DeltaTherm IR Cure Module Revision C / Sept ember 2022 Page 18 of 41 Auto Cycle 207B206B206B Auto Cycle is the normal operating mode for the DeltaTh erm IR Cure Mod ule. In Auto Cycle, the cure module can operate as pa r…

DeltaTherm IR Cure Module
Revision C / September 2022
Page 17 of 41
Cycle Stop
205B204B204B
9B9B9BFigure 10: Cycle Stop
206B205B205BOptions in Cycle Stop are: Auto Cycle, Manual, and Setup.
Select “F1” or the auto cycle icon to operate the module in Auto Cycle.
Select “F3” or the manual icon to operate the module in Manual mode.
Select “ESC” or the settings icon to go to Setup mode and view or
change the operating parameters of the module.
Select the Home icon or “F3” from any mode to return to Cycle Stop.

DeltaTherm IR Cure Module
Revision C / September 2022
Page 18 of 41
Auto Cycle
207B206B206BAuto Cycle is the normal operating mode for the DeltaTherm IR Cure Module. In Auto Cycle,
the cure module can operate as part of a production line. All communication with adjacent
machines is done without operator input. In Auto Cycle, the machine uses the parameters in
setup mode. The screen below shows Auto Cycle with four zones top and bottom.
208B207B207B
10B10B10BFigure 11: Auto Cycle
1. 50B49B49BThe Panel Temperature shows the current temperature of the heater panel.
2. 51B50B50BThe Panel Temperature Setpoint shows the current recipe’s temperature setpoint
of the heater panel.
3. 52B51B51BThe At Temperature indicator will light up when the panel temperature is within
the allowable setpoint deviation value.
4. 53B52B52BThe Current Recipe Name will display at the top of the screen.
5. 54B53B53BThe Board Counter displays the number of boards in the oven. In the event of an
incorrect value (PIP flashing), press and hold for 5 seconds to reset this to zero
6. 55B54B54BThe Autocycle Messages section displays the current Auto Cycle state and status
messages.
7. 56B55B55BPress to the Heater Panel Trend icon to view a graph of panel temperature values
over time.
8. 57B56B56BTo view the next set of panels and zones, press the Next Zone button.
9. 58B57B57BThe SMEMA Status shows the current status of SMEMA inputs and outputs.
10. 59B58B58BThe current Conveyor Speed will display at the bottom of the screen.

DeltaTherm IR Cure Module
Revision C / September 2022
Page 19 of 41
• 60B59B59BWhen in Auto Cycle, the DeltaTherm IR Cure Module operates the exhaust fan
and the intake fan.
• 61B60B60BThe IR panels will start and increase to the set system parameters. It may take a
few minutes to increase to the set values.
• 62B61B61BWhen the machine is in the range of the system parameters, auto cycle will start.
Differences in the parameters may occur to maintain optimum conditions.
274B273B273BNote: With two-sided IR ovens, the upper panels may indicate temperatures higher
than the setpoint due to absorption of energy from the lower panels. This is normal.
• 63B62B62BIf the DeltaTherm IR Cure Module is the last machine in a line, the alarm will
signal when a board exits. This only occurs if a downstream SMEMA signal is not
present.
• 64B63B63BWhen the conveyors stop for a board to be removed, the cure module will
maintain the parameters. The module will not time-out if a board is not removed.
• 65B64B64BIn Auto Cycle, the PLC will send a signal through the RS485 cable to the next
machine every 5 seconds to tell the next machine the width of the conveyor.
• 66B65B65BPush the Home Button on screen or F3 Key to leave Auto Cycle at any time.
Boards in the system are not removed when you exit.
275B274B274BNote: Make sure all boards have exited the system before you exit Auto Cycle.