ThermoFlex-Manual.pdf - 第26页

Section 2 2-8 ThermoFlex Thermo Scientific Pumping Capacity Centrifugal Pump P 5 • Pump curves are nominal values. Pressure values for centrifugal and turbine pumps are differential pressures between the inlet and the out…

100%1 / 138
Section 2
ThermoFlex 2-7
Thermo Scientific
Pumping Capacity
Positive Displacement Pump P 1/P 2
• Pump curves are nominal values. Pressure values for centrifugal pumps are differential pressures
between the inlet and the outlet of the chiller.
• Pump performance results were obtained with no restrictions on the return to the system or with
any options installed. For example, utilizing the DI option will result in a 0.5 gpm ow reduction .
• Specications obtained at sea level using water as the recirculating uid, at a 20°C process
setpoint, 25°C ambient condition, at nominal operating voltage. Other uids, uid temperatures,
ambient temperatures, altitude or operating voltages will affect performance. See Section 3.
• Thermo Fisher Scientic reserves the right to change specications without notice.
5 10 15 20 LPM
1 2 3 4 5 GPM
A
B
C
D
100
80
60
40
20
7
6
5
4
3
2
1
Bar PSIG
Pressure
Flow Rate
Pressure
100
80
60
40
20
7
6
5
4
3
2
1
20 40 60 80 100 LPM
5 10 15 20 25 GPM
Flow Rate
Bar PSID
A
B
C
D
A: P 4, 60 Hz
B: P 4, 50 Hz
C: P 3, 60 Hz
D: P 3, 50 Hz
Pumping Capacity
Centrifugal Pump P 3/P 4
A: P 2/MD 2, 60 Hz
B: P 2/MD 2, 50 Hz
C: P 1/MD 1, 60 Hz
D: P 1/MD 1, 50 Hz
Section 2
2-8 ThermoFlex
Thermo Scientific
Pumping Capacity
Centrifugal Pump P 5
• Pump curves are nominal values. Pressure values for centrifugal and turbine pumps are differential
pressures between the inlet and the outlet of the chiller.
• Pump performance results were obtained with no restrictions on the return to the system or with
any options installed. For example, utilizing the DI option will result in a 0.5 gpm ow reduction.
• Specications obtained at sea level using water as the recirculating uid, at a 20°C process
setpoint, 25°C ambient condition, at nominal operating voltage. Other uids, uid temperatures,
ambient temperatures, altitude or operating voltages will affect performance. See Section 3.
• Thermo Fisher Scientic reserves the right to change specications without notice.
25 50 75 100 125 150 LPM
10 20 30 40 GPM
60 Hz
50
Hz
100
80
60
40
20
7
6
5
4
3
2
1
Bar PSID
Pressure
Flow Rate
Pumping Capacity
Turbine Pump T 1/ T 5
A
B
C
D
10 20 30 40 LPM
2 4 6 8 10 12 GPM
100
80
60
40
20
7
6
5
4
3
2
1
Bar PSID
Pressure
Flow Rate
A: T 5 , 60 Hz
B: T 5, 50 Hz
C: T 1, 60 Hz
D: T 1, 50 Hz
Section 2
ThermoFlex 2-9
Thermo Scientific
Pumping Capacity
Turbine Pump T 0
• Pump curves are nominal values. Pressure values for turbine pumps are differential pressures
between the inlet and the outlet of the chiller.
• Pump performance results were obtained with no restrictions on the return to the system or
with any options installed. For example, utilizing the DI option will result in a 0.5 gpm ow
reduction .
• Specications obtained at sea level using water as the recirculating uid, at a 20°C process
setpoint, 25°C ambient condition, at nominal operating voltage. Other uids, uid temperatures,
ambient temperatures, altitude or operating voltages will affect performance. See Section 3.
• Thermo Fisher Scientic reserves the right to change specications without notice.
60 Hz
50 Hz
160
140
120
100
80
60
40
20
10
8
6
4
2
Bar PSID
Pressure
2.5 5.0 7.5 10.0 12.5 LPM
0.5 1.0 1.5 2.0 2.5 3.0 GPM
Flow Rate