Power supply S-20/S-23HM/F4/F5/F5HM/S-25HM/HS-50 Conversion Instructions
4.5 Converting the power supply from 3 x 204 VAC to 3 x 400 V ~ 03/2001 Edition
122
4.5.2 Replacing the motor protection trip block
The ZM-16-PKZ2 motor protection trip block, article number 00342495-01, must be used for
3x380 VAC, 3x400 VAC and 3x415 VAC supply voltages. The position of the motor protection trip
block is shown in Fig. 4 - 12
, item MS1A.
4.5.2.1 Removing the motor protection trip block
4
Fig. 4 - 13 Removing the motor protection trip block MS1A
4
Fig. 4 - 14 Lifting the protective flap
Turn the switch (1) counter-clockwise to the "0" position
Lift the
protective flap (2)
S-20/S-23HM/F4/F5/F5HM/S-25HM/HS-50 Conversion Instructions Power supply
03/2001 Edition 4 Converting the power supply unit on HS-50 placement machines
123
Fig. 4 - 15 Releasing the yellow locking tab
Fig. 4 - 16 Removing the motor protection trip block MS1A
Use the screwdriver to push up the yellow locking tab (3)
Pull out the motor protection
trip block (4)
Power supply S-20/S-23HM/F4/F5/F5HM/S-25HM/HS-50 Conversion Instructions
4.5 Converting the power supply from 3 x 204 VAC to 3 x 400 V ~ 03/2001 Edition
124
4.5.2.2 Inserting the motor protection trip block
Å Check the type of motor protection trip block before you insert it. The type depends on the
operating voltage.
Å Check the overcurrent and short-circuit current trip threshold settings.
Fig. 4 - 17 Checking the overcurrent and short-circuit current trip thresholds
Å Insert the motor protection trip block a.
Å Push the yellow locking tab f down.
Å Close the gray protective flap g.
Å Turn the rotary switch h clockwise as far as the stop.
Main power voltages Type
3x380 VAC ± 5% ZM-16-PKZ2
3x400 VAC ± 5% ZM-16-PKZ2
3x415 VAC ± 5% ZM-16-PKZ2
Tab. 4 - 4 Motor protection trip block for 3x380 VAC, 3x400 VAC, 3x415 VAC
Motor protection trip
block
Yellow dial (1) for setting the
overcurrent trip threshold
Red dial (2) for setting the short-
circuit current trip threshold
ZM-16-PKZ2 12 A 190 A
Tab. 4 - 5 Overcurrent and short-circuit current trip thresholds
Check the overcurrent trip
threshold (yellow dial a)
Check the short-circuit
current trip threshold
(red dial s)