Y e ar ly Inspe ction and Appe ndix Chap ter 6 Multi -Func tional Placer ST M1-S M ain ten an ce Ha nd bo ok 6-9 Ring blower inverter setup C03 Intelligent input terminal 3 is set. "0-FW(Forward operation command) 1…

100%1 / 84
Yearly Inspection and Appendix
Chapter 6
Multi-Functional Placer
STM1-S Maintenance Handbook
6-8
Ring blower inverter setup
Yearly Inspection and Appendix
Ring blower inverter setup
Measures
Step 1.
Refer to the following configuration table for Inverter,
and modify the configuration values of the Inverter.
Function Function name Setup range Initial Setup Modified value
A01 Frequency Command method (various
speed 0 speed command modification)
0-Main body volume
1-Input from control circuit terminal
2-Standard operator
3-Remote operator(1st communication-RJ45)
4-Remote operator(2nd communication-terminal block)"
1 0 X
(Time required: 15min / No. E-3)
Yearly Inspection and Appendix
Chapter 6
Multi-Functional Placer
STM1-S Maintenance Handbook
6-9
Ring blower inverter setup
C03 Intelligent input terminal 3 is set. "0-FW(Forward operation command)
1-RV(Reverse operation command)
2-CF1(variable speed 1)
3-CF2(variable speed 2)
4-CF3(variable speed 3)
5-CF4(variable speed 4)
6-JG(Jog operation command)
8-2CH(2-step accelerate/decelerate command)
9-FRS(Free-run command)
10-EXT(External trip)t
11-USP(Unattended Start Protection)
12-SFT(Soft lock)
13-AT(Analog input voltage/current switchover)
14-RS(Reset)
15-STA(Start)
16-STP(Maintain)
17-F/R(Forward/reverse)
18-UP(Remote control UP)
19-DOWN(Remote control DOWN)
20-O/R(Operate/remote switchover)
21-T/R(Terminal block/remote switchover)
22-PIDIR(PID integration value reset)
23-PIDD(PID Disable)"
2 10 X
Yearly Inspection and Appendix
Chapter 6
Multi-Functional Placer
STM1-S Maintenance Handbook
6-10
Ring blower inverter setup
Yearly Inspection and Appendix
H04 Number of motor poles is selected. 2/4/6/8 poles [P] 4 2 X
H05 Motor rated current “This value is set according to the inverter capacity.
0.1-800.0[A]"
- 17 X
F01 Output frequency selection "0.00-400.0[Hz]
For sensorless vector control, 0.00-300.0[Hz]"
0.00Hz 60 O
F02 Acceleration 1 is set. 0.1~3000[sec] 30 20 O
F03 Deceleration 1 is set. 0.1~3000[sec] 30 10 O