intake fan failure
The parameters are out of range
The module is over-temperature
There is a solid-state relay failure
The following sections show an example of a machine error. For a complete list of error
messages, refer to Section 11
.
Recovery from Emergency Stop or Open Door Error
If the Emergency Stop button is engaged or the machine has a system error, perform the
following procedure to return the machine to the cycle stop state.
WARNING: If the Emergency Stop was engaged because of system failure, do not
disengage the Emergency Stop. Shutdown the system and have qualified personnel
repair the machine.
1. Disengage the Emergency Stop button or close all doors.
2. Select “Clear Fault”.
Recovery from an Exhaust or Intake Fan Failure
1. Select “Clear Fault” to stop the alarm or “Reset” to clear the fault.
2. Operate the fan in Manual mode to make sure the components operate correctly.
Recovery from a Parameter Out of Range Error
1. Select “Silence Horn” to stop the alarm or “Clear Fault” to clear the fault.
2. Operate the module in manual mode or restart the Auto Cycle. Look for the
parameter that causes the error.
3. If the error continues to repeat, refer to Section 12
.
DeltaTherm IR Cure Module
Revision B / February 2020
Page 31 of 41
Recovery from an Over-Temperature Error
1. Select “Silence Horn” to stop the alarm orClear Fault” to clear the fault.
2. Let the module temperature decrease.
3. Operate the module in manual mode or restart Auto Cycle. Look for the parameter
that causes the error.
4. If the error continues to repeat, refer to Section 12
.
Recovery from an Auto Conveyor Adjust Error
In the conveyor homing procedure, two errors may occur:
Error 1: The conveyor passes the home position sensor and hits the hard stop on one side.
1. When the conveyors pass the sensor and hit the hard stop, engage the “Emergency
Stop” button.
2. Open the left cabinet and find fuse number 70.
3. Release the fuse and disengage the “Emergency Stop button. This will move the
conveyor toward the sensor.
4. When the conveyor passes the sensor, engage the “Emergency Stop” button again.
5. Examine the integrity and the wiring of the sensor.
6. Install fuse number 70, and home the conveyor again.
Error 2: The conveyor passes the software limit and hits the hard stop on the other side.
1. Engage the “Emergency Stop” button.
2. Open the left cabinet and find the conveyor direction relay (CR11).
3. Pull the blue button and disengage the “Emergency Stop” button. The conveyor
will move away from the hard stop.
4. Engage the “Emergency Stop” button again. This will stop the conveyor.
5. Push the blue button so it is in the original position in the relay.
6. Examine the wire and the conveyor position encoder.
DeltaTherm IR Cure Module
Revision B / February 2020
Page 32 of 41
Error Messages
The following are all the possible error messages generated by the PLC program.
Msg Number
DeltaTherm Fault Messages
100
Zone 1/2 Overtemp Monitor Fault
101
Zone 3/4 Overtemp Monitor Fault
102
Zone 5/6 Overtemp Monitor Fault
103
Zone 7/8 Overtemp Monitor Fault
104
Exhaust Fan Low Pressure.
105
Panel 1A Overtemp >285C
106
Panel 1B Overtemp >285C
107
Panel 2A Overtemp >285C
108
Panel 2B Overtemp >285C
109
Panel 3A Overtemp >285C
110
Panel 3B Overtemp >285C
111
Panel 4A Overtemp >285C
112
Panel 4B Overtemp >285C
113
Master Conveyor Width (CAN4) Drive Homing Timeout
114
Slave Conveyor Width (CAN6) Drive Homing Timeout
115
Data Table Error Values Not Downloaded
118
System Options Changed Reboot Required.
131
Control Power Timeout Fault
132
Autocycle Idle Timeout
141
Master Conveyor Transfer (CAN3) Communication Timeout
142
Master Conveyor Width (CAN4) Communication Timeout
143
Slave Conveyor Transfer (CAN5) Communication Timeout
145
Slave Conveyor Width (CAN6) Communication Timeout
147
Board Process Timeout Error
148
Panel 5A Overtemp >285C
149
Panel 5B Overtemp >285C
150
Panel 6A Overtemp >285C