Machine Automa tion Controller NX1P 9 Heater Burnout De tection Units Load Cell Inpu t Unit * Refer to the NX-series Load Cell Input Unit User’s Manual (W565) for detailed information on I/O refresh cycle. Position inter…

100%1 / 41
Machine Automation Controller NX1P
8
Temperature Control Units
Temperature Input Units
*1. The resolution is 0.2°C max. when the input type is R, S, or W.
*2. The NX-TS2202 and NX-TS3202 only supports Pt100 three-wire sensor.
Product
name
Specifications
Model
Number
of
channels
Input type Output
Number
of output
points
Number of
CT input
points
Control type
Conversion
time
I/O
refreshing
method
Advanced
Temperature
Control Unit
4
Universal input
(themocouple,
resistance ther-
mometer, ana-
log voltage,
analog current)
Voltage output
(for driving SSR)
4 4 Heating/cooling control
50 ms
Free-Run
refreshing
NX-HTC3510-5
Linear current putput
8
Voltage output
(for driving SSR)
8 8 Standard control
NX-HTC4505-5
Temperature
Control Unit
2-channel
Type
2
Universal
input
(thermocou-
ple, resistance
thermometer)
Voltage output
(for driving SSR)
2
2 Standard control NX-TC2405
None Standard control NX-TC2406
Voltage output
(for driving SSR)
4 None Heating/cooling control NX-TC2407
Linear current output 2 None Standard control NX-TC2408
Temperature
Control Unit
4-channel
Type
4
Voltage output
(for driving SSR)
4
4 Standard control NX-TC3405
None Standard control NX-TC3406
Voltage output
(for driving SSR)
8 None Heating/cooling control NX-TC3407
Linear current output 4 None Standard control NX-TC3408
Product
Name
Specification
Model
Number
of points
Input type
Resolution
(25°C)
Over all accuracy (25°C)
Conversion time
I/O refreshing
method
Terminals
Thermocouple
Input type
2 points
Thermocouple
0.1°C max.
*1
Refer to your OMRON
website for details.
250 ms/Unit
Free-Run
refreshing
16 Terminals NX-TS2101
4 points 16 Terminals
x 2 NX-TS3101
2 points
0.01°C max. 10 ms/Unit
16 Terminals NX-TS2102
4 points 16 Terminals x 2 NX-TS3102
2 points
0.001°C max.
60 ms/Unit
16 Terminals NX-TS2104
4 points 16 Terminals x 2 NX-TS3104
Resistance
Thermometer
Input type
2 points
Resistance
Thermometer
(Pt100/Pt1000, three-
wire) *2
0.1°C max. 250 ms/Unit
16 Terminals NX-TS2201
4 points 16 Terminals x 2 NX-TS3201
2 points
0.01°C max. 10 ms/Unit
16 Terminals NX-TS2202
4 points 16 Terminals x 2 NX-TS3202
2 points
0.001°C max.
60 ms/Unit
16 Terminals NX-TS2204
4 points 16 Terminals x 2 NX-TS3204
Machine Automation Controller NX1P
9
Heater Burnout Detection Units
Load Cell Input Unit
* Refer to the NX-series Load Cell Input Unit User’s Manual (W565) for detailed information on I/O refresh cycle.
Position interface: Incremental Encoder Input Units
Position interface: SSI Input Units
Product Name
Specification
Model
CT input section Control output section
Number of
inputs
Maximum heater
current
Number of
outputs
Internal I/O common
Maximum
load current
Rated voltage
I/O refreshing
method
Heater Burnout
Detection Unit
4 50 AAC 4
NPN
0.1 A/point,
0.4 A/Unit
12 to
24 VDC
Free-Run
refreshing
NX-HB3101
PNP 24 VDC NX-HB3201
Product Name
Specification
Model
Number of Model
Standards points
Conversion
cycle
I/O refreshing method *
Load cell excitation
voltage
Input range
Load Cell Input
Unit
1 125 μs
Free-Run refreshing
Synchronous I/O refreshing
Task period prioritized refreshing
5 VDC ± 10% -5.0 to 5.0 mV/V NX-RS1201
Product Name
Specification
Model
Number of
channels
External
inputs
Maximum response
frequency
I/O refreshing method
Number of I/O
entry mappings
Incremental
Encoder Input
Unit
1 (NPN) 3 (NPN)
500 kHz
Free-Run refreshing
Synchronous I/O refreshing
1/1
NX-EC0112
1 (PNP) 3 (PNP) NX-EC0122
1
3 (NPN)
4 MHz
NX-EC0132
3 (PNP) NX-EC0142
2 (NPN)
None 500 kHz 2/2
NX-EC0212
2 (PNP) NX-EC0222
Product Name
Specification
Model
Number of
channels
Input/Output form Maximum data length
Encoder power
supply
Type of external connections
SSI Input Unit
1
EIA standard
RS-422-A
32 bits
24 VDC,
0.3 A/CH
Screwless push-in terminal block
(12 terminals)
NX-ECS112
2
EIA standard
RS-422-A
32 bits
24 VDC,
0.3 A/CH
Screwless push-in terminal block
(12 terminals)
NX-ECS212
Machine Automation Controller NX1P
10
Position interface: Pulse Output Units
*1. This is the number of pulse output channels.
*2. Unit version 1.2 or later and an NX-ECC203 EtherCAT Coupler Unit are required.
EtherCAT Slave Unit
*1. The following shows the contents of the TxPDO data.
• I/O data set from the CPU Unit to the EtherCAT master: 1,200 bytes or less
• Status to notify the EtherCAT master: 4 bytes or less
Communications Interface Units
RFID Units
Product Name
Specification
Model
Number of
channels *1
External
inputs
External
outputs
Maximum
pulse output
speed
I/O refreshing method
Number of I/O
entry mappings
Control output
interface
Pulse Output
Unit
1 (NPN) 2 (NPN) 1 (NPN)
500 kpps
Synchronous I/O refreshing
Task period prioritized
refreshing *2
1/1
Open collector
output
NX-PG0112
1 (PNP) 2 (PNP) 1 (PNP) NX-PG0122
2
5 inputs/CH
(NPN)
3 outputs/CH
(NPN)
4 Mpps
2/2
Line driver
output
NX-PG0232-5
5 inputs/CH
(PNP)
3 outputs/CH
(PNP)
NX-PG0242-5
4
5 inputs/CH
(NPN)
3 outputs/CH
(NPN)
4/4
NX-PG0332-5
5 inputs/CH
(PNP)
3 outputs/CH
(PNP)
NX-PG0342-5
Product name
Specifications
Model
Send/receive PDO data sizes *
1
Refreshing method
EtherCAT
Slave Unit
Data input by the EtherCAT master (TxPDOs)
1,204 bytes max.
Data output by the EtherCAT master (RxPDOs)
1,200 bytes max.
Free-Run Mode NX-ECT101
Product Name
Serial interface
External connection terminals
Number of
serial ports
Communications protocol Model
Communicatio
ns Interface
Unit
RS-232C
Screwless Clamping Terminal Block 1 port
No-protocol
Signal lines
NX-CIF101
RS-422A/485 NX-CIF105
RS-232C D-Sub connector 2 ports NX-CIF210
Product name Amplifier/Antenna No. of unit numbers used Model
RFID Unit (1Ch)
V680 series
1 NX-V680C1
RFID Unit (2Ch)
2 NX-V680C2