8 Attributes 8.1 Trip Codes Code Description 0 No trip 11 Input A trip 20 Motor overload 21 Heatsink overtemperature 23 L1 phase loss 24 L2 phase loss 25 L3 phase loss 26 Current imbalance 27 Ground fault 28 Overcurrent …

•
•
Object name
Class
Instance
Attribute
Major software version - Motor control
104
103
100
Minor software version - Motor control
104
104
100
Major software version - Remote LCP (if installed)
104
105
100
Minor software version - Remote LCP (if installed)
104
106
100
Major software version - Expansion card (if installed)
104
107
100
Minor software version -. Expansion card (if installed)
104
108
100
7.2.3 Supported Services for Vendor-specific Objects
This section describes the operational instructions to carry out acyclic services on class objects 100, 101, 102, 103, and 104.
7.2.3.1 Service Codes for Acyclic Operation
Table 7: Supported Services for Vendor-specific Objects
Service code
Function
Description
01d (0x01)
Get attribute all
Only supported for class 0x01 identity object
10d (0x10)
Set attribute single
Supported
15d (0x0E)
Get attribute single
Supported
7.2.3.2 Status Codes for Acyclic Services
Table 8: Status Codes Returned in Response to Get/Set Attribute Single
Status code
Status name
Details
00d (0x00)
Success
This code is returned when:
the register mapped for "Get Attribute Single" is successfully read.
the register mapped for "Set Attribute Single" is successfully set.
03d (0x03)
Invalid parameter value
–
05d (0x05)
Path destination unknown
The mapped register does not exist.
08d (0x08)
Service not supported
The requested service is not available for this object class/instance.
09d (0x09)
Invalid attribute value
This code only applies to the service Set Attribute Single. It is returned if the value is
out of range of the mapped register.
15d (0x0E)
Attribute not settable
This code only applies to the service Set Attribute Single. It is returned if the mapped
register is read-only.
20d (0x14)
Attribute not supported
The attribute specified in the request is not supported.
22d (0x16)
Object does not exist
The object specified does not exist in the device.
AN353423548483en-000201 / 130R0945 | 25Danfoss A/S © 2022.10
Messaging
EtherNet/IP Card
Installation Guide

8 Attributes
8.1 Trip Codes
Code
Description
0
No trip
11
Input A trip
20
Motor overload
21
Heatsink overtemperature
23
L1 phase loss
24
L2 phase loss
25
L3 phase loss
26
Current imbalance
27
Ground fault
28
Overcurrent
29
Undercurrent
50
Power loss
51
Undervoltage
52
Overvoltage
54
Phase sequence
55
Frequency
60
Incorrect control card
61
FLC out of range
62
EEPROM fail (parameter out of range)
75
Motor thermistor
101
Excess start time
102
Motor connection
104
Internal fault
110
Input B trip
113
Communications card fault
114
Network communication
115
L1-T1 shorted
116
L2-T2 shorted
117
L3-T3 shorted
119
Bypass overload
AN353423548483en-000201 / 130R094526 | Danfoss A/S © 2022.10
Attributes
EtherNet/IP Card
Installation Guide

Code
Description
120
SCR overtemperature
121
Battery/clock
122
Thermistor circuit
124
RTD/PT100 B
133
Overpower
134
Underpower
142
LCP disconnected
143
Zero speed detect
144
SCR Itsm
145
Instantaneous overcurrent
146
Rating capacity
156
Current read error L1
157
Current read error L2
158
Current read error L3
160
Motor connection T1
161
Motor connection T2
162
Motor connection T3
163
Firing fail P1
164
Firing fail P2
165
Firing fail P3
166
VZC fail P1
167
VZC fail P2
168
VZC fail P3
169
Low control volts
170–182
Internal fault X. Contact the local supplier with the fault code (X).
8.2 Parameter Lists
N O T I C E
These parameter lists are for parameter list version 3.x. To check the parameter list version, read class 103d, instance 131, attrib-
ute 100.
For other parameter list versions, refer to the soft starter Operating Guide or contact the local supplier for assistance.
AN353423548483en-000201 / 130R0945 | 27Danfoss A/S © 2022.10
Attributes
EtherNet/IP Card
Installation Guide